Professional Documents
Culture Documents
4 6010257279880791650
4 6010257279880791650
INSTITUTE OF TECHNOLOGY
TEAM MEMBERS ID
HAWASSA, ETHIOPIA
DECLARATION
Student’s Declaration:
We have declared that this thesis is the original work of us, we have not copied from any
other students‘ work or from any other sources except where due reference or
acknowledgement is made explicitly in the text, nor has any part been written for us by
another person.
Advisor Approval
The thesis has been submitted for examination with my approval as a university advisor.
Hereby certifies that the work entitled STEPPER MOTOR BASED AUTOMATIC TAP
CHANGER OF A TRANSFORMER was prepared by the above named student, and was
submitted to the institute as a partial/full fulfillment for the conferment of BSC and the
aforementioned work, to the best of our knowledge, is the said student‘s work.
i
ACKNOWLEDGMENT
By the grace of Almighty GOD, we have been able to complete this thesis and achieve the
aim we set for ourselves at the start. We are especially thankful to our Advisor Tesfaye for
his never ending dedication and his kindness and support that he has shown during the thesis.
Next we would like to express our gratitude to University and their staff, for the opportunity
and encouragement to pursue our group members. Our sincere appreciation extends to all
lecturers, lab engineers and entire staff of the University.
Last but not the least we are also thankful to our family and friends for their continuous
encouragement and support throughout the entire phase of the thesis.
ii
TABLE OF CONTENTS
DECLARATION ..................................................................................................................................... i
ACKNOWLEDGMENT......................................................................................................................... ii
ABSTRACT........................................................................................................................................... ix
INTRODUCTION .................................................................................................................................. 1
iii
3.1.1 Transformer.................................................................................................................................... 8
Rectifiers ................................................................................................................................................. 9
Voltage sensor....................................................................................................................................... 10
CHAPTER FOUR................................................................................................................................. 25
4.4 Over all circuit diagram of steeper motor based automatic tap changer ......................................... 27
iv
CONCLUSION AND RECOMMENDATION .................................................................................... 32
REFERENCE........................................................................................................................................ 34
Appendix/ANNEX................................................................................................................................ 35
v
List of Figures
Figure 3.3: circuit diagram and waveform for bridge rectifier ............................................................... 9
Figure 3.8: Block diagram for OLTC power and control scheme ........................................................ 13
vi
Figure 4.5: output of PIC16F84A microcontroller steeper motor based automatic tap changer for tap-
one ......................................................................................................................................................... 28
Fig 4.6 output of PIC16F84A microcontroller steeper motor based automatic tap changer for
tap two………………………………………………………………………………………. 25
Figure 4.7: output of PIC16F84A microcontroller steeper motor based automatic tap changer for tap-
three ...................................................................................................................................................... 29
Figure 4.8: output of PIC16F84A microcontroller steeper motor based automatic tap changer for tap-
four ........................................................................................................................................................ 30
vii
List of Acronyms
AC Alternative current
DC Direct current
HV High voltage
LV Low voltage
viii
ABSTRACT
In our thesis our aim was to design, and Simulate a stepper motor based automatic tap
changer of a transformer. We have designed and simulate a system which changes the turn
ratio of the transformer by automatic microcontroller controlled stepper motor with in on-
load condition. The system consists of stepper motor, microcontroller, sensors installed at
transformer. To reduce the risk of unexpected failure and to ensure unscheduled outage, our
tap changer control tap as the voltage increases or decreases depending on the nature of the
load. When the voltage at the primary of the step down transformer varies, resulting in an
equivalent variation at the secondary side. We have used voltage sensor for sensing the
voltage from secondary winding output of transformer. These sensing signals are fed to the
microcontroller for taking the decision of tap change. Any variation at the output voltage of
the distribution transformer is sensed by the microcontroller and compared with the reference
value as per the program. This intern produces appropriate command to trigger the stepper
motor drive for change in the suitable tapping of transformer. Then system stability
improved, because of quick response. The taps are leads or connections provided at various
points on the winding. The turn ratios differ from one tap to another and hence different
voltages can be obtained at each tap. We work on on-load tap changers which are used to
change the turn ratio without disconnecting the load from it. Our work on-load tap changers
considerable increases the efficiency of the system by reducing response time.
ix
CHAPTER ONE
INTRODUCTION
A transformer is a static electrical device used in electric power systems to transfer power
between circuits through the use of electromagnetic induction. Thus the transformer transfers
energy from one circuit to another by means of a common magnetic field. When an
alternating current flows through a conductor, magnetic field exists around the conductor. If
another conductor is placed in the field created by the first conductor such that the flux lines
link the second conductor, then a voltage is induced into the second conductor. Transformers
are essential for the transmission, distribution and utilization of electrical energy.
