Professional Documents
Culture Documents
Power System Stability Enhancement by Using Series Compensation
Power System Stability Enhancement by Using Series Compensation
Power System Stability Enhancement by Using Series Compensation
i
ACKNOWLEDGEMENT
Firstly, we would like to say thanks to God and to our parents whose firm love and
support made us what we are today. words can’t express our gratitude for all they have
provided us our appreciation and heart full thanks also goes to our project advisors, Mr.
Vijay Sardinah, Mr. Animut bekel and Mr. Yared Tasew, for their guidance to follow the
right way in our project and a heart full thanks to Mr.Engdaw Abel for his responsible to
help us and thanks to all electrical engineering departments of Arba minch university for
their encouragement, love and emotional supports that they had given to us throughout
the progress of this project.
we would also like to thank for our parents for their hopefully co-operations, guidance
and helps in this project.
ii
ABSTRACT
The stability of an interconnected power system is its ability to return to normal or stable
operation after having been subjected to some form of disturbance. Transient stability
analysis has recently become a major issue in the operation of power systems due to the
increasing stress on power system networks. This problem requires evaluation of a power
system's ability to withstand disturbances while maintaining the quality of service.
A Thyristor controlled series capacitor (TCSC) belongs to the flexible alternating current
transmission systems (FACTS) family of devices. It is a variable capacitive and inductive
reactance device that can be used to provide series compensation in power transmission
lines. One of the significant advantages that a TCSC has over other series compensation
devices is that the TCSC's reactance is instantaneously and continuously variable. This
means that the TCSC can be used not only to provide series compensation but can also be
used to enhance the stability of the power system .In this project, performance of TCSC
is analyzed. Initially, Real and reactive power flow through the transmission line have
been analyzed for fixed and then after the same parameters are evaluated by inserting
controllable capacitor in the same transmission network. The considered topology of
TCSC consists of back to back thyristors that controls the reactance of the TCSC. By
changing the firing angle of these back to back thyristors it is possible to vary the
reactance of the TCSC.
As per the TCSC characteristics, in inductive region at the firing angle α=90 to 130 the
power flow decreasing and in capacitive region at the firing angle α=140 to 180 degree
respectively the power flow increasing. The simulation of 3-phase model is the
appropriate degree of compensation to increase power transfer capability. The simulation
is carried out by using software package MATLAB Simulink
iii
TABLE OF CONTENTS
CERTIFICATE .................................................................................................................... i
ACKNOWLEDGEMENT .................................................................................................. ii
ABBREVIATION............................................................................................................. vii
INTRODUCTION .............................................................................................................. 1
2.1.2 Review of the components and theories used in this project ............................. 5
iv
2.3.1 How to find critical angle and critical clearing time........................................ 11
2.41 Some Advantages of the TCSC in power system transmission and distribution
lines ........................................................................................................................... 13
5.1CONCLUSIONS...................................................................................................... 38
Reference .......................................................................................................................... 39
APPENDICES .................................................................................................................. 40
v
LIST OF FIGURES
Figure 1the overall picture of the stability problems .......................................................... 2
Figure 2 types of power system stability ............................................................................ 6
Figure 3power angle curves for equal area criterion ........................................................ 10
Figure 4 TCSC basic modules .......................................................................................... 13
Figure 5 operational region of TCSC................................................................................ 14
Figure 6 single line diagram of the power system ............................................................ 16
Figure 7 the mathematical model of the swing equation .................................................. 18
Figure 8 using the mathemathecial modeling of the swing equation................................ 19
