1. Assuming infinite available fault current at Transformer primary terminals. MERALCO maximum
size of Single-phase Transformer is 75 KVA.
FULL LOAD AMPS (FLA) = (75KVA x 1000) / 230V = 326 Amps
Transformer Multiplier: M = 100 / %Z = 100/1.4 = 71.43
Short Circuit Current = 326 x 71.43 = 23,286 Amps. (23.3 kA)
The 125AT Circuit Breaker Main Service Equipment must have at least 14.9 kA interrupting Capacity
(KAIC), Symmetrical @ 240V.
The Main and Branch Circuit Breakers of Panel Board must have at least 9.05 kA Interrupting
Capacity , Symmetrical @ 240V .
The electrical design meets the PEC 2017 requirements of 5.0 Maximum Voltage Drop on Feeders and Branch
Circuits [ PEC 2017 Part 1 Ed., 2.10.2.2, FPN No. 4, page 42 and 2.15.1.2(A)(1)(b), FPN No. 2, page 51].