Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

MSSP Report

1. Project Informa on
Date 2/26/2024
Project name Academia Cozy Cool
Project address Av Primera con Buena Vista La California Edif Befca
Country Venezuela
State
City CARACAS
Client name Inversiones Cozy Cool
Client address Av Primera con Buena Vista La California Edif Befca
Designed by
Reference New Project
Revision
Al tude(m) 48
Indoor DB temperature in cooling(℃) 24
Indoor WB temperature in cooling(℃) 16
Outdoor DB temperature in cooling(℃) 33
Outdoor WB temperature in cooling(℃) 28.4
Indoor DB temperature in hea ng(℃) 21
Indoor WB temperature in hea ng(℃) 14
Outdoor DB temperature in hea ng(℃) 21.5
Outdoor WB temperature in hea ng(℃) 18.6

2. Overall Material List


2.1 Equipment List
Model Quan ty Descrip on
MV8-785WV2WN1(MA) 1 V8 Master VRF (220V)
MIH200T1HN18 1 High Sta c Pressure Duct
MIH140T2HN18 1 Medium Sta c Pressure Duct
MIH90Q4HN18 1 Four-way Casse e
MIH71T2HN18 1 Medium Sta c Pressure Duct
MIH71F3HN18 1 Floor Standing (F3 series)
MIH56Q2HN18 1 Two-way Casse e
MIH56GHN18 1 Wall mounted
MIH36Q1HN18 1 One-way Casse e
MIH36Q4CHN18 1 Compact Four-way Casse e
FQZHN-01D 4 Branch joint
FQZHN-02D 2 Branch joint
FQZHN-03D 2 Branch joint
WDC3-86T 1 3rd genera on group controller
WDC3-86S 1 3rd genera on group controller

2.2 Field Providing List


2.2.1 Refrigerant Piping Materials
Model Quan ty Unit Descrip on
Φ1/4 19.06 m Copper pipe
Φ3/8 54.59 m Copper pipe
Φ1/2 19.06 m Copper pipe
Φ5/8 31.24 m Copper pipe
Φ3/4 12.61 m Copper pipe
Φ7/8 19.37 m Copper pipe
Φ1-1/8 1 m Copper pipe
Φ1-1/4 7.63 m Copper pipe
Insula on casing for piping All refrigerant piping and branch joints should be completely insulated.

Recommended insula on casing thickness:


Piping size Thickness
Humidity<80%RH Humidity≥80%RH
Φ6.35~Φ38.1mm ≥15mm ≥20mm
Φ41.3~Φ38.1mm ≥20mm ≥25mm

1
2.2.2 Refrigerant charge
System name Model Quan ty Unit Descrip on
UC-01 R410A 7.12 kg Extra Refrigerant Added

2.2.3 Electrical cables


Type Size Length
Power supply cable Select based on MCA of each unit According to the actual system design
Communica on cable 0.75mm2 3-core shielded According to the actual system design

3. Overall Electrical Characteris cs


Model Quan ty Power supply MCA(A) MFA(A)
MV8-785WV2WN1(MA) 1 220V-3ph-60Hz 82.50 100
MIH200T1HN18 1 220-240V-50/60Hz 8.19 30
MIH140T2HN18 1 220-240V-50/60Hz 2.30 15
MIH90Q4HN18 1 220-240V-50/60Hz 0.58 15
MIH71T2HN18 1 220-240V-50/60Hz 1.50 15
MIH71F3HN18 1 220-240V-50/60Hz 0.40 15
MIH56Q2HN18 1 220-240V-50/60Hz 0.90 15
MIH56GHN18 1 220-240V-50/60Hz 0.51 15
MIH36Q1HN18 1 220-240V-50/60Hz 0.39 15
MIH36Q4CHN18 1 220-240V-50/60Hz 0.54 15

Notes:

1. MCA: Minimum Circuit Amps. MCA is used to select wire size.The value in above table is for one unit.

2. MFA: Maximum Fuse Amps. MFA is used to select overcurrent circuit breakers and residual-current circuit breakers.The value in above
table is for one unit.

4. UC-01
4.1 BOM List (UC-01)
Model Quan ty Unit Descrip on
MV8-785WV2WN1(MA) 1 V8 Master VRF (220V)
MIH200T1HN18 1 High Sta c Pressure Duct
MIH140T2HN18 1 Medium Sta c Pressure Duct
MIH90Q4HN18 1 Four-way Casse e
MIH71T2HN18 1 Medium Sta c Pressure Duct
MIH71F3HN18 1 Floor Standing (F3 series)
MIH56Q2HN18 1 Two-way Casse e
MIH56GHN18 1 Wall mounted
MIH36Q1HN18 1 One-way Casse e
MIH36Q4CHN18 1 Compact Four-way Casse e
FQZHN-01D 4 Branch joint
FQZHN-02D 2 Branch joint
FQZHN-03D 2 Branch joint
WDC3-86T 1 3rd genera on group controller
WDC3-86S 1 3rd genera on group controller
R410A 7.12 kg Extra Refrigerant Added
Φ1/4 19.06 m Copper pipe
Φ3/8 54.59 m Copper pipe
Φ1/2 19.06 m Copper pipe
Φ5/8 31.24 m Copper pipe
Φ3/4 12.61 m Copper pipe
Φ7/8 19.37 m Copper pipe
Φ1-1/8 1 m Copper pipe
Φ1-1/4 7.63 m Copper pipe

