TotalEnergies EP Nigeria Limited

TECHNICAL SERVICES DIRECTORATE


ENGINEERING, CONSTRUCTION & PROJECTS
OML 100 FLARE REDUCTION PROJECT

EDD1 - Instrument Datasheets Flow Indicating Tranmitter page: 1/5


Rev. Status Rev. Date SMR/SOR/SIN nbr.
COMPANY ref. numbe NG-ODU-EDD1-ARI2-070403 1.2 IFR 2-Sep-22 SMR-100-20-002
Discipline INS Doc. Type DTS (Syst.) Unit NX_NAP

Flow Indicating Transmitter


Datasheet

Remarks:

1.2 2-Sep-22 Issued for Review W. Ahmed A. Olajide Y. Alege


1.1 29-Jul-22 Issued for Review I. Ajao A. Olajide Y. Alege
1.0 20-May-22 Issued for Review I. Ajao A. Olajide Y. Alege
Rev. Date Description Issued by Reviewed by Approved by
This document is the property of TOTAL and must not be reproduced, stored or disclosed without permission from COMPANY.
TotalEnergies EP Nigeria Limited
Engineering,
TECHNICAL SERVICES DIRECTORATE Construction &
ENGINEERING, CONSTRUCTION & PROJECTS Projects Division
OML 100 FLARE REDUCTION PROJECT

EDD1 - Instrument Datasheets Flow Indicating Tranmitter page: 5-Feb


Rev. Status Rev. Date SMR/SOR/SIN nbr.
ECP ref. number NG-ODU-EDD1-ARI2-070403 1.2 IFR 2-Sep-22 SMR-100-20-002
Discipline INS Doc. Type DTS (Syst.) Unit NX_NAP

Instr.
S/N DTS number TYPE Class Rev. Remarks
Tag

1 3 Flow Indicating Transmitter FIT-612 1.2

2 4 Flow Indicating Transmitter FT-213 1.2

3 5 Flow Indicating Transmitter FT-741 1.2

Note 1:

Note 2 :

Note 3:

Note 4 :

Note 5 :

This document is the property of TOTAL and must not be reproduced, stored or disclosed without permission from COMPANY.
TotalEnergies EP Nigeria Limited Engineering,
TECHNICAL SERVICES DIRECTORATE Construction &
ENGINEERING, CONSTRUCTION & PROJECTS Projects Division
OML 100 FLARE REDUCTION PROJECT
16376657 The project is currently under leadership of…
SMR100-FRP ENGINEERING TEAM CONSTRUCTION TEAM CW & SURVEY TEAM X PROJECT TEAM

EDD1 - Instrument Datasheets Flow Indicating Tranmitter page: 3/5

COMPANY Rev. Status Rev. Date Discipline INS


NG-ODU-EDD1-ARI2-070403
ref. number: 1.2 IFR 2-Sep-22 Doc. Type DTS
CONTRACTOR ref: - - - (Syst.) Unit 6X
DATASHEET Nbr: PID reference nbr:
NG-ODU-EDD1-ARI2-070403 NG-ODU-EDD1-ARI2-010201

