Installation and Maintenance Instructions

for ASHCROFT® High Pressure L-Series


Snap Action Switches with Buna N, Viton and
Teflon Diaphragms for Pressure Control

psi Ranges
6.09
(155)
4.12
(105) 2.06
(52)

3.98
(101)
0.25 3.94
(6) (100)
0.38 4.72
(10) (120)

1.21
3/4 NPT (31)
0.43
(11) 2.25 PRESSURE PORT
(57) 1/4 NPT FEMALE 3.26
(83)
2.50 X06
(64)
1/2 NPT MALE &
1/4 NPT FEMALE

2.7 lbs.

STANDARD RANGES
*1000, 2000, 3000 psi

OPERATION
The ASHCROFT® pressure control is a precision device which
features a snap action switch. Fixed deadband is available with
single or dual SPDT independently adjustable switches with
various electrical ratings. Adjustable deadband is available with
SPDT switch with various electrical ratings. Several wetted
material constructions for compatibility with pressure media may
be obtained.
Series LP-S switches have a fixed deadband which will be

ELECTRICAL CONNECTION
within the limits noted on the nameplate.
Series LP-D switches may be set to operate simultaneously or
up to 85 percent of the range apart. The deadband of each Remove cover, held in place by two screws.
switch will be within the limits noted on the nameplate. On all units except one with terminal blocks – wire directly to
Series LP-A switches may be set to operate with any the switch according to circuit requirements. Units with terminal
deadband within the limits shown on the nameplate. blocks – wire directly to terminal blocks as required. Terminals
MOUNTING
are marked common (C), normally open (NO) and normally
closed (NC).
The “L” Series ASHCROFT snap action pressure switch has a
NEMA-4 enclosure which is an epoxy coated aluminum casting.
Two holes in the integral bracket are used to surface mount
the control. Location of these holes is shown on the general
dimension drawings. An optional pipe mounting bracket is also LEFT SWITCH RIGHT SWITCH
TERMINAL BLOCK TERMINAL BLOCK
available. Mount on a vibration free surface or pipe in any orien-

wrench flats or hex on the pressure connection. NEVER


tation. When tightening control to pressure line, always use the
NC
TIGHTEN BY TWISTING THE CASE.
1

CONDUIT CONNECTIONS
NO
2

One 3⁄4 NPT hole fitted with a shipping plug, and two additional
knock outs are provided. The knockouts may be removed by
3

C
placing a screwdriver in the slot and rapping sharply with a
hammer It is recommended that Teflon tape or other sealant be
used on conduit bushings or plug threads to ensure integrity of SERVICE LEADS TO THESE TERMINALS
the enclosure.

© 2014 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com
All sales subject to standard terms and conditions of sale. All rights reserved. I&M009-10213 L Series 03/2014
Installation and Maintenance Instructions
for ASHCROFT® High Pressure L-Series
Snap Action Switches with Buna N, Viton and
Teflon Diaphragms for Pressure Control

SETPOINT ADJUSTMENTS SERIES LP-A ADJUSTABLE DEADBAND SWITCH


Setpoints are changed by means of the setpoint adjusters The Remove cover. Adjuster “B” controls the operating point of
LP-S single switch has one adjuster and the LP-A adjustable the switch on increasing pressure. Adjuster “A” controls the
deadband and LP-D dual switch each have two adjusters. On re-setpoint of the switch on decreasing pressure.
switches with two adjusters, the one on the left is referred to as For accurate setpoint adjustment, mount the switch on a
“A” and the right one is referred to as “B”; see illustration. calibration stand and use a suitable reference such as an
Setpoints can be adjusted from 15 to 100 percent of full range ASHCROFT® Duragauge or test gauge. Monitor switch with a
on increasing pressure. light or meter. Pressurize the system to the required setpoint
pressure. Turn adjuster “B” until switch operates. Then lower
pressure to the re-setpoint, turn adjuster “A” until the switch
0 0 resets. Now increase pressure to the operating point and make
final adjustment on “B”. Raise and lower pressure to ensure that
20 20 the setpoint and re-setpoint are correct.

SOME PRECAUTIONS TO OBSERVE


40 40

60 60 Do not loosen the screws holding the precision switch element(s)

Nameplate PROOF pressure should not be exceeded. Inter-


or mounting bracket in place.

mittent operation up to proof pressure is permissible, however,


some change of setpoint may be noted.

CAUTIONS TO OBSERVE
Switch Applications On Continuous Static Pressure:
A B

SERIES LP-S SINGLE SWITCH


Pressure switches that contain BUNA, VITON or TEFLON
diaphragms can experience some amount of compression set of
the diaphragm in high static pressure applications. This compres-
Remove cover. For setpoint adjustment on either increasing or
sion set has the potential to shift the switch setpoint while in ser-
decreasing pressure to within ±1% of nominal range, mount the
vice. The setpoint can shift by approximately 2% (typically less
switch on a calibration stand and use a suitable reference such
than 1%) from the original setting. To assure optimal long term
as an ASHCROFT® Duragauge or test gauge. Monitor switch
setting accuracy, Ashcroft recommends the switch setting be
with a light or meter. Pressurize the system to the required set-
checked after 30 Days in service and reset if necessary. As with
point pressure.
any calibrated instrument, Ashcroft recommends regular inspec-
If setpoint is on increasing pressure, turn adjuster so that
tion of operation and setpoint setting.
switch operates (if common – normally closed circuit is being
monitored light goes off). If setpoint is on decreasing pressure,
turn adjuster so that switch resets (if common – normally closed
circuit is being monitored light comes on). When the setpoint
has been achieved, raise and lower the pressure to ensure that
the setpoint is correct.
The deadband (difference between the operate and reset
pressures) may be verified at this time to be between the values
noted on the nameplate label.

SERIES LP-D DUAL SWITCH


Remove cover. For setpoint adjustment on either increasing or
decreasing pressure to within ±1% of nominal range, mount the
switch on a calibration stand and use a suitable reference such
as an ASHCROFT® Duragauge or test gauge. Monitor switch
with a light or meter.
Pressurize the system to the required higher setpoint pressure
and turn adjuster “B” until the switch operates or resets as
required. See discussion of increasing or decreasing pressure
setpoints and deadband verification under Series LP-S Single
Switch. When the setpoint has been achieved, raise and lower
the pressure to ensure that the setpoint is correct. Then reduce
system pressure to the required lower setpoint pressure and
turn adjuster “A” until the switch operates or resets as required.
Verify this setpoint by raising and lowering pressure. Now
increase system pressure to higher setpoint and make final
adjustment on “B.”

© 2014 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com