Confidential Service Bulletin

Eaton/Cutler-Hammer “IT” T801


Solid State Starter Fan Kit Retrofit
On Trane CenTraVac™ Chillers
This confidential service bulletin provides special warranty policy and/or service expense
compensation information for use by Trane warranty representatives.
Important: When entering your claim, select the retrofit ID with your region’s suffix from the
dropdown list. Retrofit IDs include the two main areas of the literature order number followed by
the region suffix without dashes. For example, for confidential service bulletin CVRE-SVC01A-EN
in the North America region, select retrofit ID CVRESVC01NA.
Region suffixes: AS (Asia), EU (Europe), LA (Latin America), NA (North America), MAIR (Middle
East, Africa, India)

ATTENTION: Warnings and Cautions appear at appropriate sections throughout this literature.
Read these carefully.
WARNING – Indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION – Indicates a potentially hazardous situation which, if not avoided, could result in
minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE – Indicates a situation that could result in equipment or property-damage only
accidents.

Confidential and Proprietary


March 16, 2010 © 2010 Trane All rights reserved CTV-SVC51A-EN
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical
hazards.

• Before installing/servicing this unit, technicians MUST put on all Personal Protective
Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate
MSDS sheets and OSHA guidelines for proper PPE.
• When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS
sheets and OSHA guidelines for information on allowable personal exposure levels, proper
respiratory protection and handling recommendations.
• If there is a risk of arc or flash, technicians MUST put on all necessary Personal Protective
Equipment (PPE) in accordance with NFPA70E for arc/flash protection PRIOR to servicing the
unit.
Failure to follow recommendations could result in death or serious injury.

WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power
cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have
discharged. Failure to disconnect power and discharge capacitors before servicing could result in
death or serious injury.

Note: For additional information regarding the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR.

Introduction
Eaton/Cutler-Hammer has recommended adding fans to their “IT” Solid State Starter modules
provided with Trane CenTraVac chillers. Trane has obtained free IT starter cooling fan kits from
Eaton for a limited number of shipped units with T801 solid state starters.

Discussion
Eaton advises that in order to optimize the reliability of the starter, the IT Solid State Starter
modules on affected units should be upgraded with their EMM18 fan kit in order to lower the
temperature around the IT control board to less than 50 degrees Celsius.
Some starter failures and erroneous fault codes have been attributed to control board malfunction
as the result of exposure to ambient temperatures above its 50°C rating. The EMM18 fan moves
air directly across the control board of the IT starter and significantly lowers internal starter module
temperatures around the control board.
There are two styles of fan kit available for the IT solid state starter:
• Standard mounting—Cutler-Hammer fan EMM18 (this is also Trane part # KIT15539). This fan
fits all IT T801 starter modules of frame sizes “R” and “T”, and some modules of frame sizes “U”
and “V”.
• Special mounting—Cutler-Hammer front-faced mounting fan for ITs. This fan fits “U” and “V”
frame IT starter applications that have been found to have very limited space available for fan
installation.

2 Confidential and Proprietary CTV-SVC51A-EN


Refer to the list of affected units (see Table 1) to determine which type of fan is needed for a
particular chiller starter.
For units located in equipment rooms with non-air-conditioned spaces and where ambient
temperatures are very high (90°F [32.2°C] and above), it is recommended that enclosure fan kit (part
number KIT15538) also be installed. Offices must purchase this part on their own, but the labor to
install it is reimburseable on this retrofit if done at the same time as the EMM18 fan kit. Units still
under factory warranty may file a material claim for this part. Units with motor RLAs of 961 or higher
already have factory installed enclosure fans.

Units Affected
Only the units listed in Table 1 may have labor claimed against this bulletin. This bulletin does not
affect any solid state starters shipped after September 3, 2009.