Operation of distribution transformer under rated condition guarantees their long life
However; their life is significantly reduced if they are subjected to overloading, resulting in
unexpected failures and loss of supply to a large number of customers thus effecting system
reliability. Distribution transformers are currently monitored manually where a person
periodically visits a transformer site for maintenance and records parameter of importance.
It is a normal fact that increases in load lead to decrease in the supply voltage. Hence the
voltage supplied by the transformer to the load must be maintained within the prescribed
limits. This can be done by changing the transformer turns ratio. The taps are leads or
connections provided at various points on the winding. The turn‘s ratios differ from one tap
to another and hence different voltages can be obtained at each tap.
System voltage control is essential for adjusting the terminal voltage of consumer within the
prescribed limits, Adjustment of voltage based on change in load, In order to control the real
and reactive power
Tap changing causes change in leakage reactance, core loss, copper loss and perhaps some
problems in the parallel operation of dissimilar transformer. There are two methods of tap
changing.
Off load tap changing as the name indicates, in this method tap changing is done
after disconnecting the load from the transformer. Off load tap changing is normally
provided in low power, low voltage transformers.
1
On load tap changing are used to change the turn‘s ratio without disconnecting the
load from it. Tap changing can be done even when the transformer is delivering load. .
On-Load Tap-Changers (OLTCs) are one of the indispensable components for the
regulation of power transformers used in electrical energy networks and industrial
application.
On load tap changers considerable increases the efficiency of the system. Nowadays
almost all the large power transformers are provided with on load tap changers and
our project is automatic tap changing to make the operation efficient and to reduce
response time. Previous works are done to make automatic tap changing using
selector switches and gears but they are more exposed for short circuit during
transition of taps due to high response of time but we are going to use steeper motors
which have exact and accurate positioning with very short response time in co-
ordination with micro controller and different sensors.
The reason for providing on load tap changer in power transformers are
1. During the operation of on load tap changers the main circuit remains unaffected.
2. Dangerous sparking is prevented. The taps on the windings are brought to a separate oil
2
have fast response time and accurate positioning of the transformer tape using stepper motor
aided by microcontroller.
Therefore, the project is designed with a low cost with fast and reliable operation to protect
the health of the transformer.
1.3 Objectives
1.3.1 General Objective
The main aim of this project is to design stepper motor based automatic tap changer for
transformer which changes turn ratio of transformer to keep transformer supply in balance
with load variation with on load operation.
Start
Literature Review
Results and Conclusion
System Modeling
3
1.5 System block diagram
The system model is shown in Figure 3.1 which says about the connectivity of all mentioned
devices.
Micro-
Controller
Distribution transformer P
LCD Display
transformer
I
C
Tap changer
1
6 Current sensor
Steeper motor
Load
F
8
Motor drive
7 Voltage sensor
The main aim of this thesis was to design an automated tab changer of a transformer
First part of the thesis was to design and build the circuit diagram of the entire system.
The circuit part mainly consists of a stepper motor driving unit, voltage sensor, current
sensor, tap changer and LCD display circuit.
We have used microcontroller for automatic control of the whole system.
4
The second part is the development of software for programming and interfacing of the
microcontroller. This software are, micro C Pro and the software of Proteus professional
are considered for the circuit analysis and expected result.
The proposed OLTC has got several advantages they are:
Avoids arcing during tap changing.
Less maintenance cost as compared to mechanical tap-changer.
Low cost.
Fast operation as compared to mechanical OLTC.
No labor required as compared to mechanical OLTC.
The entire project is composed of five chapters, each covering a section of the work as
summarized below:
Chapter one: gives about a brief introduction to stepper motor tape changing system, and
answers why we have gone for this project, what the objectives , Methodology and system
block diagram, what advantages can we get from this thesis and its scope.
Chapter two: Covers an extensive literature review of previous works on transformer tape
changing system.
Chapter three: about system design and analysis, it consists of System Components and
Operations, System Modeling and mathematical analysis of the system. In this chapter brief
description about architecture and interfacing of the devices such as stepper motors, sensors,
LCD display, and the microcontroller being used are proposed.