Figure 9 using the mathemathecial modeling of the swing equation................................ 20
Figure 10 the simulation diagram of the system without the thyristor controlled ............ 21
Figure 11 voltage ¤t wave form without tscs ........................................................ 22
Figure 12 results of active reactive power respectively .................................................... 22
Figure 13 single line diagram of SMIB system with TCSC controlled ............................ 30
Figure 14internal sub system of TCSC ............................................................................. 31
Figure 15 simulating diagram of the system with tcsc ..................................................... 33
Figure 16 voltage ¤t wave form result ................................................................... 34
Figure 17active &reactive power wave form at =70 degree ............................................. 35
vi
ABBREVIATION
AC Alternating current
CCT Critical clearing time
DC Direct current
EAC Equal area criteria
EMF Electro motive force
FACTS flexible ac transmission system
MW Mega watt
MVA Mega volt ampere
NR Newton rabsen
SMIB Single machine infinite bus
SSR Synchronous controlled resonance
TCR Thyrister controlled rectifier
TCSC Thyrister controlled series compensation
XTCSC Reactance of thyrister controlled series capacitor
vii
Power system stability enhancement by using series compensation
2014
CHAPTER ONE
INTRODUCTION
The classical model of a multi- machine may be used to study the stability of a power
system for a period of time during which the system dynamic response is dependent
largely on the kinetic energy rotating masses. The classical three-machine nine bus
system is the simplest model used in studies of power system dynamic and requires of
minimum amount of data. Hence such studies can be connected in a relatively short time
under minimum cost. Among various method of load flow calculation Newton Rap son
method is chosen for calculation of load flow study.
If the oscillatory response of a power system is during the transient period following a
disturbance is damped and the system settles in a finite time to a new steady operating
condition , we say the system is stable, if the system is not stable, it is considerable
unstable. This primitive definition stability requires that the oscillation system should be
damped. This condition is the same times called asymptotic stability and means that the
system contains inherent forces that tend to reduce oscillation.
Power system stability is the ability of an electrical power system, for given operating
Conditions, to regain its state of operating equilibrium after being subjected to a physical
Disturbance, with the system variables bounded, so that the entire system remains intact
and The service remains uninterrupted.
Short term
Short term Short term Long term Long term
Out of all the stability problems mentioned above, our specific focus in this project is the
Large disturbance stability which is a part of the rotor angle stability. Also, the voltage
Stability due to small disturbances is covered.
Rotor angle stability:
This refers to the ability of the synchronous generator in an interconnected power system
to Remain in synchronism after being subjected to disturbances. It depends on the ability
of the Machine to maintain equilibrium between electromagnetic torque and mechanical
torque of each synchronous machine system is Instability of this kind occurs in the form
of Swings of the generator rotor which leads to loss of synchronism.
Small Disturbance Stability:
Small Disturbance stability may refer to small disturbance voltage or rotor angle stability.
The disturbances are sufficiently small so as to assume a linearized system model. Small
Disturbances may be small incremental load changes, small control variations etc.
Tools
MATLAB. Simulation
Thyristore controlled series capacitor (TCSC)
Bus bar
Transmissions lines
Coupled transformer
Capacitor
Control unit
TCR
Converter- used for conversion of one form to another
CHAPTER TWO
THEORY & RELATED REVIEW OF LITERATURE
2.1 Literature review
In recent years, energy, environment, right- of-way, and cost problems have delayed the
generation facilities and new transmission lines, while the electric power has continued to
grow. This situation has necessitated a review of the traditional power system concept
and practices to achieve greater operating flexibility and better utilization of existing
power systems.
This project deals with power system stability by using Series compensation
Power system
Stability
Steady state
Transient Dynamic
Stability
Stability Stability
Figure 2 types of power system stability
I. Steady-state stability refers to the ability of the power system to regain synchronism
after small and slow disturbance, such as gradual power change.
II. Transient stability: the ability of the system to regain synchronism after a large
disturbance. This occurs due to sudden change in application or removal of large
load, line switching operation fault on the system, sudden outage of the line or loss of
excitation.
