Professional Documents
Culture Documents
TBS Typicals en
TBS Typicals en
Connect to knowledge
1 Air-termination 2 E
arthing 3 Equipotential 4 S
urge protection
and down-
conductor
systems bonding
systems
systems
From the basics through to concrete
systems applications – in local training offers,
we can provide knowledge about:
■
Protective equipotential bonding and func-
ten
equipo
2
Earthing systems
The foundation for lightning and surge protection
Type A Type B
■
Horizontal earther ■
Ring earther (surface earther)
■
Vertical earther (earth rod) ■
Foundation earth electrode
3
Planning aid for creating a foun-
dation earth electrode
Start of planning
No No No
Increased earthing
transition resistance,
Individual foundations,
e.g. through "Black Reinforced
e.g. for
trough", "White trough", foundations
structural supports
completely encapsulated present?
present?
perimeter insulation
present?
Yes Yes
Yes
Foundation earth
Ring earther Ring earther
electrode
outside the outside the Foundation earth elec- Foundation earth elec-
Connect all individual
floor plate/ floor plate/ trode trode
foundations into a
insulation insulation Grid width Grid width
closed ring
Grid width Grid width ≤ 20 m x 20 m ≤ 20 m x 20 m
Grid width
≤ 10 m x 10 m ≤ 20 m x 20 m
≤ 20 m x 20 m
Material laid with min. 5 cm
Material laid with min. 5 cm
concrete cover or rustproof
Material V4A, 1.4571 / Material V4A, 1.4571 / Material V4A, 1.4571 / concrete cover or V4
V4A, stainless steel or V4A
1.4404/ 316Ti/ 316L 1.4404/ 316Ti/ 316L 1.4404/ 316Ti/ 316L material, 1.4571 / 1.4404/
material, 1.4571 / 1.4404/
316Ti/ 316L
316Ti/ 316L
4
Earthing material for use in concrete:
■ Surrounded with at least 5 cm of concrete on all Earthing material for use in the earth:
sides ■ V4A material
5052 DIN 30X3.5 60 m 5019 34 7 Flat conductor 30x3.5 FT, 50 kg/ring (0.84 kg/m)
5052 DIN 40X4 40 m 5019 35 5 Flat conductor 40x4 FT, 50 kg/ring (1.28 kg/m)
5052 V4A 30X3.5 25 m 5018 73 0 Flat conductor 30x3.5 V4A, 21 kg/ring (0.83 kg/m)
250 V4A 10 pieces 5312 92 5 Cross-connector for flat conductors and round conductors V4A
252 8-10 V4A 10 pieces 5312 31 8 Cross-connector with intermediate plate V4A
249 8-10 V4A 10 pieces 5311 40 4 Vario quick connector round/round, V4A
219 20 BP V4A 5 pieces 5000 86 6 BP earth rod, ∅ 20 mm, length: 1.5 m, V4A
1819 20BP 5 pieces 3041 21 2 Earth point for earth rod ST and BP
2760 20 V4A 5 pieces 5001 63 3 Connection clip for earth rod, universal, V4A
5
Special requirements for foundations with trough Black trough
seals and perimeter insulation These are building seals which can withstand the
With trough seals, the earth contact of the earther is water pressure and are made of multi-layer plastic or
not guaranteed. For this reason, a ring earther is to be bitumen strips (black material).
installed outside the trough seal. Long-lasting corro-
White trough
sion protection is to be ensured. Rustproof stainless
The white trough is created from water-impervious
steels (V4A) must be used.
concrete (WI concrete). The concrete can take up
water but, even with the long-term effect of the water
on the concrete, is not fully permeated, i.e. no mois-
ture occurs on the inner side of the wall.
Black trough,
White trough, pressurised water-tight Insulated floor plate with perimeter
ring earther entry above the
ring earth entry in the groundwater insulation (here: shown in blue)
highest groundwater level
Equipotential bonding
Protection against dangerous potential differences
Protective equipotential bonding is to be created
by connecting the following conductors to
the main earthing rail, if appropriate:
■ Earthing conductor to system earther;
6
■ Protective equipotential bonding conductor of ■ Protective equipotential bonding conductor of
other metallic pipe systems run into the building conductive reinforcements of concrete structures,
from another building, where they can be touched and are reliably inter-
e.g. central heating and air-conditioning systems, connected
exhaust gas traps;
■ Protective equipotential bonding conductor from
other outside conductive parts, if they can be tou-
ched in the normal state of use;
7
Lightning protection systems
Lightning protection is preventive fire protection
One of the key evaluation factors in each lightning ments in a lightning location method. The result of
protection risk analysis is the local density of light- this risk analysis is the existing risk level I‒IV. The
ning strikes. These are expressed in lightning strikes planner must implement the appropriate lightning
per km²/year and should be determined by measure- protection class I‒IV.