Table 1. Affected units by servicing sales office

EMM18
Servicing Sales Unit Fan Kit
Office Order # Serial # JobName Location Type
Albuquerque L4E464A L07D02128 TAS00237 Isleta Albuquerque standard
Albuquerque L4E464B L07D02129 TAS00237 Isleta Albuquerque standard
Asheville L4H617B L08K04767 TAS0606033 Harrah's Cherokee Cherokee, NC 28719 standard
Atlanta, GA G1S632A L09C07026 Floyd Medical Center Alpharetta, GA standard
Atlanta, GA G1W754A L08M05505 Jimmy Carter Library Chiller Replacement Atlanta, GA standard
Atlanta, GA G1W754B L09A05823 Jimmy Carter Library Chiller Replacement Atlanta, GA standard
Baltimore, MD E1U826A L08M05568 Clifton T Perkins Hospital Center Baltimore, MD standard
Baton Rouge, LA K6A034A L08H03972 Healing Place Church New Sanctuary Baton Rouge, LA standard
Baton Rouge, LA K6A034B L08H03977 Healing Place Church New Sanctuary Baton Rouge, LA standard
Birmingham, AL G1G358A L08B00815 Wachovia Oxmoor Data Center Chillers Birmingham, AL standard
Birmingham, AL G1G358B L08B00822 Wachovia Oxmoor Data Center Chillers Birmingham, AL standard
Birmingham, AL G1G358C L08B00825 Wachovia Oxmoor Data Center Chillers Birmingham, AL standard
Birmingham, AL G1G358D L08B00830 Wachovia Oxmoor Data Center Chillers Birmingham, AL standard
Boise, ID U2H724A L08L05408 Campbell County Recreation Center - Gillette, WY Gilette, WY standard
Boston A1R209A L08A00458 Evergreen Solar Devens, MA special
Boston A1R209B L08A00459 Evergreen Solar Devens, MA special
Boston A1R209C L08A00464 Evergreen Solar Devens, MA special
Boston A1R325A L08C01322 Building B Kendall Square Avon, MA special
Boston A1R325C L08C01340 Building B Kendall Square Avon, MA special
Boston A1S189A L08F03012 Evergreen Solar Devens, MA standard
Boston A1S189B L08F03011 Evergreen Solar Devens, MA standard

CTV-SVC51A-EN Confidential and Proprietary 3


Table 1. Affected units by servicing sales office (continued)