III. Dynamic stability: It refers to the stability of a power system subject to a relatively
small and sudden disturbance, the system can be described by linear differential
equations, and the system can be stabilized by a linear and continuous supplementary
stability control
Swing Equation
Under normal operating conditions, the relative position of the rotor axis and the
Resultant magnetic field axis is fixed. The angle between the two is known as the Power
angle or torque angle. During any disturbance, rotor will decelerate or Accelerate with
respect to the synchronously rotating air gap mmf and a relative Motion begin. The
equation describing this relative motion is known as the swing Equation.
If Tm is the driving mechanical torque and Te is the electrical torque then under steady-
state operation with losses neglected we have
Neglecting the losses, the difference between the mechanical and electrical torque gives
the net accelerating torque Ta. In the steady state, the electrical torque is equal to the
mechanical torque, and hence the accelerating power will be zero. During this period the
rotor will move at synchronous speed s in rad/s.
The angular position is measured with a stationary reference frame. To
represent it with respect to the synchronously rotating frame, we define
Where is the angular position in rad with respect to the synchronously rotating
reference frame taking the time derivative of the above equation we get the equation.
We can therefore conclude that the rotor angular speed is equal to the synchronous speed
only when ddt is equal to zero. We can therefore term ddt as the error in speed. And
Taking (2) & Multiplying both side of thus by m we get
Where Pm, Pe and Pa respectively are the mechanical, electrical and accelerating power in
MW
We now define a normalized inertia constant as
In steady state, the machine angular speed is equal to the synchronous speed and hence
we can replace r in the above equation by s. Note that Pm, Pe and Pa are given in MW.
Therefore dividing them by the generator MVA rating Stated we can get these quantities in
per unit. Hence dividing both sides
Of (3) by Srated we get
Pu)
The Equation describes the behaviour of the rotor dynamics and hence is known as the
swing equation. The angle is the angle of the internal emf of the generator and it
dictates the amount of power that can be transferred.
power transferred to zero. Since Pm remains constant, the accelerating power Pa becomes
equal to Pm. The difference in the power gives rise to the rate of change of stored kinetic
energy in the rotor masses. Thus the rotor will accelerate under the constant influence of
non-zero accelerating power and hence the load angle will increase. Now suppose the
circuit breaker re-closes at an angle c. The power will then revert back to the normal
operating curve. At that point, the electrical power will be more than the mechanical
power and the accelerating power will be negative. This will cause the machine
decelerate. However, due to the inertia of the rotor masses, the load angle will still keep
on increasing. The increase in this angle may eventually stop and the rotor may start
decelerating, otherwise the system will lose synchronism.
)2
Multiplying both sides of the above equation by dt and then integrating between two
arbitrary angles 0 and c we get
( ⁄ ) ∫
Now suppose the generator is at rest at 0. We then have d/dt = 0. Once a fault occurs,
the machine starts accelerating. Once the fault is cleared, the machine keeps on
accelerating before it reaches its peak at c, at which point we again have d/dt = 0. Thus
the area of accelerating in the above fig is as
A1 ∫
In a similar way, we can define the area of deceleration. The area of acceleration is given
by A1 while the area of deceleration is given by A2. This is given by
A2 ∫
Now consider the case when the line is reclosed at c such that the area of acceleration is
larger than the area of deceleration, i.e., A1 > A2. The generator load angle will then cross
the point m, beyond which the electrical power will be less than the mechanical power
forcing the accelerating power to be positive. The generator will therefore start
accelerating before is slows down completely and will eventually become unstable. If, on
the other hand, A1 < A2, i.e., the decelerating area is larger than the accelerating area, the
machine will decelerate completely before accelerating again. The rotor inertia will force
the subsequent acceleration and deceleration areas to be smaller than the first ones and
the machine will eventually attain the steady state. If the two areas are equal, i.e., A1 = A2,
then the accelerating area is equal to decelerating area and this is defines the boundary of
the stability limit. The clearing angle c for this mode is called the critical clearing angle
and is denoted by cr. We then get from Fig.by substituting c = cr
∫ ∫
We can calculate the critical clearing angle from the above equation
The critical clearing time, however, is dependent on H and will vary as this parameter
varies.