Lightning
Air-termin- Down-con- Separation Room protection
Earthing
ation systems ductors distance screening equipotential
bonding
8
Protection class of the lightning protection system ■ Separation distance to avoid dangerous
The characteristics of a lightning protection system spark formation
(LPS) are specified by the characteristic values of the ■ Minimum length of the earthers
structure system to be protected and according to the
b) Characteristic data, irrespective of the pro-
lightning protection class.
tection class of the LPS:
Each protection class of an LPS is ■ Lightning protection equipotential bonding
9
Product standards Contents
VDE 0185-305-1 (IEC 62305-1) Lightning protection system components – Requirements for connection components
VDE 0185-561-2 (IEC 62561-2) Lightning protection system components – Requirements for conductors and earthers
VDE 0185-561-3 (IEC 62561-3) Lightning protection system components – Requirements for isolating spark gaps
VDE 0185-561-4 (IEC 62561-4) Lightning protection system components – Requirements for holders
VDE 0185-561-6 (IEC 62561-6) Lightning protection system components – Requirements for lightning strike counters
VDE 0185-561-7 (IEC 62561-7) Lightning protection system components – Requirements for earthing enhancing compounds
VDE 0675-6-11 (IEC 61643-11) Surge protection devices for use in low-voltage power systems – Requirements and test methods
VDE 0845-3-1 (IEC 61643-21) Surge protective devices connected to telecommunications and signalling networks
Air-termination systems
Planning with the protective angle, rolling sphere and grid method
The probability that a lightning current enters a con- nected at roof height, in order to guarantee current
struction system to be protected is reduced consid- distribution.
erably by a correctly planned air-termination system.
The air-termination system can be comprised of On a structure, air-termination systems must be at-
any combination of the following components: tached to corners, exposed areas and edges (particu-
■ Air-termination rods (including freestanding masts)
larly to the top part of facades).
■ Tensioned cables Following a practical assessment of the building, one
■ Meshed conductors or a combination of the following planning methods is
The individual air-termination rods should be intercon- selected.
The rolling sphere method is suitable in The grid method is suitable for
The protective angle method is suitable
every case, but is particularly suitable for buildings with simple shapes, e.g.
for buildings with simple shapes.
complex systems. with flat roofs.
10
With the different protection methods, the bases for protection class can be found in the tables and the
the calculation of the air-termination system are the aid diagram and are intended as orientation for the
rolling sphere radius, the grid width or the protective following protection methods.
angle α. The basis data for the appropriate lightning
Protection method
Radius of this
Lightning protection class Grid width W Protective angle α°
rolling sphere r
I 20 m 5 x 5m
II 30 m 10 x 10 m
See graphic below
III 45 m 15 x 15 m
IV 60 m 20 x 20 m
Maximum values of the rolling sphere radius, the grid width and the protective angle according to the appropriate lightning protection class of
the LPS according to IEC/EN 62305-3
1 Lightning protection
angle α
2 Ridge height in m
3 Lightning protection
class I/II/III/IV
Diagram for determining the protective angle in accordance with IEC 62305
II 72 °
III 76 °
IV 79 °
Protective angle based on lightning protection class according to IEC 62305-3 for air-termination rods up to 2 m
11
Rolling sphere method
Calculation of the penetration depth
p Penetration depth r Radius of the lightning sphere d Distance of the air-termination system
12
Protective angle method
Installation principle, building with pitched roof
height greater than 0.5 m 2 Air-termination rod height (h2) 3 Protective angle α
13
Grid method
Installation principle, building with flat roof
1st step: Installing the air-termination system 2nd step: Installing the grids
First, a round conductor is installed at all primary im- A number of different loop sizes are suitable for the
pact points such as ridges, crests or edges. Deter- particular lightning protection class of the building. If,
mine the protected area by transferring the height of as in our example, the overall length l is greater than
the building to the diagram, reading off the protective 20 m, an expansion piece must also be integrated for
angle and transferring this to the building. temperature-controlled length changes.