EMM18
Servicing Sales Unit Fan Kit
Office Order # Serial # JobName Location Type
Central Ontario CHR287A L08D01723 University of Waterloo Chillers Humanities Plant Waterloo, ON special
Central Ontario CHR287B L08D01730 University of Waterloo Chillers Humanities Plant Waterloo, ON special
Central Ontario CHG095A L08M05451 First Canadian Place D Plant Renovation Phase 2 Guelph, ON standard
Central Ontario CHG095B L08M05441 First Canadian Place D Plant Renovation Phase 2 Guelph, ON standard
Central Ontario CHQ502A L09C06886 St Michaels Hospital Li Ka Shing Knowledge Inst. Hamilton, ON standard
Central Ontario CHQ502B L09C06900 St Michaels Hospital Li Ka Shing Knowledge Inst. Hamilton, ON standard
Central Ontario CHQ502C L09C06901 St Michaels Hospital Li Ka Shing Knowledge Inst. Hamilton, ON standard
Central Ontario CHR021A L08A00389 First Canadian Place D Plant Renovation Richmond Hill, ON standard
Central Ontario CHR021B L08B00602 First Canadian Place D Plant Renovation Richmond Hill, ON standard
Central Ontario CHR022A L08A00440 University of Waterloo School of Optometry Chiller Hamilton, ON standard
Central Ontario CHR117A L08B00871 Maple Leaf 2 Mississauga, ON standard
Central Ontario CHT361A L09G00734 Concord Place Block 26W Bldg U and V Richmond Hill, ON standard
Central Ontario CHT436B L09B06630 University of Waterloo Engineering 5 Chillers Waterloo, ON standard
Charleston, SC F1N451A L05H03744 Vought Aircraft and Global Aeronautica Order North Charleston, SC standard
Charleston, SC F1N451B L05H03745 Vought Aircraft and Global Aeronautica Order North Charleston, SC standard
Charleston, SC F1N451C L05H03746 Vought Aircraft and Global Aeronautica Order North Charleston, SC standard
Charleston, SC F1N459C L05L04867 Vought Aircraft and Global Aeronautica Order North Charleston, SC standard
Charleston, SC F1N459B L05L04869 Vought Aircraft and Global Aeronautica Order North Charleston, SC standard
Charleston, SC F1N459A L05L04871 Vought Aircraft and Global Aeronautica Order North Charleston, SC standard
Chattanooga, TN J2B140A L09G00721 Volkswagen Chiller Equipment Procurement Chattanooga, TN standard
Chicago, IL R1S665A L09B06632 Elmhurst Memorial Hospital - Chiller Pre-Purchase Elmhurst, IL special
Chicago, IL R1S665B L09C06680 Elmhurst Memorial Hospital - Chiller Pre-Purchase Elmhurst, IL special
Chicago, IL R1S665C L09B06649 Elmhurst Memorial Hospital - Chiller Pre-Purchase Elmhurst, IL special
Chicago, IL R1N693C L08E02516 Alexian Brothers Medical Center 112806 [Rev 09140] Franklin Park, IL standard
Chicago, IL R1S586A L08M05726 Batavia High School - 2008 Addition and Remodel Batavia, IL standard
Chicago, IL R1S586B L08M05727 Batavia High School - 2008 Addition and Remodel Batavia, IL standard
Chicago, IL R1T034A L08M05736 Panduit New World HQ Cchillers 091808 Tinley Park, IL standard
Chicago, IL R1T034B L08M05737 Panduit New World HQ Cchillers 091808 Tinley Park, IL standard
Chicago, IL T1G039A L09G00745 Central Dupage Hospital - Bed Tower Winfield, IL standard
Cleveland, OH N3K499A L08H03981 EBD08: Verizon Chiller Garfield Heights, OH standard
Dallas L4F842A L07J04250 TAS 0706022 Winstar Thackerville, OK 73459 special
Dallas L4F842B L07J04257 TAS 0706022 Winstar Thackerville, OK 73459 special
Dallas L4F842C L07J04258 TAS 0706022 Winstar Thackerville, OK 73459 special
Detroit, MI M1D821A L08C01551 Getrag Chillers Tipton, IN special
Detroit, MI M1D821B L08C01550 Getrag Chillers Tipton, IN special
Detroit, MI M1D821C L08C01554 Getrag Chillers Tipton, IN special
Detroit, MI M1E534A L08D01967 WBH Troy Shipping Receiving & Powerhouse Chiller Troy, MI special
Detroit, MI M1D765A L08A00438 UM Kellogg Eye Center Chillers Ann Arbor, MI standard
Detroit, MI M1D765B L08A00439 UM Kellogg Eye Center Chillers Ann Arbor, MI standard
Detroit, MI M1D765C L08A00471 UM Kellogg Eye Center Chillers Ann Arbor, MI standard
Detroit, MI M1E733A L08G03385 SBC ATT Bell Building Chiller Retrofit Oak Park, MI standard
Detroit, MI M1E733B L08G03386 SBC ATT Bell Building Chiller Retrofit Oak Park, MI standard

4 Confidential and Proprietary CTV-SVC51A-EN


Table 1. Affected units by servicing sales office (continued)