To obtain a description for the critical clearing time, let us consider the period during
which the fault occurs. We then have Pe = 0. We can therefore write from
Integrating the above equation with the initial acceleration being zero we get
∫
Further integration will lead to
∫
Replacing by cr and t by tcr in the above equation, we get the critical clearing time as
CHAPTER THREE
SYSTEM DESIGN AND ANALYSIS
Synchr Infin
onous bus
genera
tor
SWING EQUATION
Now we want to do an example of the most simple power system that we can consider –
the so-called one-machine against an infinite bus.
Let’s considering the per faults, during fault and post fault calculation
∬
Pm=mechanical constant
Ea=voltage at the generator in per unit
V∞=voltage exist at the infinite bus
Note that the graph is drawn the rotor angle vs. time for the mathematical modeling of
the swing equation
The simulation result of single machine connected to infinite bus bar system by using
mathematical modeling of swing equation as shown below. This is clearly for the solution
behavior we desired. Since it is bounded limit of the result.
Note that the graph is drawn the rotor angle vs. time for mathematical modeling with
numerical value for stable condition
Figure 10 the simulation diagram of the system without the thyristor controlled
Note that the results is shown below the voltage and current respectively
We ended our last set of notes, concluding that the following equation characterizes the
electromechanical dynamics of a synchronous machine system.
Pm=mechanical constant
Ea=voltage at the generator in per unit
V∞=voltage exist at the infinite bus
Consider the power system in Fig. 1. It is referred to as a one-machine against an infinite
bus. So many engineers use it to provide a conceptual basis for understanding
fundamental machine behavior. It would not be used, however, to provide precise
machine response as the computer serves well for this purpose
We ended our last set of notes, concluding that the following equation characterizes the
electromechanical dynamics of a synchronous machine system.
| || |
⁄
Pm=mechanical constant
Ea=voltage at the generator in per unit
V∞=voltage exist at the infinite bus
Consider the power system in Fig. 1. It is referred to as a one-machine against an infinite
bus.So many engineers use it to provide a conceptual basis for understanding
fundamental machine behavior. It would not be used, however, to provide precise
machine response as the computer serves well for this purpose
j0.1 j0.4
X’d=j0.2 V= 1.0<0°
j0.4
|Vt|= |V1|=1.0
Bus 2, the infinite bus, is so-called because it has a voltage and angle that is constant
under all conditions, and it can absorb infinite power. Although there is no real infinite
bus in power systems, a single small machine connected to a very large power system
behaves as if it is connected to an infinite bus.
Given that the machine is delivering 1.0 per unit power under steady-state conditions, we
have the following objectives in this problem.
1. Determine the voltage pastor Ea.
2. Draw the power-angle (P-δ) curve.
3. Determine the point corresponding to the 1.0 Pu power condition on the pre-fault
power angle curve.
4. Consider the fault in the middle of one of the lines between buses 3 and 2,
determine the fault-on power angle curve
5. Determine the post-fault or after fault power-angle curve after protection has
operated to clear the fault.
6. Use the three curves to describe what happens to the angle δ during the three
periods i.e. in pre-fault, fault-on, and post-fault condition.
Solution
Case 1
Determine voltage at the generator Ea.
j0.4
j0.1
j0.2
j0.4
1.0<0
Ea=|Ea|<δ
Compute the impedance x between the generator terminals and the infinite bus:
Note that we have two bus voltage magnitudes, the reactance between them, and the
power flowing out of one of them, so our familiar relation for power flowing out of
generator terminals will work here, i.e.,
| || |
From this we can compute the current flowing from the machine terminals (bus 1) to the
infinite bus, according to the voltage current relation.
And from this, we may compute the internal voltage pharos E a, according to
Note that the above procedure is typical of what is done in full-scale commercial power
flow programs where the program will begin from a power flow solution, from which it
computes the current flow from every gen bus, and then it computes each generator’s
internal voltage just as we have done in the above.