14
1Risk through direct lightning strikes 2 Protected
against direct lightning strikes but at risk s = separation distance
3 Height of the air-termination rod α Protective angle
Down-conductor systems
Connection of the air-termination system with the earthing system
I 10 m
II 10 m
III 15 m
IV 20 m
15
Calculation of the separation distance according to IEC/EN 62305-3
Steps
kc is dependent on the (partial) lightning current that flows into the down-conductors:
■ 1 down-conductor (only in the case of an isolated lightning protection system): kc = 1
Calculate the value ■ 2 down-conductors: kc = 0.66
(simplified
system) The values apply to all type B earthers and to those type A earthers in which the earther resistance of the neigh-
bouring earther electrodes does not differ by more than a factor of 2. If the earther resistance of
individual electrodes deviates by more than a factor of 2, kc = 1 should be assumed.
If several insulating materials are used, in practice the lowest value for km is used.
Calculate the L is the cable length in metres, measured from the point at which the separation distance (s) is to be calculated
value L up to the closest point of the equipotential bonding.
s = separation distance
16
1 1
3 3
3 HES
2 Length L
Equipotential areas as the reference layer for Creation of equipotential areas, e.g. on every 2nd
calculating the separation distance in high or 3rd floor using:
buildings ■ Lightning protection equipotential bonding through
In high buildings, conventional separation distance cal- suitable lightning arresters and surge protection
culations can create separation distances which can devices for power and communication units
no longer be implemented, as the length to the next ■ Meshed earthing system according to DIN 1804
reference level (e.g. earthing system or closest point of ■ Meshed ceiling reinforcement (multiple times in
the equipotential bonding) is very long in the calcula- the building) 5 x 5 m according to DIN EN 62305-4
tion due to the building dimensions. (VDE 0185-304-4)
■ Connection to reinforcement every 2 m
To still be able to plan and install a lightning protec-
■ Lightning protection equipotential bonding of all
tion system according to VDE 0185- 305-3 (IEC/EN
metallic or electrical cables running into the equipo-
62305-3), the creation of equipotential layers should
tential levels (e.g. external cameras, luminaires,
be taken into account early in the project planning.
supply lines, PV systems, etc.)
17
isCon® down-conductors
Selection aid
Yes
s air > 75 cm
No
Yes
Paintable?
No
Yes
Ex requirements?
No
Additional
Yes No Protection against
mechanical
contact
protection*
voltage
required?
No Yes
s air ≤ 45 cm
Yes No
18
Materials and corrosion protection
Requirements for long-lasting protection
The following materials are preferred for use in exter- vanised surfaces or above aluminium parts as copper
nal lightning protection systems: Hot galvanised steel, particles worn away by rain or other environmental
rustproof steel (VA), copper and aluminium. influences can penetrate the galvanised surface. In
addition, a galvanic element is created, which acceler-
Corrosion
ates corrosion of the contact surface.
Especially when different materials are connected
with one another, there is a risk of corrosion. For this
reason, no copper parts may be installed above gal-
Steel,
Aluminium Copper Stainless steel Titanium Tin
galvanised
Material, form and minimum dimensions of air-termination conductors, air-termination rods, earth entry rods and down-conductors
(a) Chromium ≥ 16%; nickel ≥ 8%; carbon ≤ 0.08%
(b) In certain applications, 8 mm diameter can be reduced to 28 mm² (6 mm diameter) if echanical resistance is not a primary criterion.
(c) At least 70 μm copper plating with 99.9% copper content
(d) Can be used for air-termination rods and base
19
Minimum
Material Shape
dimensions
Earth rod Earthing cable Earth plate
Copper Cable
Tin-plated copper Round, solid
Strip, solid 50 mm²
Round, solid ø 15 mm ø 8 mm
Grid plate ø 20 mm 20 x 2.5 mm
Pipe 500 x 500 mm
Plate, solid 600 x 600 mm
Hot galvanised steel Round, solid
Round, solid ø 14 mm
Pipe ø 25 mm ø 10 mm
Strip, solid
Plate, solid
Grid plate 30 x 3 mm 500 x 500 mm
Profile (a) 290 mm² 600 x 600 mm
Bright steel (b) Cable 70 mm²
Round, solid ø 8 mm ø 10 mm
Strip, solid 25 x 3 mm
Copper-coated steel (c) Round, solid ø 8 mm
Round, solid ø 14 mm ø 10 mm
Strip, solid 30 x 3 mm
Rustproof steel (d) Round, solid ø 10 mm
Round, solid
Strip, solid ø 15 mm 30 x 3.5 mm
Materials, form and cross-section of earthers according to VDE 0185-561-2 (IEC 62561-2)
(a) Various profiles with a cross-section of 290 mm² and a minimum thickness of 3 mm are approved, e.g. cross profiles.