EMM18
Servicing Sales Unit Fan Kit
Office Order # Serial # JobName Location Type
Greenville, SC F5U485A L07G03393 Oconee Hospital Patient Tower Spartanburg, SC standard
Greenville, SC F5U485B L07F03193 Oconee Hospital Patient Tower Spartanburg, SC standard
Greenville, SC F5W782A L09D07100 Simon Haywood Mall Greenville SC Greenville, SC standard
Harrisburg, PA D1A193A L09A05822 Brethren Village Lancaster Renovations Ephrata, PA standard
Harrisburg, PA D1A193B L08M05732 Brethren Village Lancaster Renovations Ephrata, PA standard
Honolulu, HI W1P173A L08C01310 Lihue Airport AC Replacement Long Beach, CA standard
Honolulu, HI W1P173B L08C01347 Lihue Airport AC Replacement Long Beach, CA standard
Houston L4G310A L07L05369 TAS - 0707018 Veritas Houston, TX special
Houston L4G310B L07M05495 TAS - 0707018 Veritas Houston, TX special
Houston L4G346A L07M05500 TAS00265 Kreido TAS Shop standard
Houston L4G346B L07M05504 TAS00265 Kreido TAS Shop standard
Houston, TX L4G620A L08C01557 UTB TSC Thermal Plant Brownsville, TX standard
Houston, TX L4H646A L08J04373 9850 Gaylord Central Plant Houston, TX standard
Houston, TX L4H646B L08J04378 9850 Gaylord Central Plant Houston, TX standard
Houston, TX L4J445A L09A05990 St. Lukes Clear Lake Hospital Houston, TX standard
Houston, TX L4J445B L09A06009 St. Lukes Clear Lake Hospital Houston, TX standard
Houston, TX L4J445C L09A06118 St. Lukes Clear Lake Hospital Houston, TX standard
Indianapolis, IN P1Q782A L02A01062 Indiana University Biotechnology Reseearch Indianapolis, IN special
Indianapolis, IN P1Q782B L02A01064 Indiana University Biotechnology Reseearch Indianapolis, IN special
Indianapolis, IN P1Q828A L02A01175 Indiana Heart Hospital Castleton, IN special
Indianapolis, IN P1Q828B L02A01177 Indiana Heart Hospital Castleton, IN special
Indianapolis, IN Q2M011A L07M05687 Saint Francis Hospital Indianapolis Chiller Indianapolis, IN special
Indianapolis, IN Q2M011A L07M05687 Saint Francis Hospital Indianapolis Chiller Indianapolis, IN special
Indianapolis, IN P1G534A L07F03138 Indiana University Forest Quad Chillers Bloomington, IN standard
Indianapolis, IN P1G534B L07F03139 Indiana University Forest Quad Chillers Bloomington, IN standard
Jackson, MS K1T563A L08J04316 River Oaks Hospital Patient Bed and E.D. Addition Flowood, MS standard
Jackson, MS K1T563B L08J04327 River Oaks Hospital Patient Bed and E.D. Addition Flowood, MS standard
Kansas City L4E472A L07C01468 TAS0607018 MPG Atchison, KS 66002 standard
Kansas City, KS Q2L980A L08A00066 Liberty Hospital South Tower Expansion Kansas City, MO special
Kansas City, KS Q2N210A L08M05502 KCKCC Chillers Kansas City, KS standard
Kansas City, KS Q2N210B L08M05530 KCKCC Chillers Kansas City, KS standard
Las Vegas, NV W4P075A L08D01936 Hard Rock - Central Plant Expansion Las Vegas, NV special
Las Vegas, NV W4P075B L08D01943 Hard Rock - Central Plant Expansion Las Vegas, NV special
Las Vegas, NV W4P075C L08D01957 Hard Rock - Central Plant Expansion Las Vegas, NV special
Las Vegas, NV W4P075D L08E02085 Hard Rock - Central Plant Expansion Las Vegas, NV special
Las Vegas, NV W4P517A L09A06115 Nevada Cancer Institute Research Lab Las Vegas, NV standard
Las Vegas, NV W4P517B L09A06134 Nevada Cancer Institute Research Lab Las Vegas, NV standard
Los Angeles, CA W2Z358A L08F02820 Ritz Rancho Mirage AHU’s Bloomington, CA standard
Macon, GA G3E487A L08G03156 Macon State - Replace York Chiller Macon, GA standard
Memphis, TN K2A861A L09A06125 University of MS - Residential College Phase 2 University, MS standard

CTV-SVC51A-EN Confidential and Proprietary 5


Table 1. Affected units by servicing sales office (continued)