2. Draw the power-angle (P-δ) curve
We can draw the power angle curve for different angles. Some of the choices are
Note that the electrical power (left-hand-side) is the same in all three cases since there is
no resistance in this circuit. We should choose the most restrictive power angle curve,
i.e., the one that gives the largest angle for the same power. Since the voltages are all
reasonably close, the most restrictive curve is determined by the one with the largest
reactance
By using the above numerical data to find the pre fault power pre
The operating point corresponding to the 1.0 pu power condition on the pre-fault power
angle curve.
This is where Pe=1.0, i.e.
Solving for δa=28.44°.
We can show this point on the pre-fault power-angle curve,
However, that there are really two solutions, one at 28.44° and the other at 180-
28.44=151.56°. Both of these points constitute equilibrium, i.e., a location in terms of the
problem variables where all equations are satisfied, since the two angles complementary.
Case 2
Consider the three phase fault in the middle of one of the lines between buses 3 and 2,
determine the fault-on power angle curve.
The equivalent circuit diagram corresponding to the faulted system is.
j0.4
j0.1
j0.2
1.0<0
Ea=|Ea|<δ j0.2 j0.2
it, however, if we replace the circuit to the right of the two marked nodes then by using
the venin equivalent. The relevant part of the circuit is shown
We obtain the venin voltage
We get the venin impedance by ideal the source and computing the composite
impedance, as shown
j0.1333
j0.1
j0.2
0.333<0
Ea=|Ea|<δ
2.2
2.0
Pe Ppre
1.8
1.6
1.4
1.2
1.0 ● ●
0.8
0.6
0.4 Pfault
0.2
0
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 δa
Case 3
To determine the post-fault power-angle curve after protection has operated to clear the
fault.
The post-fault system is obtained from the understanding of basic protective relaying
which results in removing the faulted circuit. The resulting one-line diagram is shown,
and the corresponding equivalent circuit diagram is
j0.1 j0.4
X’d=j0.2 V= 1.0<0°
|Vt|= |V1|=1.0
j0.1 j0.4
j0.2
1.0<0
Ea=|Ea|<δ
In the present work SIMULINK has been used as a simulation tool. SIMULINK is an
interactive environment for modeling, analyzing a wide variety of dynamic Systems.
Single machine infinite bus system with all the required components is modeled and is
described in the following section. The Single machine infinite bus (SMIB) system of Fig
8 has been considered for the present study and opening of the corresponding line clears a
symmetrical three-phase fault.
Transmission line
G TCSC
Infinite bus
𝐿 𝐿 , 𝐿≤ 𝐿 ≤
-3
L=0.9337*10 H/Km standard at 200Km
-3
L=0.9337*10 H/km*200km=0.1867H
=0.2, XL=0.2XC
𝐿 𝐿 For
𝐿 𝐿
𝐶 𝐶
C = =2.72 F
Inclusion of TCSC device to one of the lines changes the power flow in given lines
according to level desired. This change is achieved by changing the impedance of line, in
which is installed TCSC device. With the entry values of angle switching thyristors α,
TCSC can change the impedance of the line and thereby regulates the power flow as
required. When such a change power flow, the power flow on lines is reallocated to
another ratio, but the resulting flow performance remains unchanged.
First the system has been simulated in MATLAB/SIMULINK environment. The voltages
and powers in all the buses have been found out and given as a “Table” below. Because
of the variation in powers at bus 2, it is selected as the candidate bus to which TCSC has
to be installed.
After simulation we have been obtained the real time voltage, current, power variations at
bus. The active and reactive powers at bus got oscillated due to large loads of the system
and which keep continuing for almost 3 sec. Because of the ohmic loads the active power
oscillations are more compared to reactive power oscillations. The preliminary
controlling systems such as governor, PSS are used for damping these oscillations.