(b) Must be embedded in concrete to a depth of at least 50 mm.
(c) At least 250 μm copper plating with 99.99% copper content.
(d) Chromium ≥ 16%; nickel ≥ 5%; molybdenum ≥ 2%; carbon ≤ 0.08%.
20
Lightning and surge protection
systems
During a lightning strike, only 50% of the lightning operations. OBO lightning current and surge arrest-
energy is arrested into the ground via the earthing ers offer secure protection of the sensitive electrical
system. The other half flows into the electrical in- devices in the system against damage from surge
stallation of the structure. Other reasons for surge voltages.
voltages are remote lightning strikes or switching
4 Data cable ~ 5% I = 5 kA
5 Lightning surges
2,500
Range within which surge protec-
6 tion devices are used
1,500
21
Causes of damage
Equipment and systems can be protected against all the shown causes of
damage using OBO surge arresters.
1 Pulse shape 1, direct lightning strike, 2 Pulse shape 2, remote lightning strike or switching operation,
10/350 μs simulated lightning pulse 8/20 μs simulated lightning pulse (surge voltage)
22
Surge protection systems for energy technology (N) is connected to the protective earth via a collect-
Surge protection devices ensure that power lines under ive spark gap. Following consultation with the local
voltage are properly equipotentially bonded. They re- energy provider, use before the main meter device is
spond before the insulation in electrical and electronic also possible.
devices can be irreparably damaged by surges.
Surge arrester type 2/class II
Type 2/class II surge arresters are used in the 3+1
circuit (e.g. V20 3+NPE). With the 3+1 circuit, the
Lightning current arrester, type 1/class I external lines (L1, L2, L3) are connected to the neu-
Combination arrester, type 1+2/class I+II tral cable (N) via arresters. The neutral conductor (N)
TN-C system: type 1/class I lightning current arrest- is connected to the protective earth via a collective
ers and type 1+2/class I+II combination arresters are spark gap. The arresters must be used before a resid-
used in the 3-pin circuit (e.g.: 3 x MCD 50-B). ual current protective device (RCD), as it would other-
TN-S and TT system: Lightning current and combina- wise interpret the surge current as a residual current
tion arresters are used in the 3+1 circuit (e.g. 3 x MC and interrupt the power circuit.
50-B and 1 x MC 125-B NPE). With the 3+1 circuit,
the external lines (L1, L2, L3) are connected to the
neutral cable (N) via arresters. The neutral conductor
23
Lightning and surge protection for satellite
systems according to IEC/EN 60728-11
Satellite systems and antennas are often in exposed
locations on roofs, next to the air-termination rods. For
this reason, air-termination rods must be used to pro-
tect these systems against direct lightning strikes, to
prevent them from serving as lightning air-termination
systems themselves. Ideally, in the finished lightning
protection system, the satellite antenna should be lo-
cated within the protective angle of the air-termination
rod. In this case, the risk of a direct lightning strike in
the SAT cables is almost zero.
However, if the air-termination rod is struck,
surge voltages will be coupled.
Using a surge protection device like the OBO TV 4+1
(for protecting for example multiswitches) or FC-SAT-D
(for protecting a TV set), these surge voltages can be
limited to a level that is safe for the device in question.
Here, it is vital that the required separation distance (s)
is maintained between the air-termination rod and the
antenna system. The following figures show the light-
ning and surge protection for a satellite TV system:
3 Fine protection device for SAT and 230 V supply line, e.g. OBO FC-SAT-D 5092816
With appropriate coordination of the lightning and addition to the surge protection. As well as the stand,
surge protection components, lightning currents and ard antenna earthing using 4 mm² Cu, the antenna
surges can be safely arrested. If there is no external system must additionally be connected with the main
lightning protection on the building, the exposed in- earthing rail using a copper earthing conductor of
stallation of the satellite system poses the risk of at- minimum 16 mm².
tracting a direct strike, like an air-termination rod. For
this reason, class D1 lightning arresters are needed in
24
Should a risk analysis according to VDE 0185-305-2
(IEC/EN 62305-2) not be possible or not be required
by the authorities, then static atmospheric surge
voltages (e.g. lightning) can cause arcing from the
16 mm² earthing conductor to the electrical installa-
tion or the antenna system of the building. For this
reason, we recommend making the earthing conduc-
tor insulating and resistant to high voltages and float-
ing discharges through suitable measures.