EMM18
Servicing Sales Unit Fan Kit
Office Order # Serial # JobName Location Type
Miami, FL H8A704A L04L05025 Charlotte Arena Charlotte, NC special
Miami, FL H8A704B L04L05027 Charlotte Arena Charlotte, NC special
Miami, FL H8A704C L04L05030 Charlotte Arena Charlotte, NC special
Miami, FL H3K392A L08H03732 Northrop Grumman 1st Floor Laser Lab Apopka, FL standard
Miami, FL H4H700A L08M05511 FIU Engineering Bldg Chiller Replacement Miami, FL standard
Miami, FL H4H700B L08M05548 FIU Engineering Bldg Chiller Replacement Miami, FL standard
Miami, FL H4K373A L08M05446 UM - Richter Library Chiller Replacement Coral Gables, FL standard
Miami, FL H4K614A L09B06643 State School LLL Carol City Sr High Replacement Carol City, FL standard
Miami, FL H4K614B L09B06644 State School LLL Carol City Sr High Replacement Carol City, FL standard
Milwaukee, WI T5G392A L08B01072 Aurora Medical Center Summit Central Utility Plant Oconomowoc, WI special
Milwaukee, WI T5G392B L08B01096 Aurora Medical Center Summit Central Utility Plant Oconomowoc, WI special
Milwaukee, WI T5G392C L08C01207 Aurora Medical Center Summit Central Utility Plant Oconomowoc, WI special
Milwaukee, WI T5J268A L09E07906 Aurora Medical Center Grafton Grafton, WI standard
Milwaukee, WI T5J268B L09E07919 Aurora Medical Center Grafton Grafton, WI standard
Mobile, AL J5S867A L08A00465 Thomas Hospital Patient Tower Addition Fairhope, AL special
Mobile, AL J5T808A L08K04786 NGSS Gulfport Assembly and Erection Bldg Gulfport, MS standard
Mobile, AL J5T884A L09A05905 Nas Pensacola Bldg 633 Chiller #1 Replacement Pensacola, FL standard
Montreal CFA312A L08K04721 Place du Canada PMA Montreal, QC standard
Montreal CFA312B L08K04725 Place du Canada PMA Montreal, QC standard
Montreal CFA552A L09D07083 ADM Nouv Refroidisseur Dorval, QC standard
New Orleans, LA K4S321A L08F03009 UNO North Chiller Plant New Orleans, LA standard
New Orleans, LA K4S321B L08F03020 UNO North Chiller Plant New Orleans, LA standard
New Orleans, LA K4T478A L09E07837 TGMC Atrium New Chiller Harahan, LA standard
New Orleans, LA K4T499A L09E07836 TGMC Atrium New Chiller Harahan, LA standard
New York B3Q144A L07M05521 Goldman Sachs World Headquarters Maspeth, NY special
New York B3Q144B L07M05522 Goldman Sachs World Headquarters Maspeth, NY special
New York B3Q144C L07M05528 Goldman Sachs World Headquarters Maspeth, NY special
New York B3Q144D L07M05529 Goldman Sachs World Headquarters Maspeth, NY special
New York B3Q144E L07M05591 Goldman Sachs World Headquarters Maspeth, NY special
Norfolk, VA E5C957A L08A00454 Central Heating / Cooling Plant - William & Mary Williamsburg, VA special
North Jersey B6M612A L08G03305 Meadowlands Stadium Mahwah, NJ standard
North Jersey B6M612B L08G03315 Meadowlands Stadium Mahwah, NJ standard
North Jersey B6M612C L08G03319 Meadowlands Stadium Mahwah, NJ standard
North Jersey B6M612D L08G03320 Meadowlands Stadium Mahwah, NJ standard
Oklahoma City, OK L1K061A L08K04730 Integris Cancer Center Oklahoma City, OK standard
Oklahoma City, OK L1K061B L08K04736 Integris Cancer Center Oklahoma City, OK standard
Omaha H2L043A L09H00879 Yahoo Replacement Chillers La Vista, NE standard
Omaha H2L043B L09H00880 Yahoo Replacement Chillers La Vista, NE standard
Omaha H2L043C L09H00881 Yahoo Replacement Chillers La Vista, NE standard
Omaha H2L043D L09H00882 Yahoo Replacement Chillers La Vista, NE standard
Omaha H2L043E L09H01059 Yahoo Replacement Chillers La Vista, NE standard
Omaha H2L043F L09H01065 Yahoo Replacement Chillers La Vista, NE standard