Chapter four: Results and Discussions, shows Software simulation results and discussions
covers the detailed design and simulation of each sensor, and the overall integrated system or
main thesis results and output.
Chapter five-Conclusions and recommendations: This chapter will Concludes the entire
work performed during the project and Points out some few recommendations on improving
the performance, and efficiency.
5
CHAPTER TWO
LITERATURE REVIEW
A very large work has been done on observing and checking of transformer, Some of those
researches which had been organized and carried out, their setbacks, ambiguities and merits
are as discussed in the subsequent paragraphs.
[F. Milano] [2] ULTC (under load tap changer) transformers are relatively common devices
in sub transmission and distribution systems. This fact is demonstrated by the constant
interest in the improvement of ULTC technology, modeling, and regulation, as well as by
several studies on power flow and stability analysis.
[Miles A Redfern] [5] The enhancements to the AVC control scheme using Source Drop
Compensation and pre-emptive tap changing enable the voltage control offered by the
OLTCT to be improved. On-Load Tap-Changer Transformers (OLTCT) provides a well-
established method for controlling the voltage on supply networks. Their associated
automatic voltage control relays (AVC) include a selection of features to ensure that they
enable the voltage to be controlled at a nominal supply point rather than just the transformer
terminals and avoid complications when transformers are operated in parallel.
Nikunj R. Patel, Makrand M. Lokhande, [6] The on-load tap changing (OLTC) regulators
have been widely used since the introduction of electrical energy. They ensure a good
regulation of the output voltage in presence of large variations of the input voltage with
typical response time from several mili-seconds to several seconds. Earlier mechanical type
of on load tap changers were into practice. But they had considerable limitations and
drawbacks like arcing, high maintenance, service costs and slow reaction times. In order to
overcome
[R. Shuttle worth, B. A. T. Al Zahawi] [9] With the use of high power semiconductor devices
such as triac, IGBTs, Thyristor, problems related with the mechanical on-load tap changing
power transformer have been eliminated. In order to overcome these limitations and
drawbacks, new circuits and configurations for tap-changers have been introduced.
Smith C A, Potts S C and Redfern M A [10] ‗Simulation Studies of OLTC Transformer AVC
relays Operating in Series using a RTDS, Real Time Digital Simulator.‘ Proceedings of the
8th IEE Conference on Developments in Power System Protection, April 2004, Amsterdam
6
[J. Faiz and B. Siahkolah] [4] Electronically assisted ULTC and solid state tab changer both
technologies are intrinsically faster than the motor-based one. However, the differences in the
model are mainly in the low-level logic of the electronic switches. The overall controller
scheme is basically the same as for the motor-driven technology, but for the speed of the time
response. Note that electronically assisted ULTCs are also sometimes called ―hybrid‖ ULTC.
7
CHAPTER THREE
The power supply unit is used to provide a 5V of DC supply. These will acts as power to
different standard circuits mainly for microcontroller. It also provides 24V for steeper motor.
It mainly consists of following blocks.
8
Rectifiers
A rectifier is an electrical device that converts alternating current (AC), which periodically
reverses direction, to direct current (DC).
9
Uni-polar Stepper motor
A uni-polar stepper motor has two windings per phase, one for each direction of magnetic
field, one for each direction of magnetic field.
Bipolar Stepper motor
Bipolar motors have a single winding per phase. The current in a winding needs to be
reversed in Order to reverse a magnetic pole.
For our project we choose bipolar steeper motor, because windings are better utilized, they
are more power full than a unipolar motor of the same weight. Hence it is 50% efficient (or
approximately 70% of the torque output available). Though bipolar is more complicated to
drive, the abundance of driver chip means this is much less difficult to achieve. This type of
motor is more efficient than a unipolar stepper motor.
10
3.1.6 Tap changer
The taps are leads or connections provided at various points on the winding. The turns ratio
differ from one tap to another and hence different voltages can be obtained at each tap
Taps are provided at the HV windings of the transformer because of the following reasons.
1. The number of turns in the High voltage winding is large and hence a fine voltage variation
can be obtained.
2. The current on the low voltage winding of large transformers are high. Therefore
interruption of high currents is a difficult task.
3. LV winding is placed nearer to the core and HV winding is placed outside. Therefore
providing taps on the HV winding is comparatively easier than that of the LV winding.
