Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

saTECH SCU

121 Series

A COMPACT SOLUTION FOR


SUBSTATION MONITORING

APPLICATION
 Gateway for obtaining and processing data from all IEDs and for the transmission to control centres.
 It supports simple and redundant configurations.
 It facilitates the integration of all substation IEDs, whether they are next-generation ones or existing IEDs
with conventional protocols.

 Simple System SCU Architecture  Dual System SCU Architecture

BENEFITS
 Native design in accordance with IEC 61850 standard, which allows for advanced monitoring strategies at
the Digital Substation.
 It facilitates the current and future coexistence of monitoring systems, allowing for the interoperability of
traditional protocols (DNP3.0, IEC 60870-5-104, Modbus) with IEC-61850 standard.
 Robust and powerful hardware that complies with the strictest international standards for operation in
Electrical Substations: IEC 61850-3, IEEE 1613, CE, FCC class A, UL, CCC.

www.arteche.com 1
1.0
MAIN FEATURES

 IEC 61850 native design. Protocols Master Slave


 High capability for Ethernet communications: Customer Server
 8 10/100/1000 Base-T RJ-45 ports.
 4 FO ports. Optional S.C. interface.
IEC 61850 MMS
Report  

 
Programmable logical functions for the
configuration of control logic in accordance with DNP3 TCP/Series
IEC 61131 standard.
 Communications through isolated serial ports: IEC 60870-5-104  
 2 DB-9 RS-232 connector ports.
 8 connector ports in terminals. MODBUS TCP/Series  
 High capability of interoperability with IEDs of
different manufacturers (ABB, Siemens, SEL,
GE, etc.) through IEC-61850 ed1 and IEC-
61850 ed2 standards, and/or conventional
protocols such as DNP3.0, IEC-60870-5-104
and Modbus.
 Historical record with large capacity. Stored in
non-volatile memory.
 Multiple synchronisation sources managed
through priorities, which allows for the
synchronisation of both the SNTP protocol and
conventional protocols.
 Integrated cybersecurity mechanisms, including
access control, secure user authentication, host
firewall, and secure protocols (SSH).
 Hardware design with no removable parts and
a solid-state storage.
 Redundancy: Database synchronisation
management system between the main and
standby equipment, automatic failover
switching and virtual network management.
PRP upon request (IEC-62439-3).
 Substation and equipment configuration
software—saTECH CNF.

www.arteche.com 2
1.0
TECHNICAL SPECIFICATIONS

GENERAL

Watchdog Watchdog hardware and software.

COMMUNICATIONS
8 10/100/1000 Mbit BASE-TX Ethernet (RJ-45)
12 Ethernet ports
4 10/100 BASE-FX SC Ethernet (Optional)

Communication Ports RS-232 Canon DB9 ports


10 Serial ports
8 RS-232/422/485 connector ports in terminals
2 3.0 USB ports at the front and 4 2.0 USB ports at the back.
IEC
61850: Client and Server.

DNP 3.0 TCP/Series: Master and Slave.

MODBUS TCP/Series: Master.


Communication Protocols IEC 61870-5-104: Master.

IEC 61870-5-101: Master. (*)

SAP-20: Master. (*)

CYBERSECURITY

Cybersecurity Secure user authentication.

Configurable firewall integrated to the equipment.


REMOTE CONTROL

Remote Control SFTP, SSH.

SYNCHRONISATION

Synchronization through network with SNTP/NTP.


Synchronisation
Synchronization through conventional protocols.
Priority management with up to 8 synchronization sources.
POWER SUPPLY

Simple or redundant power supply.


Power supply
100-240 VAC / 100-240 VDC
ENVIRONMENT

Environmental features Operation temperature: -20ºC to +70ºC.

Storage temperature: -30ºC to +85ºC


MECHANICAL FEATURES

Size 2U mechanics for 19” rack mounting.

