V5 X VRF 60Hz

MV5-X2010W/V2DN1 / MV5-X2070W/V2DN1 / MV5-X2125W/V2DN1


Table 2-1.12: MV5-X2010(2070, 2125)W/V2DN1 specifications
HP 72 74 76
Model name (Combination unit) MV5-X2010W/V2DN1 MV5-X2070W/V2DN1 MV5-X2125W/V2DN1
Combination type 10HP+18HP+22HP×2 10HP+20HP+22HP×2 10HP+22HP×3
Power supply 3 phase, 220V, 60Hz
kW 201 207 212.5
Capacity
kBtu/h 685.7 706.2 724.9
Cooling1
Power input kW 51.93 53.62 55.55
EER 3.87 3.86 3.83
kW 225.5 232.5 238.5
Capacity
kBtu/h 769.4 793.2 813.7
Heating2
Power input kW 53.36 55.48 57.31
COP 4.23 4.19 4.16
Connected Total capacity 50-130% of outdoor unit capacity
indoor units Maximum quantity 64
Type DC inverter
Quantity 7
Compressors
Oil type FV68H
Start-up method Soft start

Part 2 - Outdoor Unit Engineering Data


Type Propeller
Motor type DC
Quantity 7
(580)+(520+440)+ (580)+(550+430)+ (580)+(550+430)+
Motor input W
Fans (550+430)+(550+430) (550+430)+(550+430) (550+430)+(550+430)
(465)+(420+350)+ (465)+(440+350)+ (465)+(440+350)+
Motor output W
(440+350)+(440+350) (440+350)+(440+350) (440+350)+(440+350)
Airflow rate m3/h 60000
Drive type Direct
Type R410A
Refrigerant 9+13+16×2 9+16×3 9+16×3
Factory charge kg (lbs.)
(20+29+35×2) (20+35×3) (20+35×3)
Liquid pipe mm (in.) Φ25.4 (Φ1)
Pipe
Gas pipe mm (in.) Φ44.5 (Φ1-3/4)
connections3
Oil balance pipe mm (in.) Φ6.35 (Φ1/4)
Sound pressure level4 dB(A) 69
mm (990×1635×790)+(1340×1635×790)×3
Net dimensions (W×H×D)
in. (39×64-3/8×31-1/8)+(52-3/4×64-3/8×31-1/8)×3
mm (1090×1805×860)+(1405×1805×855)×3
Packed dimensions (W×H×D)
in. (42-7/8×71-1/16×33-7/8)+(55-3/8×71-1/16×33-5/8)×3
219+305+340×2 219+340×3 219+340×3
Net weight kg (lbs.)
(483+673+750×2) (483+750×3) (483+750×3)
234+323+358×2 234+358×3 234+358×3
Gross weight kg (lbs.)
(516+712+790×2) (516+790×3) (516+790×3)
Operating temperature range °C (°F) Cooling: -5 to 48 (23 to 118.4); heating: -20 to 24 (-4 to 75.2)
High/low pressure switch, fan driver overload protector, overcurrent relay, inverter
Safety devices
overload protector, overvoltage protector
Standard accessories Installation manual, operation manual, connection pipes, clamps
Notes:
1. Indoor air temperature 27°C (80.6°F) DB, 19°C (66.2°F) WB; outdoor air temperature 35°C (95.0°F) DB; equivalent refrigerant Conversion Formulae:
piping length 7.5m (24.6ft.) with zero level difference. kBtu/h = kW × 3.412;
2. Indoor air temperature 20°C (68.0°F) DB; outdoor air temperature 7°C (44.6°F) DB, 6°C (42.8°F) WB; equivalent refrigerant in.W.G. = Pa × 0.004;
piping length 7.5m (24.6ft.) with zero level difference. lbs. = kg × 2.2;
3. Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems in. = mm / 25.4
with total equivalent liquid piping lengths of less than 90m (295.2ft). For systems with total equivalent liquid piping lengths of 90m (295.2ft) or longer, please
refer to Part 3 “System Design and Installation” for connection piping diameters..
4. Sound pressure level is measured at a position 1m (3.28ft.) in front of the unit and 1.3m (4.26ft.) above the floor in a semi-anechoic chamber.

201610 33