A handle fitted for manual operation in case of emergency. The selector switch is a form of
make before break switch and during the transition of the tap changers from one tap to
another; momentary connection must be made between the adjacent taps. This results in short
11
circuit between the adjacent taps. The short circuit current must be limited by including
resistor or reactor. Hence all forms of on load tap changer are provided with an impedance to
limit short circuit current during tap changing operation. The impedance may be resistance or
a center tapped reactance. In modern designs it is invariably carried out by a pair of resistors.
The tap change operation takes place in two steps; first the next tap is preselected by the tap
selector at no load, then the diverter switch transfers the load current from the tap in
operation to the preselected tap The OLTC is operated by means of a drive mechanism. The
tap selector is operated by a gearing directly from the drive mechanism. At the same time, a
spring energy accumulator is tensioned; this operates the diverter switch – after releasing in a
very short time – independently of the motion of the drive mechanism. The gearing ensures
that this diverter switch operation always takes place after the tap pre- selection operation has
been finished. The switching time of a diverter switch lies between 40 and 60 MS with
today‘s designs. During the diverter switch operation, transition resistors are inserted which
are loaded for 20–30 MS, i. e. the resistors can be designed for short-term loading. The
amount of resistor material required is therefore relatively small. The total operation time of
an OLTC is between 3 and 10 sec depending on the respective design
Let suppose a current inter from point ‗A‘ to main winding than enter in tap winding through
reversing switch contact N—>L , Taps l & 2 both are connected with move able selectors but
the current flows only in tap no. I (Because the diverter side-1 is closed) so the current finally
end on point B as shown in above fig.
Side 1
Side 2
12
Now if we want to change the tap position from tap-1 to tap-2, operates the drive unit steeper
motor through raise control switch .The motor starts operation (at this time only an action
starts in diverter switch because tap -2 is already Selected). For changing the tap-1 to tap-2
the voltage will be increased on secondary side of transformer because the numbers of
primary turns have now reduced.
Similarly, if we want to go on tap no.3, the operational sequence will be same as above but in
reverse (side -2 to side-1) and now the operation will become at first in selector switch, as the
odd moveable selector selects the tap no.3. For doing continuous changing the taps in step by
step, we select the tap-5. At this time only a main winding will be in circuited and current
will flows from ‗A‘ to ‗B‘ via the main winding to diverter switch. The tap-5 of this
arrangement is called ‗principal‘ tap. At this tap the voltage on both sides will be rated. Now
if we want further changing in taps, operates the motor through the raise switch placed in
drive unit.
33kv
Steeper
Motor
Motor
Drive
Fig 3.8 Block diagram for OLTC power and control scheme
13
3.3 System Modeling
Mathematical calculation of Tap changer
Considering total mass of the system to be moved or rotated by our steeper motor we can
select type and specification of our steeper motor and type of coupler to be used.
NB: The total mass estimated is 20 kg in the tape places and our auxiliary around there is
estimated to weight totally 30 kg. And the transformer tape have 32mm diameter in its
mounting; having this in mind we have calculated the torque required to move our tapes
using the motor first and then we will select the type of the steeper motor and type of
coupler.
Speed of the tape changing is assumed to be1000 rpm at its maximum torque
Here we have selected steeper motor with torque of 1.5 since it should be somehow greater
than the calculated value.
14
Fig 3.9 Selected steeper motor and it‘s specification
Shaft coupling:
5mm/32mm D19L25 Flexible Shaft Coupling CNC Stepper Motor Coupler Conn0ector
At the end transformer the transformer and the motor are coupled as indicated below at
number 147
Voltage Ratio: kV
15
With ON-Load Tap Changing of +10 % to - 10% at 2.5% Steps, to Calculate Tap Changer
Levels
According to CERC & CEA Norms, Highest Voltage level for the 33kV system is 36kV, So
Maximum Tap level should be equal to or greater than 36kV, Also Lowest Voltage level is
30 kV. Now we will see Calculations.
+10%will be
Now add 3300 volt with 33000 volt [i.e. 33kv] then final output will be:
Tap-Changer Adjustment:
To represent tap number and their output voltage let us work on steps that our tap changer
works.
At normal operation
Tap 3- the high voltage winding read 3300V and it gives 433V in the low voltage side
16
In case of 5% step
LV side
17
a)
b)
Fig 3.12 the overall arrangement inside tap changer; A) before adjustment b) after adjustment
In our case a V transformer has five taps on the primary winding giving -
Case1:
If, on-load, the secondary voltage increases to 454.65V then, the tap should be used to
maintain 433v V on-load (assuming the supply voltage remains constant)
18
This indicates that, to keep the equation in balance with primary voltage and secondary
winding turns fixed, either V2 or N1 must be adjusted. Since the objective is to reduce V2
back to nominal, then N1 must be decreased.