3 Fine protection device for SAT and 230 V supply line, e.g. OBO FC-SAT-D 5092816
25
Notes
26
OBO Typicals ‒ detailed mounting drawings of lightning protection,
earthing and equipotential bonding systems
27
1 External lightning protection systems for flat roofs
=90°
=180°
=0-360°
Sheet: of:
Ind. Amendment typical Date: Name:
28
1 External lightning protection systems for flat roofs
Sheet: of:
Ind. Amendment typical Date: Name:
29
1 External lightning protection systems for flat roofs
2
3
Sheet: of:
Ind. Amendment typical Date: Name:
30
1 External lightning protection systems for flat roofs
1
6
Steel 15
Stainless steel 10
Copper 10
Aluminium 10
Sheet: of:
Ind. Amendment typical Date: Name:
31
1 External lightning protection systems for flat roofs
3
2
Sheet: of:
Ind. Amendment typical Date: Name:
32
1 External lightning protection systems for flat roofs
5
3
Sheet: of:
Ind. Amendment typical Date: Name:
33
1 External lightning protection systems for flat roofs
2
3
Sheet: of:
Ind. Amendment typical Date: Name:
34
1 External lightning protection systems for flat roofs
2
3
Sheet: of:
Ind. Amendment typical Date: Name:
35
1 External lightning protection systems for flat roofs
Detail 1
Detail 2
Detail 2
Detail 1
1.
1
Item No. Designation Description Q-ty
Sheet: of:
Ind. Amendment typical Date: Name:
36
1 External lightning protection systems for flat roofs
Detail 1
2
Detail 1
Sheet: of:
Ind. Amendment typical Date: Name:
37
1 External lightning protection systems for flat roofs
4 5
1
3
3 Mounting on 5 blind rivets d = 3,5 mm 4 2 blind rivets made of stainless steel VA d = 6,3 mm
2 1
Sheet: of:
Ind. Amendment typical Date: Name:
38
1 External lightning protection systems for flat roofs
4
3
Sheet: of:
Ind. Amendment typical Date: Name:
39
1 External lightning protection systems for flat roofs
down-conductor
4 5
Sheet: of:
Ind. Amendment typical Date: Name:
40
1 External lightning protection systems for flat roofs
4 3
Sheet: of:
Ind. Amendment typical Date: Name:
41
1 External lightning protection systems for flat roofs
2 3
Detail 1
Detail 1
Sheet: of:
Ind. Amendment typical Date: Name:
42
1 External lightning protection systems for flat roofs
3
down-conductor
Sheet: of:
Ind. Amendment typical Date: Name:
43
1 External lightning protection systems for flat roofs
down-conductor
4
2
Sheet: of:
Ind. Amendment typical Date: Name:
44
1 External lightning protection systems for flat roofs
Sheet: of:
Ind. Amendment typical Date: Name:
45
1 External lightning protection systems for flat roofs
1
2
Sheet: of:
Ind. Amendment typical Date: Name:
46
1 External lightning protection systems for flat roofs
3 4
2
3 4
7 5
Sheet: of:
Ind. Amendment typical Date: Name:
47
1 External lightning protection systems for flat roofs
e
h
5
1
4 3
3m 0,15 m
4m 0,25 m
5m 0,35 m
6m 0,45 m
Sheet: of:
Ind. Amendment typical Date: Name:
48
1 External lightning protection systems for flat roofs
Sheet: of:
Ind. Amendment typical Date: Name:
49
1 External lightning protection systems for flat roofs
Sheet: of:
Ind. Amendment typical Date: Name:
50
Notes
51
2 External lightning protection systems for flat roof equipment
1
1
2
the set
1 1
2
the set
Sheet: of:
Ind. Amendment typical Date: Name:
52
2 External lightning protection systems for flat roof equipment
Sheet: of:
Ind. Amendment typical Date: Name:
53
2 External lightning protection systems for flat roof equipment
Sheet: of:
Ind. Amendment typical Date: Name:
54
2 External lightning protection systems for flat roof equipment
Sheet: of:
Ind. Amendment typical Date: Name:
55
2 External lightning protection systems for flat roof equipment
Sheet: of:
Ind. Amendment typical Date: Name:
56
2 External lightning protection systems for flat roof equipment
4
2
Sheet: of:
Ind. Amendment typical Date: Name:
57
2 External lightning protection systems for flat roof equipment
Sheet: of:
Ind. Amendment typical Date: Name:
58
2 External lightning protection systems for flat roof equipment
Sheet: of:
Ind. Amendment typical Date: Name:
59
2 External lightning protection systems for flat roof equipment
