SYMBOL DESCRIPTION SPECIFICATIONS REMARKS
W V CW HW
”
KOHLER HIGHCLIFF K-96057. (1.28 GPF) WHITE VITREOUS CHINA
WATERCLOSET -
FLOOR MOUNTED ELONGATED. 12" ROUGH-IN, 16 7/8" RIM HEIGHT,
FLOOR MOUNTED - FLUSH
P-1 3" 2" 1" --- FULLY GLAZED TRAPWAY, AND BOLT CAPS. SEAT SHALL BE WHITE,
VALVE
LUSTRA K-4650-A. FLUSH VALVE SHALL BE SLOAN OPTIMA PLUS
(ADA COMPLIANT)
8111-1.28 (HANDS FREE).
STORAGE RECOVERY @ 90
NO OF ELECTRICAL INPUT
” MARK LOCATION TYPE CAPACITY °F RISE NOTES MANUFACTURER MODEL NO
ELEMENTS
GAL GPH TOTAL kW
KATHLEEN, GA 31047
3 PROVIDE WITH GLASS-LINED TANK, SACRIFICIAL ANODE, AND MINIMUM FIVE YEAR WARRANTY.
4 PROVIDE WITH INTERNAL DIP TUBE AND PRESSURE RELIEF VALVE. PIPE RELIEF VALVE DISCHARGE TO SAFETY PAN BELOW HEATER.
5 TOTAL KW IS BASED ON THE OPERATION OF ALL ELEMENTS.
2440 GA-127
INSTANTANEOUS WATER HEATER SCHEDULE
NO OF ELECTRICAL INPUT
MARK LOCATION TYPE TEMP CHANGE AT NOTES MANUFACTURER MODEL NO
ELEMENTS
TOTAL kW VOLT / PH
IWH-1 215 - R.R. ELEC 71oF AT 0.4 GPM 1 4.16 208/ / 1 1 CHRONOMITE SR-20L/208
PUMP SCHEDULE
FLOW HEAD TEMPERATURE NOMINAL POWER
MARK LOCATION SYSTEM TYPE SPEED CONTROL NOTES MANUFACTURER MODEL
GPM FT °F HP
MECHANICAL AND
CP-1 EWH-1 INLINE 3 3.5 104 1/40 CONSTANT 1,2 TACO 003-ST4
ELECTRICAL
NOTES (APPLICABLE TO THIS SCHEDULE)
POWER CORD CONNECTED TO PUMP SHALL BE A ONE PIECE CORD. NO EXTENSIONS SHALL BE USED. UNIT SHALL BE RATED FOR 115V ELECTRICAL OUTLET AND HAVE A
1
THREE PRONG CONNECTION.
2 PROVIDE WITH AQUASTAT CONTROL TO REGULATE TEMPERATURE AT A SETPOINT.