4.2 Indoor Unit Details (UC-01)


4.2.1 Indoor Unit Details Table
2
IDU Name Model Weight(kg) Dimension(WxHxD)(mm) Power supply MCA(A) MFA(A)
Academia/UE-04 MIH56Q2HN18 31.6 1259*299*591 220-240V-50/60Hz 0.9 15
Academia/UE-09 MIH56GHN18 11.5 950*295*265 220-240V-50/60Hz 0.51 15
Academia/UE-05 MIH200T1HN18 125 1388*580*1050 220-240V-50/60Hz 8.19 30
Academia/UE-08 MIH71T2HN18 25 910*245*770 220-240V-50/60Hz 1.5 15
Academia/UE-03 MIH36Q1HN18 11.8 1054*153*428 220-240V-50/60Hz 0.39 15
Academia/UE-06 MIH140T2HN18 39 1510*245*770 220-240V-50/60Hz 2.3 15
Academia/UE-02 MIH90Q4HN18 21.5 840*246*840 220-240V-50/60Hz 0.58 15
UE-01 MIH36Q4CHN18 14 575*235*638 220-240V-50/60Hz 0.54 15
Academia/UE-10 MIH71F3HN18 26.1 1253*566*200 220-240V-50/60Hz 0.4 15

IDU Name Model Tmp-C(℃)RTC(Btu/h)ATC(Btu/h)RSC(Btu/h)ASC(Btu/h)PI-C(W)Tmp-H(℃)RHC(Btu/h)AHC(Btu/h)PI-H(W)


Academia/ MIH56Q2HN18 24.0/16.0 14,236 12,893 69 21 20,724 69
UE-04
Academia/ MIH56GHN18 24.0/16.0 14,251 12,638 40 21 20,724 40
UE-09
Academia/ MIH200T1HN18 24.0/16.0 51,675 45,113 780 21 74,398 780
UE-05
Academia/ MIH71T2HN18 24.0/16.0 18,531 16,318 96 21 26,453 96
UE-08
Academia/ MIH36Q1HN18 24.0/16.0 9,449 8,337 30 21 13,090 30
UE-03
Academia/ MIH140T2HN18 24.0/16.0 36,715 31,708 172 21 52,906 172
UE-06
Academia/ MIH90Q4HN18 24.0/16.0 23,642 20,583 43 21 33,066 43
UE-02
UE-01 MIH36Q4CHN18 24.0/16.0 9,457 8,344 18 21 13,090 18
Academia/ MIH71F3HN18 24.0/16.0 18,501 16,292 53 21 26,453 53
UE-10

IDU Name Model Airflow(CFM) Sound-Pr dB(A) ESP(in.w.g.)


Academia/UE-04 MIH56Q2HN18 575.67[SSH] 39[SSH]
Academia/UE-09 MIH56GHN18 505.18[SSH] 41[SSH]
Academia/UE-05 MIH200T1HN18 2760.86[SSH] 51[SSH] 200(0-400)
Academia/UE-08 MIH71T2HN18 634.41[SSH] 35[SSH] 30(10-160)
Academia/UE-03 MIH36Q1HN18 270.21[SSH] 38[SSH]
Academia/UE-06 MIH140T2HN18 1236.51[SSH] 40[SSH] 50(10-160)
Academia/UE-02 MIH90Q4HN18 781.26[SSH] 38[SSH]
UE-01 MIH36Q4CHN18 311.33[SSH] 31[SSH] 0
Academia/UE-10 MIH71F3HN18 545.12[SSH] 40.5[SSH]

IDU Name Model Piping Length to 1st Y Joint(m)


Academia/UE-04 MIH56Q2HN18 35.17
Academia/UE-09 MIH56GHN18 34.57
Academia/UE-05 MIH200T1HN18 23.50
Academia/UE-08 MIH71T2HN18 16.80
Academia/UE-03 MIH36Q1HN18 14.00
Academia/UE-06 MIH140T2HN18 10.50
Academia/UE-02 MIH90Q4HN18 5.39
UE-01 MIH36Q4CHN18 10.01
Academia/UE-10 MIH71F3HN18 16.75

4.2.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Indoor temperature in cooling (Dry bulb temp. / Wet bulb temp. / RH)
RTC Required total cooling capacity
ATC Available total cooling capacity
RSC Required sensible cooling capacity
ASC Available sensible cooling capacity
Tmp-H Indoor temperature in hea ng (Dry bulb temp.)
RHC Required hea ng capacity
AHC Available hea ng capacity
Tdis-H Indoor unit discharge air temperature in hea ng
Airflow Indoor unit airflow (High/Medium/Low)
3
ESP External sta c pressure
Sound-Pr Sound pressure level (High/Medium/Low)
Sound-Po Sound power level (High/Medium/Low)
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
PI-C Power input in cooling
PI-H Power input in hea ng
Power supply Power supply
Dimension(WxHxD) Net Dimension (WxHxD) mm
Weight Weight