3
5
Sheet: of:
Ind. Amendment typical Date: Name:
60
2 External lightning protection systems for flat roof equipment
Sheet: of:
Ind. Amendment typical Date: Name:
61
2 External lightning protection systems for flat roof equipment
Detail 1
1 4
Detail 1
Sheet: of:
Ind. Amendment typical Date: Name:
62
2 External lightning protection systems for flat roof equipment
6 7 8
9
3 4
10
11 3
1
Sheet: of:
Ind. Amendment typical Date: Name:
63
2 External lightning protection systems for flat roof equipment
2
6
1
5
Sheet: of:
Ind. Amendment typical Date: Name:
64
2 R External lightning protection systems for flat roof equipment
4 5 6
2
1
Sheet: of:
Ind. Amendment typical Date: Name:
65
2 External lightning protection systems for flat roof equipment
Detail 1
Detail 1
Detail 2
4
Detail 2
Detail 3
1
5
2
Detail 3
Sheet: of:
Ind. Amendment typical Date: Name:
66
2 External lightning protection systems for flat roof equipment
2
1
8
2 7
separation distance
Sheet: of:
Ind. Amendment typical Date: Name:
67
2 External lightning protection systems for flat roof equipment
Sheet: of:
Ind. Amendment typical Date: Name:
68
2 External lightning protection systems for flat roof equipment
8 9
3 4
Sheet: of:
Ind. Amendment typical Date: Name:
69
2 External lightning protection systems for flat roof equipment
1
11
10
6 7
5
Sheet: of:
Ind. Amendment typical Date: Name:
70
Notes
71
3 External lightning protection systems for pitched roofs
distance max. 1 m
2
1
Sheet: of:
Ind. Amendment typical Date: Name:
72
3 External lightning protection systems for pitched roofs
distance max. 1 m
2
Sheet: of:
Ind. Amendment typical Date: Name:
73
3 External lightning protection systems for pitched roofs
distance max. 1m
Sheet: of:
Ind. Amendment typical Date: Name:
74
3 External lightning protection systems for pitched roofs
distance max. 1 m
Sheet: of:
Ind. Amendment typical Date: Name:
75
3 External lightning protection systems for pitched roofs
distance max. 1 m
Sheet: of:
Ind. Amendment typical Date: Name:
76
3 External lightning protection systems for pitched roofs
3 distance max. 1 m
1
2
Sheet: of:
Ind. Amendment typical Date: Name:
77
3 External lightning protection systems for pitched roofs
distance max. 1m
3
Sheet: of:
Ind. Amendment typical Date: Name:
78
3 External lightning protection systems for pitched roofs
Detail 1
≈150°, L≈0.3 m
Detail 1
Replacement options:
6
Sheet: of:
Ind. Amendment typical Date: Name:
79
3 External lightning protection systems for pitched roofs
Detail 1
1
Detail 1
3
Detail 2
Detail 2
distance max. 1 m 1
Sheet: of:
Ind. Amendment typical Date: Name:
80
3 External lightning protection systems for pitched roofs
≈150°, L≈0.3 m
Sheet: of:
Ind. Amendment typical Date: Name:
81
3 External lightning protection systems for pitched roofs
down conductor
Sheet: of:
Ind. Amendment typical Date: Name:
82
3 External lightning protection systems for pitched roofs
1
3 2
≈150°, L≈0.3 m
down conductor
Sheet: of:
Ind. Amendment typical Date: Name:
83
3 External lightning protection systems for pitched roofs
2 3
Detail 1
5
Detail 1
down conductor
Sheet: of:
Ind. Amendment typical Date: Name:
84
3 External lightning protection systems for pitched roofs
Detail 1
Detail 1
Sheet: of:
Ind. Amendment typical Date: Name:
85
3 External lightning protection systems for pitched roofs
≈150°, L≈0.3 m
4 2
Detail 1
Detail 1
Sheet: of:
Ind. Amendment typical Date: Name:
86
3 External lightning protection systems for pitched roofs
≈150°, L≈0.3 m
Detail 1
Detail 1
Sheet: of:
Ind. Amendment typical Date: Name:
87
3 External lightning protection systems for pitched roofs
4 2
Sheet: of:
Ind. Amendment typical Date: Name:
88
3 External lightning protection systems for pitched roofs
6 7
Sheet: of:
Ind. Amendment typical Date: Name:
89
3 External lightning protection systems for pitched roofs
4 5
Sheet: of:
Ind. Amendment typical Date: Name:
90
3 External lightning protection systems for pitched roofs
6 5
3 2
Sheet: of:
Ind. Amendment typical Date: Name:
91
3 External lightning protection systems for pitched roofs
Detail 1