: or must be increased to
( )
Case2:
If, on-load, the secondary voltage increases to 443.825V then, the tap should be used to
maintain 433v V on-load (assuming the supply voltage remains constant)
This indicates that, to keep the equation in balance with primary voltage and secondary
winding turns fixed, either V2 or N1 must be adjusted. Since the objective is to reduce V2
back to nominal, then N1 must be decreased.
: or must be increased to
( )
19
Increasing N1 by 0.5% will accomplish reduction in secondary voltage output.
Case 3
At normal voltage limit our tap changer won‘t change position and it is fixed at tap number 3
Case 4
If, on-load, the secondary voltage reduces to 411.35V then, the tap should be used to
maintain 433v V on-load (assuming the supply voltage remains constant) is
This indicates that, to keep the equation in balance with primary voltage and secondary
winding turns fixed, either V2 or N1 must be adjusted. Since the objective is to raise V2 back
to nominal, then N1 must be reduced.
: or must be reduced to
( ) will
accomplish the increase in secondary voltage output.
20
Fig3.13 tap selection process
Case 5:
If, on-load, the secondary voltage reduces to 422.175V then, the tap should be used to
maintain 433v V on-load (assuming the supply voltage remains constant) is
This indicates that, to keep the equation in balance with primary voltage and secondary
winding turns fixed, either V2 or N1 must be adjusted. Since the objective is to raise V2 back
to nominal, then N1 must be reduced.
: or must be reduced to
( )
21
3.4 Algorithm flow chart of the System
From the block diagram the sensors gather real data about the condition of the transformer. These
sensors are internally embedded in transformer for their proper functioning and switch off the
transformer through relay during faulty condition. The sensor unit includes current sensor and
voltage sensing unit.
Current sensor is a device which senses the current level of the series circuit of both analog
and dc current values. Therefore in the block diagram, current sensor is used to measure the
load current.
Start
22
3.4.2 Voltage sensor
Voltage Sensing is a method used for determining the value of voltage in the circuit. Voltage
sensing is usually obtained by using either the voltage division method or a step down
Potential transformer.
Start
Micro -controller
Changing tap of
the transformer
Tap selection logic is shown in the figure below, The microcontroller continuously reads the
value of the input voltage using voltage sensor. It checks whether the input voltage is within
prescribed voltage limits. If the voltage is within the predetermined limits the tap will be
rotated as per programed.
23
Fig 3.16 flow chart of overall tap changing system
24
CHAPTER FOUR
RESULT AND DISCUSSION
The design of microcontroller based stepper motor automatic tap changer was simulated by
using proteus 8.6 professional software, it is designed by using different parts integrating
together it consists of PIC16F84A microcontroller, voltage sensor, current sensor bipolar
stepper motor, ULN2003A driver.
4.1 Voltage Sensor simulation circuit
Voltage Sensing is a method used for determining the value of voltage in the circuit. Voltage
sensing is usually obtained by using a step down potential transformer. The output from sensing
unit is feed to ADC port of microcontroller. Whenever a disturbance in the monitored voltage is
accompanied by a change in the transformer‘s load, it can be assumed, either in full or in part to
have been caused by the change in that load. The local AVC relay can therefore be allowed to
make a correction to the transformer‘s ratio irrespective of any up-stream corrective actions
required. when the measured value is above or below from normal range the microcontroller
activates the relay to start the steeper motor for tap changing of turn ratio.
25
Fig 4.2 Current sensor interfaced with microcontroller
26
4.4 Over all circuit diagram of steeper motor based automatic tap changer
The final simulation circuit that we developed gives the detailed information about how the
system can be developed and how they are integrated and combine all the major systems that
develop for tap changing operation of the transformer.
The system checks these two parameters whether or not the voltage varies. The sensors send
a signal to the microcontroller, and it also sends a command for a steeper motor for changing
turn ratio of a transformer. The Microcontroller also sends the monitored parameters to LCD
display.
