SEBALECTRIC

PASSENGER TERMINAL BUILDING (PTB)


DISTRIBUTION PANEL: URP-UR2A(B)

LOAD DESCRIPTION BREAKERS BREAKERS LOAD DESCRIPTION


CCT# PH CCT#
LOAD FEEDER & FEEDER & LOAD
DESCRIPTION GFI OTHER 20A/1P 15A/1P 15A/1P 20A/1P OTHER GFI DESCRIPTION
(KW) CONDUIT CONDUIT (KW)

SPARE x 31 A 32 x 2#12+G, 21mmC 0.6 2 x duplex, FIDS

CNT 2C 1.5 2#12+G, 21mmC 30A-1P 33 B 34 x 2#12+G, 21mmC 2x DUPLEX IDS (axis 8)

SPACE 35 C 36 x 2#12+G, 21mmC 1.5 5 x duplex, FIDS, CUSS

5 x duplex, FIDS,CUSS 1.5 2#12+G, 21mmC x 37 A 38 x 2#12+G, 21mmC 1.5 5 x duplex, FIDS

5 x duplex, FIDS 1.5 2#12+G, 21mmC x 39 B 40 x 2#12+G, 21mmC 1.5 5 x duplex, FIDS, CUSS

EF-2-6 0.5 2#12+G, 21mmC x 41 C 42 x 2#12+G, 21mmC 1.5 5 x duplex, FIDS

SPACE 43 A 44 x 2#12+G, 21mmC 2 x Kiosks, Check-in

45 B 46 x 2#12+G, 21mmC 2 x Kiosks, Check-in

STARTER CONTROL 3#12, 21mmC 20A-3P 47 C 48 x 2#12+G, 21mmC 2 x Kiosks, Check-in

49 A 50 x 2#12+G, 21mmC 2 x Kiosks, Check-in

2 x Kiosks, Check-in 2#12+G, 21mmC x 51 B 52 x 2#12+G, 21mmC 2 x Kiosks, Check-in

2 x Kiosks, Check-in 2#12+G, 21mmC x 53 C 54 x 2#12+G, 21mmC 2 x Kiosks, Check-in

2 x Kiosks, Check-in 2#12+G, 21mmC x 55 A 56 SPACE

SPACE 57 B 58 SPACE

SPACE 59 C 60 SPACE

PANEL: URP-UR2A(B) VOLTAGE: 120/208V, 3PH, 4W LOCATION: Elec. Rm. 2A003

PANEL TYPE: NQ BREAKER: YES FED FROM: URP-UR2A(A)

NOTES: 1. 15A/1P AND 20A/1P SHALL BE COMPLETE WITH 2#12+G IN 21mmC OR OTHERWISE NOTED.
2. PANEL COMES COMPLETE WITH INTEGRATED TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS).