Professional Documents
Culture Documents
177 Qy Series Dat 8pages 1.30MB
177 Qy Series Dat 8pages 1.30MB
177 Qy Series Dat 8pages 1.30MB
Features Applications
• DC circuit breaker • DC branch circuit protection (UL 489A, IEC / EN 60947-2)
• Hydraulic-magnetic technology • Telecom / datacom equipment
• 100% rating capability, independent of ambient temperature • UPS equipment
• VDE, EAC and CCC approved, CE certified • Alternative energy equipment
• UL listed (UL 489A) • Battery protection & switching
• Ratings 0.1 to 63 A (1 & 2 pole), 3 pole parallel • Telecommunication DC power distribution
(150 A maximum), 4 pole parallel (200 A maximum) • Railway signalling equipment
• Optional shunt trip (approvals pending)
• Wide range of time delays and operating currents
• Precision tripping characteristics
• Ultra compact – 13 mm wide module
• Trip indication with mid-trip handle
• Reset immediately after overload
• DIN mount product in grey shells
• Dual mount product in black shells
• 80 V DC devices are reverse feedable
• 125 / 250 / 600 V DC devices are polarity sensitive
• Suitable to use for electrical isolation
Auxiliary Switch,Trip Alarm & Combo: Optional Accessories
Features
• Auxiliary switch (DIN and Dual Mount) • Handle lock
• Auxiliary switch + trip alarm (Dual Mount only) • Surface mounting clips
• Trip alarm (Dual Mount only) • Busbar
• AC and DC voltages • 57 mm escutcheon blank (Dual Mount only)
• UL 489 listed (Auxiliary Switch: 6 A 250 V AC, • 57 mm safety blank (Dual Mount only)
0.5 A 80 V DC)
• IEC 60947-5-1 approved (auxiliary switch: 6 A 240 V AC,
0.5 A 110 V DC; trip alarm: 6 A 240 V AC, 0.5 A 110 V DC)
• Factory fitted
• Attached to right hand side of circuit breaker
• Compact 6.5 mm width
Approvals
S
Approvals UL 489A
2 2 3 4 1 pole
Number of Poles 1 2 2 series 4 series
parallel parallel parallel parallel plug-in
125 V 80 / 125 250 V 600 V
Operating Voltages 80 V DC, 125 V DC 80 V DC 80 V DC 80 V DC
DC V DC DC DC
Minimum Current Rating 0.1 A 0.1 A 30 A 20 A 110 A 200 A 0.1 A 0.1 A 0.1 A
Maximum Current Rating 63 A 50 A 100 A 100 A 150 A 200 A 50 A 20 A 50 A
Interrupting Capacity 10 kA
Approvals CCC
Number of Poles 1 2 2 parallel 3 parallel 4 parallel 1 pole plug-in
Operating Voltages 80 V DC
Minimum Current Rating 0.1 A 0.1 A 30 A 110 A 200 A 0.1 A
Maximum Current Rating 63 A 50 A 100 A 150 A 200 A 50 A
Interrupting Capacity 10 kA
Product Type QY
Operating Temperature Range -40 °C to +85 °C
Mounting Options Dual mounting (DIN & Mini), surface mounting clip, plug-in terminal
Time Delay Curves 1, 9, U2, U3, OP
10000 operations - 1500 electrical at rated current and voltage (IEC 60947-2)
Endurance
1000 electrical operations (UL 489A)
Dielectric Strength 1480 V (single pole) / 1830 V (multi pole), 50 Hz for one minute after testing
Weight 102 g per pole, 160 g with auxiliary (unpacked)
Humidity 35 to 85% relative
Certification tests done at altitude ≈ 2000 metres.
Altitude
Will operate at higher altitudes.
Shock 16 G (IEC 60068-2-27)
Vibration 2 G (IEC 60068-2-6) (sinusoidal wave)
I3 - Ignition does not persist at 850 °C after
Flammability
glow wire is withdrawn with an oxygen index of ≥ 28
Toxicity F1 - Smoke index of ≤ 20 which determines the fume class
PD2 - Normally only non-conductive pollution occurs.
Pollution Degree
Temporary conductivity caused by condensation is to be expected.