1 Tag Number 12-FIT-612

2 P&ID No. NG-ODU-EDD1-ARI2-010201

3 Service Pilot Gas

4 Line Number Piping Class Material 2'' FL 1236 002 B01 B01 Carbon Steel
GENERAL

5 Line Size Schedule Thickness 2'' XS 5.54mm

6 NACE Requirement SIL Requirement MR0175 (a)

7 ATEX / IECEx Certification ATEX MARKING Ex II 2G / Ex "d"-IIB T3 Yes

8 Rating 150#

9 End connection(Welded/Flanged/Threaded) Flanged

10 Face (RF/RJ) RF

11 Fluid Phase Hydrocarbon GAS

12 Design Pressure barg 14


GENERAL

13 Minimal Inlet Meter run Minimal Outlet Meter run 5D 3D


o
14 Design Temp. Min. Design Temp. Max. C -29 60
PROCESS CONDITION

15 Pressure Min Nor m. Max. Barg 8.7


o
16 Temperature C 30.5

17 Viscosity Cp 0.012

18 Mass Flow Rate Kg/h 5.0

19 Volumetric Flow Rate Am3/hr 0.7


GAS

20 Density Kg/m3 7.3

21 Compressiblity Factor Z 0.98

22 Molecular Weight g/mol 18.63

23 Connection Type / Material Flanged RF / SS 1.4408 / CF3M

24 Cable Connection Cable Length (a) m (a)

25 Cable Inner Type Material Cable outer/ Material (a) (a)


SENSOR

26 Flow Velocity Min/Max Unit 0.18 /35 (a) m/s (a)

27 Principle of Operation Time of Flight

28 No. of Paths Multiple path

29

30 Flow Calibration Flow Scale Max./Min m3/h (a) m/s (a)

31 Flow Accuracy Flow Repeatability % ± 0.5% of Reading % ± 0.25%

32 Enclousre Material Ingress Protection SS316L IP65 mini


ULTRASONIC FLOW TRANSMITTER

33 power supply/consump. Loop Supply Vm 24V DC Loop powered

34 Analog Output Frequqency Output mA 4-20mA

35 Local Display Unit Yes LCD Nm3/h

36 Intergrated/ Remote Transm. Cable Gland Remote M20

37 HART Protocol Yes Version 6 or 7

38 Mounting Position Horizontal Orientation, Transmitter head up

39 Intrusive / Non-Intrusive Type Intrusive Type

40 Accuracy ± 0.5% of Reading

41 Repeatability ± 0.25%

42 Sunshade Yes
PURCH

43 Manufacturer Model Endress + Hauser Prosonic Flow G500


AS E

44 Purchase Order Number VTA


Note:
(a). Vendor to Advise VTC = Vendor to confirm

This document is the property of TOTAL and must not be reproduced, stored or disclosed without permission from COMPANY.
TotalEnergies EP Nigeria Limited Engineering,
TECHNICAL SERVICES DIRECTORATE Construction &
ENGINEERING, CONSTRUCTION & PROJECTS Projects Division
OML 100 FLARE REDUCTION PROJECT
16376657 The project is currently under leadership of…
SMR100-FRP ENGINEERING TEAM CONSTRUCTION TEAM CW & SURVEY TEAM X PROJECT TEAM

EDD1 - Instrument Datasheets Flow Indicating Tranmitter page: 4/5

COMPANY Rev. Status Rev. Date Discipline INS


NG-ODU-EDD1-ARI2-070403
ref. number: 1.2 IFR 2-Sep-22 Doc. Type DTS
CONTRACTOR ref: - - - (Syst.) Unit 6X
DATASHEET Nbr: PID reference nbr:
NG-ODU-EDD1-ARI2-070403 NG-ODU-EDD1-ARI2-010201

1 Tag Number 12-FT-213

2 P&ID No. NG-ODU-EDD1-ARI2-010201

3 Service Relief Gas

4 Line Number Piping Class Material 10'' FS 1236 011 B01 B01 Carbon Steel
GENERAL

5 Line Size Schedule Thickness 10'' Sch, 20 6.35mm

6 NACE Requirement SIL Requirement MR0175 (a)

7 ATEX / IECEx Certification ATEX MARKING Ex II 2G / Ex "d"-IIB T3 Yes

8 Rating 150#

9 End connection(Welded/Flanged/Threaded) Flanged

10 Face (RF/RJ) RF

11 Fluid Phase Hydrocarbon GAS

12 Design Pressure barg 7


GENERAL

13 Minimal Inlet Meter run Minimal Outlet Meter run 5D 3D


o
14 Design Temp. Min. Design Temp. Max. C -29 60
PROCESS CONDITION

15 Pressure Min Nor m. Max. Barg 0.3


o
16 Temperature C 45.47

17 Viscosity Cp 0.01222

18 Mass Flow Rate Kg/h 3746.9

19 Volumetric Flow Rate Nm3/hr 3370


GAS

20 Density Kg/m3 1.112

21 Compressiblity Factor Z 0.9957

22 Molecular Weight g/mol 22.327

23 Connection Type / Material Flanged RF / SS 1.4408 / CF3M

24 Cable Connection Cable Length (a) m (a)

25 Cable Inner Type Material Cable outer/ Material (a) (a)


SENSOR

26 Flow Velocity Min/Max Unit 0.18 /35 (a) m/s (a)


27 Principle of Operation Time of Flight

28 No. of Paths Multiple path

29

30 Flow Calibration Flow Scale Max./Min m3/h (a) m/s (a)


31 Flow Accuracy Flow Repeatability % ± 0.5% of Reading % ± 0.25%

32 Enclousre Material Ingress Protection SS316L IP65 mini


ULTRASONIC FLOW TRANSMITTER

33 power supply/consump. Loop Supply Vm 24V DC Loop powered

34 Analog Output Frequqency Output mA 4-20mA

35 Local Display Unit Yes LCD Nm3/h

36 Intergrated/ Remote Transm. Cable Gland Remote M20

37 HART Protocol Yes Version 6 or 7

38 Mounting Position Horizontal Orientation, Transmitter head up

39 Intrusive / Non-Intrusive Type Intrusive Type

40 Accuracy ± 0.5% of Reading

41 Repeatability ± 0.25%

42 Sunshade Yes
PURCH

43 Manufacturer Model Endress + Hauser Prosonic Flow G500


AS E

44 Purchase Order Number VTA


Note:
(a). Vendor to Advise VTC = Vendor to confirm

This document is the property of TOTAL and must not be reproduced, stored or disclosed without permission from COMPANY.
TotalEnergies EP Nigeria Limited Engineering,
TECHNICAL SERVICES DIRECTORATE Construction &
ENGINEERING, CONSTRUCTION & PROJECTS Projects Division
OML 100 FLARE REDUCTION PROJECT