Final Results
27
Voltage sensor change sensed current signals to voltage and feed to micro controller
The value of voltage displayed on LCD
Steeper motor rotate clock wise for 66 full rotations
Then tape number on LCD displayed
LED for tape number one on
Finally the transformer operate in balance with load demand
Fig 4.5 output of PIC16F84A microcontroller steeper motor based automatic tap changer for
tap-one
When voltage is in between 433-443.825 the following events are undertaken:
Voltage sensor change sensed current signals to voltage and feed to micro controller
The value of voltage displayed on LCD
Steeper motor rotate clock wise for 33 full rotations
Then tape number on LCD displayed
LED for tape number two on
Finally the transformer operate in balance with load deman
28
Fig 4.6 output of PIC16F84A microcontroller steeper motor based automatic tap changer for
tap-two
When voltage is in between 422.175-433 the following events are undertaken:
Voltage sensor change sensed current signals to voltage and feed to micro controller
The value of voltage displayed on LCD
Steeper motor rotate clock wise for 33 full rotations
Then tape number on LCD displayed
LED for tape number three on
Finally the transformer operate in balance with load demand
Fig 4.7 output of PIC16F84A microcontroller steeper motor based automatic tap changer for
tap-three
29
When voltage is in between 411.35-422.175 the following events are undertaken:
Voltage sensor change sensed current signals to voltage and feed to micro controller
The value of voltage displayed on LCD
Steeper motor rotate anti-clock wise for 33 full rotations
Then tape number on LCD displayed
LED for tape number four on
Finally the transformer operate in balance with load demand
Fig 4.8 output of PIC16F84A microcontroller steeper motor based automatic tap changer
for tap-four
Voltage sensor change sensed current signals to voltage and feed to micro controller
The value of voltage displayed on LCD
Steeper motor rotate clock wise for 33 full rotations
Then tape number on LCD displayed
LED for tape number five on
30
Finally the transformer operate in balance with load demand
Fig 4.9 output of PIC16F84A microcontroller steeper motor based automatic tap
changer for tap-five
As it is shown above all expected outputs are shown and our tap changer is operating as the sated
pre condition with subscribed limit.
31
CHAPTER FIVE
In this work steeper motor based automatic tap changer with five taps that located at high
voltage side of transformer is designed. In our thesis we have developed automatic system
which has fast response time and accurate positioning of the transformer tape using stepper
motor aided by microcontroller. According to our work any variation at the output voltage of
the distribution transformer is sensed by the microcontroller and compare with the reference
value as per the program. This it produces appropriate command to trigger the motor drive to
run the steeper motor for change in the suitable tapping of transformer. microcontroller
having input parameters from sensor, it starts its work by sending signal to LCD to display
there all measured value and activate LED with their own respective symbol to make easier
information for operators. The system stability is improved, because of quick response.
Because of static devices, maintenance cost is reduced due to elimination of frequent
sparking. Output voltage can be regulated in the range of ±5 V of nominal voltage.
Transformer tap changing is wide concept it needs great concern and care if the tap
monitoring is not done in fast response and in accurate calibration it leads to outage of system
and sudden accident or faults on the transformer. Manual operation of tape change is full of
such problems, operation involving manual tap changing will leads to danger to the operator
when short circuit appears during tap changing process so our work reduces these all risks
involving tap changing. And it is economically viable and can be installed to existing
transformers without affecting its property and operation principles.
32
5.2 RECOMMENDATION
In our recommendation we recommend that any transformer manual checkers to apply our
steeper motor based tap changer system. Any work and investigation on tap changing is very
advantageous and challenging. Based on the present time, it can be observed that the world‘s
population is increasing rapidly. Therefore demands on electricity will be high and these will
lead to demands of highly sophisticated protection devices, and tap changer which will be
incorporated in transformer tap changer schemes.
We have designed an automatic steeper motor based tap changer but in our design there are
some parts which must be done, some improvements need to be made in the future work.
These are:-
We are going forward to implement the project in real time applications.
we also recommended that it can be done by more modifying this tap changing system
by adding additional tap levels, we only works on 5 voltage level taps, it means our
tap changer is designed for transformer which contains 5 taps.
The system is made up of two system electrical and mechanical system; we have
shown simulation result for full of the electrical part and some parts of mechanical
part and the remaining part is only possible to show in implementation.
So this is not the end of the thesis but rather is a step towards exploring other
possibilities that it brings with it. We feel very happy to work in such a challenging
project which has tremendous application and possibilities.