(*) Upon request

www.arteche.com 3
1.0
TECHNICAL SPECIFICATIONS

Compliance standards
STANDARDS AND/OR
TEST REQUIRED SEVERITY LEVEL
SPECIFICATIONS

Dry heat operation temperature IEC 60068-2-2 Test Bd 70 °C

Cold operation temperature IEC 60068-2-1 Test Ad -20 °C

Dry heat storage temperature IEC 60068-2-2 Test Bb 85 °C


Environmental
Cold storage temperature IEC 60068-2-1 Test Ad -30 °C

Temperature change IEC 60068-2-14 Test Nb 70 °C and -20 °C

93% humidity, 40 °C during 10


Wet heat IEC 60068-2-2 Test Acb
days
vibration IEC 60255-21-1 Class 1
Mechanical Shocks IEC 60255-21-2 Class 1
Bump IEC 60255-21-2 Class 1
6 kV contact
IEC61000-4-2
8 kV air
Electrostatic discharges
6 kV contact
IEEE 1613-2009-8
15 kV air

80 MHz - 3,000 MHz


IEC61000-4-3 AM 80%, 1KHz, 10 V/m
electromagnetic field immunity

Fast transients IEC61000-4-4 4 KV


4,0 kV earth line
Surge Immunity IEC61000-4-5
2,0 kV earth line
Conducted disturbances IEC61000-4-6 AM 80%, 1 KHz, 10 V

Power frequency magnetic field 100 A/m continuous


IEC61000-4-8
immunity 1000 A/m 1s

100 A/m continuous


IEEE 1613-2009-7
1000 A/m 1s
Electromagnetic
compatibility
80 MHz – 1 GHz AM 80%, 1
KHz, 20 V/m;
Damped oscillatory magnetic 1.0 GHz – 3.8 GHz 80% AM, 1
field immunity KHz, 10 V/m,
IEC61000-4-10 Exact frequency tests at 1.732
GHz, 1.8 GHz, 2.31
GHz, 2.45 GHz, and 5.8 GHz,
modulated pulse (50% cycle)

Δ U 30% during 1 period

Voltage dips, short interruptions Δ U 60% during 50 periods


IEC61000-4-11
and voltage variations immunity Δ U 100% during 5 periods
Δ U 100% during 50 periods
Δ U 30% during 0,1 s
Voltage dips, short interruptions
and voltage variations on d.c. IEC61000-4-29 Δ U 60% during 0,1 s
input power port immunity
Δ U 100% during 0,05 s

www.arteche.com 4
1.0
Immunity to conducted,
common mode disturbances in 30 V continuous
IEC61000-4-16
the frequency range 0 Hz to 300 V 1s
150 kHz

Ripple on d.c. input power port


IEC61000-4-17 10% of the Un
immunity.

Damped oscillatory wave 2,5 kV common mode


IEC61000-4-18
immunity. 1,0 kV differential mode
Conducted emissions CISPR 22 Class A
Radial emissions CISPR 22 Class A
EN 60950-1: 2006 + A11: 2009 + A1: 2010 + A12: 2011 + A2: 2013
Security
IEC 60950-1: 2005 + A1: 2009 + A2: 2013

www.arteche.com 5
1.0
FRONT AND REAR VIEW

1 8 9
2 4 6

3 5 7

10 11

1  USB 7  Program LED


2  Power key 8  LAN1-8
3  Reset 9  COM1-10
4  PWR1 10  Slot1 LED
5  PWR2 11  Slot2 LED
6  HDD

5 10
7 8 9 11
1 3

2 4 6 14 12 13

1  Power 1 8  USB
2  Power 2 9  LAN1-8
 Power1 key / Power 2
3 10  COM 1-2
key (option)
4  Relay 11  COM 3-10
5  HDD 12  E/S
6  DVI 13  IRIG-B
7  VGA 14  LAN 9-12 FO SC connector

www.arteche.com 6