16376657 The project is currently under leadership of…

SMR100-FRP ENGINEERING CONSTRUCTION TEAM CW & SURVEY TEAM X PROJECT TEAM

EDD1 - Instrument Datasheets Flow Indicating Tranmitter page: 5/5


COMPANY Rev. Status Rev. Date Discipline INS
NG-ODU-EDD1-ARI2-070403
ref. number: 1.2 IFR 2-Sep-22 Doc. Type DTS
CONTRACTOR ref: - (Syst.) Unit 6X
DATASHEET Nbr: PID reference nbr:
NG-ODU-EDD1-ARI2-070403 NG-ODU-EDD1-ARI2-010201
1 Tag Number 12-FT-741
2 Service Nitrogen Purge Gas Flow to Flare
3 Equipment Function
4 Line Number / Piping Class / Material 1'' NG 1274 001 B01 B01 Carbon Steel
GENERAL 5 Pipe O.D. / Schedule / Thickness 33.4 mm XS 4.55 mm
6 Line Size 1"
7 Area Classification Zone-2, Gr. IIA, T3
8 NACE Requirement SIL Requirement MR0175 Note 2
9 ATEX / IECEx Certification ATEX MARKING Ex II 2G / Ex "d"-IIB T3 Yes
10 Process Fluid Fluid State Nitrogen Gas
Mass Flow Rate
11 Volume Flow Rate Am3/ 0.95 (HOLD 1) 2 (Note 1)
Kg/hr
12 Inlet Pressure bar-g Min./Oper./Max. 0.5 0.7 1.0
o
13 Temperature C Min./Oper./Max. AMB 30 (HOLD 1) 40 (HOLD 1)
14 Base Spec. Gravity Oper. Spec. Gravity
PROCESS
15 Molecular Weight Viscosity @ Oper. cP 28.0 0.01 (HOLD 1)
CONDITIONS
16 Quality Superheat
17 Compressiblity Factor Z 0.99 (HOLD 1)
18 Percent Solids
19 Design Pressure / Temperature / Oper. Density 7 Barg 60oC (HOLD 1) 1.92 (HOLD 1)
20 Minimal Inlet Meter run Minimal Outlet Meter run 5D 3D
21 Element Type Flat Blade Turbine
22 Integrated flow straightener Yes
23 End Conn. Size & Type 1/2" RF Flanged
24 End Conn. Rating CL150
25 Nominal Flow Range m3/hr VTA
Accuracy
26 ± 0.5% of Reading
% Repeatability
27 Linearity % (VTA) ± 0.25%
%
28 K Factor (cycles per unit volume) VTA
29 Excitation VTA
30 Body Material 316L SS
31 Support Material 316L SS
METER 32 Shaft Material AISI 316 or 316L SS
33 Flange Material 316L SS
34 Rotor Material AISI 316 or 316L SS
35 Bearing Material Tungsten Carbide
36 Bearing Type Ball
37 Maximum Speed RPM VTA
38 Minimum Output Voltage VTA
39 Pick-Up Type & Quantity Magnetic, Two (2)
40 Ingress Protection IP65 minimum
41 Pressure Drop 0.21 - 0.34 Bar (VTC)
42 Temperature & Pressure Rating VTA
Over Speed Protection / Reverse Flow Protection / Shocks
43 Yes Yes Yes
Protection
44 Function Indicate, Transmit
45 Pre-Amplifier Yes
46 Mounting Remote on 2" Pipe, with 316 SS Bracket
47 Supply Voltage Electrical Connection 24V DC, Loop-powered M20 x 1.5
48 Scale Range VTA
49 Output Range SMm3/d VTA
OPTIONS
50 Temperature Compensation No
51 Preset Counter MFR. STD.
52 Strainer Size & Mesh Provided by Other
53 Totalizer No
54 Transmitter Housing Material / Output 316L SS / 4-20 mA, HART
55 Sunshade Yes
56 Manufacturer Faure Herman
57 Model No. VTA
PURCHASE
58 Purchase Order Num. VTA
59 Serial Number VTA
NOTES:
1) Maximum =13 kg/h (initial sweeping of air during start-up
2) VTA = Vendor to Advice
3) VTC = Vendor to Confirm

HOLDS:
1) To be confirmed with Nitrogen Generator Package vendor data

This document is the property of TOTAL and must not be reproduced, stored or disclosed without permission from COMPANY.