4.3 Outdoor Unit Details (UC-01)


4.3.1 Outdoor Unit Details Table
Model MV8-785WV2WN1(MA)
Module MV8-785WV2WN1(MA)
Tmp-C ℃ 33
RTC Btu/h
ATC Btu/h 198,593
PI-C kW 19.59
EER 2.97
Tmp-H ℃/℃ 21.5/18.6
RHC Btu/h
AHC Btu/h 280,904
PI-H kW 14.35
COP 5.74
CR 96.3
Airflow CFM 17035.08
Sound-Pr 64
Sound-Po
Bas-Refr kg 19.00
Ex-Refr(ODU) kg 0.00
Ex-Refr(Piping) kg 7.12
TCO2 eq. 54.53
MCA A 82.5
MFA A 100
Power supply V/ph/Hz 220V-3ph-60Hz
Dimension (WxHxD) mm 1880*1760*825
Weight kg 380

4.3.2 Table of Abbrevia ons


Abbrevia on code Descrip on
Tmp-C Outdoor condi ons in cooling (Dry bulb temp.)
RTC Required cooling capacity
ATC Available cooling capacity
PI-C Power input in cooling
EER EER
Tmp-H Indoor condi ons in hea ng (Dry bulb temp. / Wet bulb temp. / RH)
RHC Required hea ng capacity
AHC Available hea ng capacity
PI-H Power input in hea ng
COP COP
CR Combina on ra o
Airflow Outdoor unit airflow
Sound-Pr Sound pressure level
Sound-Po Sound power level
Bas-Refr Standard factory refrigerant charge
Ex-Refr(ODU) Extra refrigerant charge for outdoor unit
Ex-Refr(Piping) Extra refrigerant charge for liquid piping
TCO2 eq. Tonnes of CO2 equivalent
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
Power supply Power supply
Dimension (WxHxD) Net Dimension (WxHxD) mm
Weight Weight

4.4 Piping Limita ons (UC-01)


4
4.4.1 Piping Limita ons
Item Capability Actual Value
Total piping length 1100.00(m) 139.10(m)
Longest actual length 220.00(m) 37.80(m)
Longest equivalent length 260.00(m) 44.80(m)
Longest equivalent length a er first branch 120.00(m) 35.17(m)
Indoor unit to nearest branch length 40.00(m) 8.30(m)
Length difference between longest and shortest distance to indoor units 40.00(m) 29.78(m)
Height difference between indoor and outdoor unit(ODU up) 110.00(m) 0.00(m)
Height difference between indoor and outdoor unit(ODU down) 110.00(m) 0.00(m)
Height difference between indoor units 40.00(m) 0.00(m)
Combina on ra o 50-200% 96.31%
IDU quan ty 46 9

4.4.2 Correc on Factors


Item Correc on factor
Al tude (indoor unit) 0.999
Al tude (outdoor unit) 1.000
Piping (cooling) 1.000
Piping (hea ng) 1.000
Defrost (hea ng) 1.000

4.4.3 Piping Details Table


No. Length(m) Piping diameter
(1) 7.63 Φ1-1/4/Φ3/4
(2) 1.00 Φ1-1/8/Φ5/8
(3) 2.35 Φ3/4/Φ3/8
(4) 16.37 Φ7/8/Φ3/8
(5) 3.00 Φ7/8/Φ3/8
(6) 2.63 Φ3/4/Φ3/8
(7) 4.50 Φ5/8/Φ3/8
(8) 7.70 Φ1/2/Φ1/4
(9) 8.30 Φ1/2/Φ1/4
(10) 3.50 Φ5/8/Φ3/8
(11) 4.60 Φ5/8/Φ3/8
(12) 1.90 Φ1/2/Φ1/4
(13) 4.70 Φ5/8/Φ3/8
(14) 1.04 Φ5/8/Φ3/8
(15) 4.00 Φ5/8/Φ3/8
(16) 1.16 Φ1/2/Φ1/4
(17) 7.90 Φ5/8/Φ3/8

4.4.4 Branch Joints Details Table


No. Load(Btu/h) Model
(1) 257,958 FQZHN-03D
(2) 190,739 FQZHN-03D
(3) 106,459 FQZHN-02D
(4) 38,216 FQZHN-01D
(5) 84,280 FQZHN-02D
(6) 36,510 FQZHN-01D
(7) 67,219 FQZHN-01D
(8) 36,510 FQZHN-01D

4.4.5 Reducer Details Table

4.4.6 Bends Detailed Table


Quan ty Equivalent length(m)
34 17

4.5 Piping Diagrams (UC-01)

5
4.6 Wiring Diagrams (UC-01)

6
5. Centralized Control Solu on
5.1 Centralized Controller List
The centralized control system of this project is full output regardless of whether the system is selected.