6 Confidential and Proprietary CTV-SVC51A-EN


Table 1. Affected units by servicing sales office (continued)

EMM18
Servicing Sales Unit Fan Kit
Office Order # Serial # JobName Location Type
Orlando, FL H3G895A L08B00855 OUC Lake Nona Central Energy Plant Orlando, FL special
Orlando, FL H3G895B L08B00862 OUC Lake Nona Central Energy Plant Orlando, FL special
Orlando, FL H3G895C L08B00884 OUC Lake Nona Central Energy Plant Orlando, FL special
Orlando, FL H3G895D L08B01070 OUC Lake Nona Central Energy Plant Orlando, FL special
Orlando, FL H3G676A L08A00028 Cypress Creek / Oakridge Relief HS New Const Orlando, FL standard
Orlando, FL H3G676B L08A00030 Cypress Creek / Oakridge Relief HS New Const Orlando, FL standard
Orlando, FL H3G866A L08A00466 Timber Creek Relief High School New Const Orlando, FL standard
Ottawa CGB525A L08M05546 KGH - Redevelopment Project Kingston, ON standard
Phoeniz, AZ V3K690A L08E02389 Dysart High School #4 Waddell, AZ standard
Phoeniz, AZ V3K690B L08E02456 Dysart High School #4 Waddell, AZ standard
Phoeniz, AZ V3K690C L08E02457 Dysart High School #4 Waddell, AZ standard
Phoeniz, AZ V3N864A L08E02256 Cancer Trmnt Ctr - CVHE Chillers Goodyear, AZ standard
Phoeniz, AZ V3N864B L08E02257 Cancer Trmnt Ctr - CVHE Chillers Goodyear, AZ standard
Providence A5L994A L09B06300 CVS Woonsocket Power Project Cranston, RI standard
Raleigh, NC F4M813D L07M05678 NET APP - Bldg. 4 RTP, NC special
Raleigh, NC F4M813D L07M05678 NET APP - Bldg. 4 RTP, NC special
Raleigh, NC F4P115A L08D01931 NC Museum of Art Morrisville, NC standard
Raleigh, NC F4P115B L08D01932 NC Museum of Art Morrisville, NC standard
Raleigh, NC F4Q600A L09E07770 Novo Nordisk 080 Short Chiller Clayton, NC standard
Raleigh, NC F4Q600B L09E07771 Novo Nordisk 080 Short Chiller Clayton, NC standard
Rochester, NY C4A103B L08F02675 RIT Central Plant Webster, NY special
Rochester, NY C4A103C L08F02683 RIT Central Plant Webster, NY special
Rochester, NY C4D122A RH L09E07910 RIT Westside Cooling Winter Chiller Project Rochester, NY special
Rochester, NY C4A103A L08G03349 RIT Central Plant Webster, NY standard
Rochester, NY C4A103A L08G03349 RIT Central Plant Webster, NY standard
Rochester, NY C4A103B L08F02675 RIT Central Plant Webster, NY standard
Rochester, NY C4A103C L08F02683 RIT Central Plant Webster, NY standard
Rochester, NY C4V721A L08D01918 SUNY Geneseo - Greene Hall Webster, NY standard
Spokane L4E392A L07B01303 TAS0606001 YDC1 Quincy, WA 98848 standard
Spokane L4E392B L07B01304 TAS0606001 YDC1 Quincy, WA 98848 standard
Spokane L4E392C L07C01314 TAS0606001 YDC1 Quincy, WA 98848 standard
Spokane L4E392D L07C01315 TAS0606001 YDC1 Quincy, WA 98848 standard
Spokane L4F471A L07H04110 TAS0704036 YDC2 Quincy, WA 98848 standard
Spokane L4F471B L07H04113 TAS0704036 YDC2 Quincy, WA 98848 standard
Spokane L4F471C L07H04114 TAS0704036 YDC2 Quincy, WA 98848 standard
Spokane L4F471D L07H04120 TAS0704036 YDC2 Quincy, WA 98848 standard
Spokane L4G565A L08A00331 TAS - 0709004 YDC3 Quincy, WA 98848 standard
Spokane L4G565B L08A00335 TAS - 0709004 YDC3 Quincy, WA 98848 standard
Spokane L4G565C L08A00336 TAS - 0709004 YDC3 Quincy, WA 98848 standard
Spokane L4G565D L08A00366 TAS - 0709004 YDC3 Quincy, WA 98848 standard