Detail 1
9 10
Sheet: of:
Ind. Amendment typical Date: Name:
92
3 External lightning protection systems for pitched roofs
2
3
Sheet: of:
Ind. Amendment typical Date: Name:
93
3 External lightning protection systems for pitched roofs
4
1
Detail 1
Detail 1
Sheet: of:
Ind. Amendment typical Date: Name:
94
3 External lightning protection systems for pitched roofs
Detail 1
Detail 1
Detail 2
Detail 2
5
Detail 3
3 4
2
Detail 3
1
Item No. Designation Description Q-ty
Sheet: of:
Ind. Amendment typical Date: Name:
95
4 Down-conductors
distance max. 1 m
Sheet: of:
Ind. Amendment typical Date: Name:
96
4 Down-conductors
distance max. 1 m
Sheet: of:
Ind. Amendment typical Date: Name:
97
4 Down-conductors
Detail 1
Detail 1
Sheet: of:
Ind. Amendment typical Date: Name:
98
4 Down-conductors
Sheet: of:
Ind. Amendment typical Date: Name:
99
4 Down-conductors
Detail 1
distance max. 1 m
Sheet: of:
Ind. Amendment typical Date: Name:
100
4 Down-conductors
Sheet: of:
Ind. Amendment typical Date: Name:
101
4 Down-conductors
distance max. 1 m
Sheet: of:
Ind. Amendment typical Date: Name:
102
4 Down-conductors
3
2
4
Sheet: of:
Ind. Amendment typical Date: Name:
103
4 Down-conductors
1
2
Sheet: of:
Ind. Amendment typical Date: Name:
104
Notes
105
5 Lightning strike counter
Sheet: of:
Ind. Amendment typical Date: Name:
106
5 Lightning strike counter
Detail 1
Detail 1
4
3
1 2
Sheet: of:
Ind. Amendment typical Date: Name:
107
6 Isolated lightning protection systems
3
7
Detail 1
2
8
4 5 6
Detail 1
1 5408938 isFang IN-A 4000 isFang, insulated air-termination rod for inner-routed isCon
2 5408002 isCon Pro+ 75 SW isCon conductor
3 5408930 isFang 3B-100-A isFang air-termination rod stand with side exit
4 5403227 F-FIX-S16 Concrete block for FangFix-System 16 kg
5 5403238 F-FIX-B16 3B Base for FangFix system 16 kg for mounting the isFang tripod
6 5408971 isFang 3B-G1 isFang-3B threaded rod
7 2153726 M-Quick M25 LGR Multi-Quick clip
8 5218882 165 MBG UH Universal flat conductor adapter for roof conductor holder
9 5218700 165 MBG 8-10 Roof conductor holder for flat roofs
Sheet: of:
Ind. Amendment typical Date: Name:
108
6 Isolated lightning protection systems
Detail 1
4
Detail 1
Detail 2
6
Detail 2
5
Sheet: of:
Ind. Amendment typical Date: Name:
109
6 Isolated lightning protection systems
Detail 1
Detail 1
2
3
Detail 2
Detail 2
Detail 3
Detail 3
7
Sheet: of:
Ind. Amendment typical Date: Name:
110
6 Isolated lightning protection systems
Detail 1 Detail 1
6 5 4
Detail 2
Detail 2
7
Detail 3
10
Detail 3 8
11
9
12
Item No. Designation Description Q-ty
1 5408938 isFang IN-A 4000 isFang, insulated air-termination rod for inner-routed isCon
2 5408002 isCon Pro+ 75 SW isCon conductor
3 5408930 isFang 3B-100-A isFang air-termination rod stand with side exit
4 5403227 F-FIX-S16 Concrete block for FangFix-System 16 kg
5 5403238 F-FIX-B16 3B Base for FangFix system 16 kg for mounting the isFang tripod
6 5408971 isFang 3B-G1 isFang-3B threaded rod
7 2153726 M-Quick M25 LGR Multi-Quick clip
8 5218882 165 MBG UH Universal flat conductor adapter for roof conductor holder
9 5218700 165 MBG 8-10 Roof conductor holder for flat roofs
10 5021294 RD 8 ALU-T Round conductor, aluminium
11 5408022 isCon connect isCon-connection element
12 5311519 249 8-10 ALU Vario quick connector
Sheet: of:
Ind. Amendment typical Date: Name:
111
6 Isolated lightning protection systems
Detail1
Detail 1
2 Detail 2
Detail 2
Sheet: of:
Ind. Amendment typical Date: Name:
112
6 Isolated lightning protection systems
Detail 1
1
Detail 1
Detail 2
Detail 2
Sheet: of:
Ind. Amendment typical Date: Name:
113
6 Isolated lightning protection systems
Detail 1
Detail 2
3
Detail 1
1
4
Detail 2
Detail 3 Detail 3
Detail 4
3
5
Detail 4
Sheet: of:
Ind. Amendment typical Date: Name:
114
6 Isolated lightning protection systems
Detail 1
2 3
0,7 m
Detail 1
1
insulation of 3 - 5 m
Remark:
DIN EN 62305-3 (VDE 0185-305-3)
2
The area to be protected against shock
voltages correponds to the height of
the finger tips of a person with raised
hand (2,5 m) plus the separation
distance "s".
