CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Composite Beam Design with Verco Floor Deck Based on AISC 360-05 / IBC 2006
DESIGN CRITERIA
The input STUDS SPACING must be based on actual deck ribs spacing for perpendicular to beam. For the following total [15] studs, if ribs spacing
12" o. c., the minimum composte beam capacity is from
2 rows @ 12" o.c., not one row @ 8.57" o.c.
ANALYSIS
DETERMINE REACTIONS, MOMENTS & SHEARS
w1 = ws1+ wwt= 98.6972148 +( 43.50 + 5.17 ) = 147.37 lbs / ft2
= 1.43 kips / ft (total gravity loads on span beam)
w2 = ws,2+ wwt= 121.327215 +( 43.50 + 5.17 ) = 170.00 lbs / ft2
= 1.64 kips / ft (uniform gravity loads on cantilever)
P= 3.3845 kips
X1 = 20.94 ft R1 = 29.85 kips
X2 = 20.94 ft R2 = 38.67 kips
X3 = 0.54 ft Vmax = 34.00 kips, at R2 left.
Mmax = 312.5 ft-kips Mmin = -16.282 ft-kips
tw = 0.36 in tf = 0.57 in
(cont'd)
AF y
h for Atotal 2 Actr
0.85 f 'cb
yb d 0.5 Atotal Actr for Atotal 2 Actr A f
bf
21.8 in, (plastic neutral axis to bottom)
t Atotal A f 0.5 A fill for A
f total 2 Actr A f
tw
0 r b
0.5 t h y for Atotal 2 A ctr
0.5 t 0 A ctr 0.5 dA 0.5 A total A ctr h d y b
y h
0.5 Atotal
for Atotal 2 A ctr A f
0.5 t 0 A total A f t 0 h r t f 0.5 A fill t 0 h r 2 t f t w d y t f h 0.5 d 0.5 y 0.5 t f t w y t f 0.5 y b 0.5t f
h
b
0.5 A total
b b
for A total 2 A ctr A f
thus, y= 14.0 in, (moment arm between centroid of tensile force and the resultant compressive force.)
E
n 13.01 , (ACI 318-05 8.5.1)
Ec
Actr t 02
I tr I x A y b 0.5d Actr 0.5t 0 h r d y b
2 2
2636 in4
12
I tr
S tr 146 in3, referred to steel bottom.
yb
I tr
St 425 in3, referred to concrete top.
d hr t 0 yb
CHECK BENDING & SHEAR CAPACITIES
Middle Bottom : Mmax = (Ztr / Zx) MDL + MLL = 452.2 ft-kips
< Mn / Wb = Ztr Fy / Wb = 593.0 ft-kips, (AISC 360 I3.2a) [Satisfactory]
where Wb = 1.67 (AISC 360-05 I3.2a)
3.76(E / Fy )0.5 = 90.55 > h / tw = 50.70
Cantilever Top : Mmin = -16.28179 ft-kips < M n / Wb = 252.0 ft-kips, (AISC 360 I3.2b) [Satisfactory]
where Wb = 1.67 (AISC 360-05 I3.2b)
Lb = MAX( X3 , L2) = 2.85 ft
Lp = 1.76 ry (E / Fyf)0.5 = 5.83 ft
2
E Jc 0.7 F y S x h 0
L r 1.95 r ts 1 1 6.76
E 16.96 ft
0.7 F y S x h0 Jc
M p = Fy Z x = 420.8 ft-kips
2
C b 2E Jc L b
F cr 1 0.078 1265.34 ksi
S x h 0 r ts
2
Lb
r ts
S eff S s 2
V ' MAX S tr S s , 0.25 C f 183.75 kips, (AISC 360-05 C-I3-4)
Qn = MIN [ 0.5 Asc (fc' Ec)0.5 , RgRpAscFu] = 15.37 kips, (AISC 360-05 I3.2d.3)
where wc = 115 pcf
Ec = wc1.5 33 (fc')0.5 = 2229.06 ksi
Asc = 0.44 in2
Fu = 58 ksi
Rg = 1.00 (AISC 360-05 Table I3.2b.3)
Rp = 0.60 (AISC 360-05 Table I3.2b.3)
P a 2 L a w1 L 3a w 2 a 3 4 L 3a
End -0.21 in, uplift perpendicular to beam.
3EI 24 EI 24 EI
Pa L 2 5w1 L 4 w 2 L 2a 2
Mid 1.06 in, downward perpendicular at middle of beam.
16 EI 384 EI 32 EI
USE C = 1 0/4" AT MID BEAM.
Pa 2 L a w 3a w 2 a 3 4 L 3a
End 1L -0.63 in, uplift.
3 EI 24 EI 24 EI
< 2L2 / 240 = 0.28 in [Satisfactory]
Pa L 2 5w1 L 4 w 2a 2
Mid 2L 0.92 in, downward.
16 E I eff 384 E I eff 32 E I eff
Technical References:
1. AISC 360-05: "Specification for Structural Steel Buildings", American Institute of Steel Construction, March 9, 2005.
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Steel Beam Design with Gravity Loading Based on AISC-ASD 9th
ANALYSIS
DETERMINE REACTIONS, MOMENTS & SHEARS
w DL ,1 w
R 2 0.5 w LL ,1 L1 DL ,2 w LL ,2 L1 0.5 L 2 L 2 P L1 L 2
cos cos L1 L1
= 38.67 kips
w DL ,1 w
R1 w LL ,1 L1 DL ,2 w LL ,2 L 2 P R 2
cos cos
= 29.85 kips
X1 = 20.94 ft
X2 = 20.94 ft
X3 = 0.54 ft
w DL ,2
M Min 0.5 w LL ,2 L 22 P L 2 16.3 ft-kips
cos
X 1 X 2
2
wDL ,1
M Max wLL ,1 312.5 ft-kips
cos 8
2
M1 M1
C b 1.75 1.05 0.3 1.75 , since M1 is 0
M2 M2
rT = 1.94 in , Af = 4.27 in2
76b f 20000
L c MIN , 6.72 ft
Fy
d / A f F y
102000C b 12000C b
L u MAX r T , 13.85 ft
Fy 0.6 d / A f F y
510000C b
L3 r T 21.60 ft
Fy
(cont'd)
2 F yl / r T
2
F b1 MIN F y , 0.6 F y 30.0 ksi
3 1530000C b
170000C Fy
F b 2 MIN
b
, 16.7 ksi
l / r T 2 3
12000C
b
F b3 MIN , 0.6 F y 30.0 ksi
l d / A f
0.66 F y , for l L c
0.6
F y , for L c l L u
Fb 33.0 ksi
MAX F b1 , F b3 , for L u l L 3
MAX F
b 2 , F b3 , for l L 3
Pa 2 L a w1 L 3a w 2 a 4 L 3a
3
End -0.21 in, uplift perpendicular to beam.
3EI 24 EI 24 EI
USE C = 1/4" AT CANTILEVER.
Pa L 2 4 2 2
5w1 L w a
Mid 2L 1.06 in, downward perpendicular at middle of beam.
16 EI 384 EI 32 EI
USE C = 4/4" AT MID BEAM.
Pa 2 L a w 3a w 2 a 3 4 L 3a
End 1L cos -0.63 in, uplift to vertical direction.
3 EI 24 EI 24 EI
> 2L2 / 240 = 0.28 in [Unsatisfactory]
Pa L 2 5w1 L 4 w 2 L 2 a 2
Mid cos 0.92 in, downward to vertical direction.
16 EI 384 EI 32 EI
< L1 / 240 = 2.12 in [Satisfactory]