According to the figures it is also clear that the voltage and current waveforms are closer
to sinusoidal waveforms. The voltage amplitude is 0.25 per unit and the current
amplitude is 0.12 per unit. TCSC is mainly used for controlling the active and reactive
power flow through the transmission system and also to improve the transient stability of
the system. Form the simulation result it is clear that after the installation of TCSC the
active power oscillation damping time will be less than the mode without TCSC. Also it
will decrease the reactive power damping time.
3.2.2 SIMULATION DIAGRAM OF THE SYSTEM WITH THYRISTORE
CONTROLED CAPACTOR (TCSC)
At firing angleα=70°
Note that in the simulation result when we used thyristore controled capacitor TCSC
the fault clearing time become fast as we compared to without TCSC
Without TCSC fault clearing times=0.0234sec.
The fault cellaring time with TCSC=0.0231sec
CHAPTER FOUR
The simulation result of single machine connected to infinite bus bar system by using
mathematical modeling of swing equation as shown figure 9. This is clearly for the
solution behavior we desired. Since it is bounded limit of the result.
Note that the transient stability depends on the time when it required to transiently
stabile or unstable. The power is interrupted in small time interval, even in micro second
level.as we shown in figure 8 unboundedly unstable systems the reason why we have
pensioned. But in figure 9 shows that the system is transiently stable after relatively
longer time interval. The above two figures (figure 8&figure9) are drawn the rotor angle
vs. time for the mathematical modeling of the swing equation.
Duing when we used with out of the thyriostered controlled series capacitor(TCSC) case
the time of fault occruance in the interval between 0.02sec.≤ ≤ and the out
put voltagee and current results are shown the above.
But when we used thyristore controlled series capacitor (TCSC) technique the time of
response is fast .the response is taken at the time interval between 0.02sec≤t≤0.024sec
and the output of voltage, current, active power and the reactive power wave forms are
shown in the above figures 16&17
CHAPTER FIVE
CONCLUSIONS AND FUTURE -SCOPE OF Work
5.1CONCLUSIONS
Power system stability is the property of a power system that insures the system remains
in electromechanical equilibrium throughout any normal and abnormal operating
Conditions. Because the power system stability is an electromechanical Phenomenon, it
is thus defined as the ability of designated synchronous machines in the system to remain
in synchronism with one another following disturbance such as fault and fault removal at
various locations in the system. This paper presents the study of transient stability
analysis and also the transient stability analysis using the TCSC.
This paper presents systematic procedure for modeling, simulation of TCSC controller
for enhancing power system stability. A MATLAB/SIMULINK model is developed for a
single-machine infinite bus power system withTCSC model. The controller is tested on
power system subjected to large as well as small disturbances. The simulation results
show that, the TCSC controller improves the stability performance of the power system
and power system oscillations are effectively damped out. Thus, it is observed that the
proposed TCSC controller is effective in damping low frequency oscillations resulting
from small disturbances conditions like increase in mechanical power input and reference
voltage settings.
Reference
[1] Power system dynamics: stability and control second edition, Jan
Machowski, Janus W. Bialek, James R. Bumby.
[2] Dommel, H.W., and Sato, N.,’Fast Transient stability solutions”,
IEETrans, PAS-91, pp.1643-1650) October, 1972.
[3] Martin German-Sobek, ubomír Bea, Roman Cimbala
Using of the Thyristor Controlled Series Capacitor in
Electric Power System
[4] Power system and design, second fifth edition.J.DUNCAN GLOVER
MULUKUTLAS.SARMA THOMAS J.OVERBYE
[5] Design and Implementation of Firing Circuit for Single-Phase
Converter
Tirtharaj Sen, Pijush Kanti Bhattacharjee, Member, IACSIT, Manjima
Bhattacharya
[6]S.B.Griscom, Mechanical analogy of the problem of transmission stability,
Elec.jour. vol.23, pp.230, 5th May 1996
APPENDICES
The swing equation
Where
Reactance of TCSC
𝐿 𝐿 , 𝐿≤ 𝐿 ≤