10
Item No. Designation Description Q-ty
Sheet: of:
Ind. Amendment typical Date: Name:
115
6 Isolated lightning protection systems
2 3 4
Sheet: of:
Ind. Amendment typical Date: Name:
116
Notes
117
7 Earthing systems
Sheet: of:
Ind. Amendment typical Date: Name:
118
7 Earthing systems
HIT HIT
8 9 10 11 12 13 14 15 16 17
HIT
1 2 3 4
HIT
5 6 7
Sheet: of:
Ind. Amendment typical Date: Name:
119
7 Earthing systems
5 6
4 6
3
1
8
1
8
Sheet: of:
Ind. Amendment typical Date: Name:
120
7 Earthing systems
2
1m
0,7 m
4 1
Sheet: of:
Ind. Amendment typical Date: Name:
121
7 Earthing systems
1m
3
0,7 m
8
6
Sheet: of:
Ind. Amendment typical Date: Name:
122
7 Earthing systems
2 1m
0,7 m
8 3
4
8
6
7
Sheet: of:
Ind. Amendment typical Date: Name:
123
7 Earthing systems
8
1
10
7
Sheet: of:
Ind. Amendment typical Date: Name:
124
7 Earthing systems
3
1m
50 mm
0,7 m
1
2
Sheet: of:
Ind. Amendment typical Date: Name:
125
7 Earthing systems
20 m
20 m
Sheet: of:
Ind. Amendment typical Date: Name:
126
7 Earthing systems
Fittings
Sheet: of:
Ind. Amendment typical Date: Name:
127
7 Earthing systems
Sheet: of:
Ind. Amendment typical Date: Name:
128
7 Earthing systems
3 4
5
Expansion joint
1
Sheet: of:
Ind. Amendment typical Date: Name:
129
7 Earthing systems
Sheet: of:
Ind. Amendment typical Date: Name:
130
7 Earthing systems
2
1
1 5003040 213 3000 DIN Profile earthing rod with connecting lug
2 5040507 928 Earthing terminal for fastening on earthing strap
Sheet: of:
Ind. Amendment typical Date: Name:
131
8 Equipotential bonding systems
Detail 1
Detail 1
6
7
3
2
0,4 m
Sheet: of:
Ind. Amendment typical Date: Name:
132
8 Equipotential bonding systems
50 mm
2
0,4 m
Sheet: of:
Ind. Amendment typical Date: Name:
133
8 Equipotential bonding systems
Gas boiler
4 Detail 1
Detail 1
6 3
Sheet: of:
Ind. Amendment typical Date: Name:
134
8 Equipotential bonding systems
Detail 1
5
Detail 1
Detail 2 6
4 2
6
Detail 2
Sheet: of:
Ind. Amendment typical Date: Name:
135
8 Equipotential bonding systems
50 mm
Sheet: of:
Ind. Amendment typical Date: Name:
136
Notes
137
Notes
138
Notes
139
OBO Bettermann Holding GmbH & Co. KG
P.O. Box 1120
58694 Menden
GERMANY
Technical Customer Service
Tel.: +49 (0) 2373 - 89 1300
toi@obo.de
www.obo-bettermann.com