V5 X VRF 60Hz

MV5-X2345W/V2DN1 / MV5-X2405W/V2DN1 / MV5-X2460W/V2DN1


Table 2-1.14: MV5-X2345(2405, 2460)W/V2DN1 specifications
HP 84 86 88
Model name (Combination unit) MV5-X2345W/V2DN1 MV5-X2405W/V2DN1 MV5-X2460W/V2DN1
Combination type 18HP+22HP×3 20HP+22HP×3 22HP×4
Power supply 3 phase, 220V, 60Hz
kW 234.5 240.5 246
Capacity
kBtu/h 800 820.5 839.2
Cooling1
Power input kW 62.15 63.84 65.78
EER 3.77 3.77 3.74
kW 263 270 276
Capacity
kBtu/h 897.3 921.1 941.6
Heating2
Power input kW 64.54 66.66 68.49
COP 4.07 4.05 4.03
Connected Total capacity 50-130% of outdoor unit capacity
indoor units Maximum quantity 64
Type DC inverter
Quantity 8
Compressors
Oil type FV68H
Start-up method Soft start

Part 2 - Outdoor Unit Engineering Data


Type Propeller
Motor type DC
Quantity 8
(520+440)+(550+430)+ (550+430)+(550+430)+ (550+430)+(550+430)+
Motor input W
Fans (550+430)+(550+430) (550+430)+(550+430) (550+430)+(550+430)
(420+350)+(440+350)+ (440+350)+(440+350)+ (440+350)+(440+350)+
Motor output W
(440+350)+(440+350) (440+350)+(440+350) (440+350)+(440+350)
Airflow rate m3/h 64000
Drive type Direct
Type R410A
Refrigerant
Factory charge kg (lbs.) 13+16×3 (29+35×3) 16×4 (35×4) 16×4 (35×4)
Liquid pipe mm (in.) Φ25.4 (Φ1)
Pipe
Gas pipe mm (in.) Φ44.5 (Φ1-3/4)
connections3
Oil balance pipe mm (in.) Φ6.35 (Φ1/4)
Sound pressure level4 dB(A) 70
mm (1340×1635×790)×4
Net dimensions (W×H×D)
in. (52-3/4×64-3/8×31-1/8)×4
mm (1405×1805×855)×4
Packed dimensions (W×H×D)
in. (55-3/8×71-1/16×33-5/8)×4
305+340×3
Net weight kg (lbs.) 340×4 (750×4) 340×4 (750×4)
(673+750×3)
323+358×3
Gross weight kg (lbs.) 358×4 (790×4) 358×4 (790×4)
(712+790×3)
Operating temperature range °C (°F) Cooling: -5 to 48 (23 to 118.4); heating: -20 to 24 (-4 to 75.2)
High/low pressure switch, fan driver overload protector, overcurrent relay, inverter
Safety devices
overload protector, overvoltage protector
Standard accessories Installation manual, operation manual, connection pipes, clamps
Notes:
1. Indoor air temperature 27°C (80.6°F) DB, 19°C (66.2°F) WB; outdoor air temperature 35°C (95.0°F) DB; equivalent refrigerant Conversion Formulae:
piping length 7.5m (24.6ft.) with zero level difference. kBtu/h = kW × 3.412;
2. Indoor air temperature 20°C (68.0°F) DB; outdoor air temperature 7°C (44.6°F) DB, 6°C (42.8°F) WB; equivalent refrigerant in.W.G. = Pa × 0.004;
piping length 7.5m (24.6ft.) with zero level difference. lbs. = kg × 2.2;
3. Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems in. = mm / 25.4
with total equivalent liquid piping lengths of less than 90m (295.2ft). For systems with total equivalent liquid piping lengths of 90m (295.2ft) or longer, please
refer to Part 3 “System Design and Installation” for connection piping diameters..
4. Sound pressure level is measured at a position 1m (3.28ft.) in front of the unit and 1.3m (4.26ft.) above the floor in a semi-anechoic chamber.