33
REFERENCE
[2] [F. Milano] ULTC (under load tap changer) transformers are relatively common devices
in s transmission and distribution systems. Mar -2017
[3] International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395
0056 Volume: 04 Issue: 04 | Apr -2017 www.irje
[4] J. Faiz and B. Siahkolah, ―Optimal Configurations for Tap of winding and Power
Electronics Switches in Electronic Tap-Changers,‖ IEE Proceedings on Generation,
Transmission and Distribution, vol. 149, no. 5, pp. 517–524, Sep. 2002.
[5] [Miles A Redfern] The enhancements to the AVC control scheme using Source Drop
Compensation and pre-emptive tap changing enable the voltage control offered by the
OLTCT to be improved. On-Load Tap-Changer Transformers (OLTCT) Third International
Conference on Electrical Engineering, 2009, ICEE '09, pp. 1-6, 9-11 April 2009, Lahore
[8] Rodolfo Echavarría, Abraham Claudio, Maria Cotorogea, Analysis, Design, and
Implementation of a Fast OnLoad Tap Changing Regulator‖ IEEE Power Electronics, vol. 22,
no. 2, march 2007
[9] [R. Shuttle worth, B. A. T. Al Zahawi] With the use of high power semiconductor devices
such as triac, IGBTs, Thyristor, problems related with the mechanical on-load tap changing
power transformer have been eliminated. IEEE press, Piscataway, 2002.
34
Appendix/ANNEX
* Processor: PIC16F877A
*/
#include <xc.h>
#define SBIT_ADON 0
#define SBIT_CHS0 3
#define SBIT_ADFM 7
char num[]="12345";
int pos=0;
int dfc=0;
unsigned i,j ;
for(i=0;i<time;i++)
for(j=0;j<1275;j++);
35
void lcd_cmd(unsigned char command) //Function to send command instruction to LCD
PORTD = command;
msdelay(1);
PORTC=0x00;//e=0;
PORTC=0x05;
msdelay(1);
PORTC=0x01; //e=0
msdelay(10);
msdelay(10);
36
msdelay(10);
msdelay(10);
while(cnt--);
void ADC_Init()
ADCON1=(1<<SBIT_ADFM); // All pins are configured as Analog pins and ADC result
is right justified
int main()
char dot[2]=".V";
int adcValue=0;
TRISB=0x00;
TRISC=0x00;
TRISD = 0x00;
PORTB=0x00;
while(1)
{ lcd_init();
for(int i=0;i<13;i++){
lcd_data(volt[i]);
float voltage=((adcValue*3248.0)/1023.0);
int val_int=voltage;
int x=val_int/100;
38
lcd_data(temp);
int val_int1=(voltage-x*100)/10;
lcd_data(temp2);
int val_int2=((voltage-x*100)-(val_int1*10));
lcd_data(temp2);
lcd_data(dot[0]);
int val2=((voltage-x*100)-(val_int1*10))-val_int2;
int val_int3=((val2);
lcd_data(temp3);
lcd_data(dot[1]);
msdelay(5);
if(voltage>443.825&& voltage<454.65)//clockwise
PORTB=0xA0;
msdelay(40);
PORTB=0x00;
lcd_cmd(0xC0);
for(int i=0;i<13;i++)
39
lcd_data(tap[i]);
lcd_cmd(0xCE);
lcd_data(num[0]);
msdelay(10);
PORTB=0x01;
if(voltage>433&& voltage<443.825)//clockwiise
PORTB=0xA0;
msdelay(20);
PORTB=0x00;
lcd_cmd(0xC0);
for(int i=0;i<13;i++){
lcd_data(tap[i]);}
lcd_data(num[1]);
msdelay(10);
PORTB=0x02;
PORTB=0x00;
40
lcd_cmd(0xC0);
for(int i=0;i<13;i++)
lcd_data(tap[i]);
lcd_data(num[2]);
msdelay(10);
PORTB=0x04;
if(voltage>411.35&& voltage<422.175)//anticlockwise
PORTB=0xC0;
msdelay(20);
PORTB=0x00;
lcd_cmd(0xC0);
for(int i=0;i<13;i++)
lcd_data(tap[i]);
lcd_data(num[3]);
msdelay(10);
PORTB=0x08;
41
PORTB=0xC0;
msdelay(40);
PORTB=0x00;
lcd_cmd(0xC0);
for(int i=0;i<13;i++)
lcd_data(tap[i]);
lcd_data(num[4]);
msdelay(10);
PORTB=0x10;
42