Breaker QY Wire Size mm² (IEC) Wire Gauge (UL) Torque (IEC) Torque (UL) Comments
Pozidriv #2
1 Pole & 2 Pole 0.75 - 35 mm² 18 – 2 – AWG 2.5 Nm 20 in-lb
Combi head
2 Pole Parallel 50 mm² 14 – 1/0 – AWG 3.2 Nm 28 in-lb Bridge Terminal
3 Pole Parallel 95 mm² 14 – 5/0 – AWG 5.6 Nm 50 in-lb Bridge Terminal
4 Pole Parallel 95 mm² 14 – 5/0 – AWG 5.6 Nm 50 in-lb Bridge Terminal
Data Sheet QY-SERIES-DAT
Page 2 of 8 JAN 2017
low voltage
Continues on page 4
OPERATING
CHARACTERISTICS
10000
CURVE 1
1000
100
Tripping Time (Seconds)
10
0.1 100000
1500
OPERATING
CHARACTERISTICS
Maximum
0.01 10000
CURVE 9
Minimum
0.001 1000
1000
100
105
1500
2000
2500
3000
4000
5000
130
150
200
300
400
500
% Rated Current
100
Tripping Time (Seconds)
10
0.1
Maximum
0.01
Minimum
0.001
100
1000
105
130
150
200
300
400
500
1500
2000
2500
3000
4000
5000
% Rated Current
Data Sheet QY-SERIES-DAT
Page 4 of 8 JAN 2017
low voltage
1500
OPERATING
CHARACTERISTICS
10000
CURVE U2
1000
100
Tripping Time (Seconds)
10
0.1
Maximum
0.01
Minimum
0.001
100
1000
105
130
150
200
300
400
500
1500
2000
2500
3000
4000
5000
% Rated Current
100000
1500
OPERATING
CHARACTERISTICS
10000
CURVE U3
1000
100
Tripping Time (Seconds)
10
0.1
Maximum
0.01
Minimum
0.001
100
1000
105
130
150
200
300
400
500
1500
2000
3000
4000
5000
% Rated Current
1500
OPERATING
CHARACTERISTICS
10000
CURVE OP
1000
100
Tripping Time (Seconds)
10
0.1
Maximum
0.01
Minimum
0.001
100
1000
105
130
150
200
300
400
500
1500
2000
2500
3000
4000
5000
% Rated Current
* The published time delay curves are generated at 30 C ambient temperature with the Circuit Breaker mounted in the up-right position. The “must hold”, “must trip” and “instantaneous
o
trip” current values are not affected by temperature, although delay time for the other operating current values may have to be adjusted using the temperature compensation curve which
is available on request.
Internal Resistance vs Current Rating
Q-Range Resistance values
10,000
1,000
100
Resistance (m Ω )
10
Maximum
1
Minimum
0.1
0 5 10 15 20 25 30 35 40 45 50 55 60 65
Amp rating
[0.270]
attached to a Dual mount single pole
45°
6.8
Circuit Breaker
(fitted on a Dual mount product)
[0.020]
All dimensions in mm [ inch ]
[0.090]
0.5
2.3
Tolerance ± 0.2 unless otherwise specified
• Type AT - Auxiliary Switch + Trip Alarm (as shown)
CONNECTING TERMINALS
• Type A - Auxiliary Switch DETAIL (COMMON TO ALL)
19.3 ± 0.3 35.5
Circuit Diagram when the Circuit
[0.760 ± 0.012] [1.400]
Breaker is in the “OFF” position 18.0
AUXILIARY/ TRIP ALARM (AT)
Trip Alarm Switch Auxiliary Switch [0.709]
6.0
16 NC 11 C [0.236]
18 NO 12 NC
15 C 14 NO
16 18 15
16
18
15
TEST BUTTON
POLLUTION DEGREE 3
UTIL. CAT. AC12/DC12
[2.244]
[3.827]
Uimp = 2.5kV
Icw = 0.1kA
97.2
Q-AUX
AUXILIARY SWITCH
110 VDC : 0,5A
S
A005438
12
11
14
11 12 14
11.7
[0.461]
69.8 6.5 18.0
[2.750] [0.256] [0.709]
37.8
Polarity identification [1.5900]
Diagram identifying the polarity of 125 V DC products in reference to Group 9 on page 3. Devices are shown viewed from the
front. Series devices (standard) - each pole is opposite polarity from the next pole on the left (bridged “-” to “+”). Parallel devices
- each pole has the same polarity (bridged “+” to “+”, “-” to “-”).
Series Bridged Parallel Bridged
- + - + + + - +
Polarity
Marking
4 Poles 2 Poles 1 Pole 1 Pole
+ - + - - - + -