CTV-SVC51A-EN Confidential and Proprietary 7


Table 1. Affected units by servicing sales office (continued)

EMM18
Servicing Sales Unit Fan Kit
Office Order # Serial # JobName Location Type
Springdale, AR G5F820A L08A00374 Baxter Healthcare - Chiller Plant Revisions Moutain Home, AR special
Springdale, AR G5C327A L02K19806 U OF A - Southwest Chiller Plant Fayetteville, AR standard
Springdale, AR G5C327B L02K19812 U OF A - Southwest Chiller Plant Fayetteville, AR standard
Springdale, AR G5C327C L02K19789 U OF A - Southwest Chiller Plant Fayetteville, AR standard
Springfield, MO Q8P047A L09B06287 Cox-Walnut Lawn Chiller Plant Upgrade Springfield, MO standard
Springfield, MO Q8P047B L09B06288 Cox-Walnut Lawn Chiller Plant Upgrade Springfield, MO standard
St. Louis, MO Q3R504B L08L05231 Biomedical Research Building One St. Louis, MO special
St. Louis, MO Q3R504B L08L05231 Biomedical Research Building One St. Louis, MO special
St. Louis, MO Q3R504D L08L05240 Biomedical Research Building One St. Louis, MO standard
Tampa, FL H5D880A L08A00031 SPC - Clearwater Campus Chillers Clearwater, FL standard
Tampa, FL H5G297A L08K04752 Derby Lane New Poker Room Saint Petersburg, FL standard
Tulsa L4G622A L08B00622 TAS0708030 Cherokee Catoosa, OK 74015 special
Tulsa L4G622B L08B00680 TAS0708030 Cherokee Catoosa, OK 74015 special
Tulsa L4G622C L08B00681 TAS0708030 Cherokee Catoosa, OK 74015 special
Tulsa L4G623A L08B00689 TAS0701022 Cherokee Catoosa, OK 74015 special
Tulsa L4G623C L08B00690 TAS0701022 Cherokee Catoosa, OK 74015 special
Tulsa K2A918A L09C06905 Choctaw Chillers Durant, OK standard
Tulsa K2A918B L09C06909 Choctaw Chillers Durant, OK standard
Tulsa K2A918C L09C06908 Choctaw Chillers Durant, OK standard
Tulsa K2A918D L09C06916 Choctaw Chillers Durant, OK standard
Twin Cities, MN S3E168A L08F03007 CHS Oilseed Processing Plant New Chiller Mankato, MN standard
Washington, DC E2P487E L07A00138 ACC-4 Data Center, DuPont Fabros - RD/2855 Capitol Heights, MD special
Washington, DC E2E252A L08G03374 Northern VA Forensics Lab Upper Marlboro, MD standard
Washington, DC E2E252B L08G03375 Northern VA Forensics Lab Upper Marlboro, MD standard
Washington, DC E2U435A L07E02290 Embassy of the People’s Republic of China Washington, DC standard
Washington, DC E2U435B L07E02291 Embassy of the People’s Republic of China Washington, DC standard
Wilmington, NC F9F143A L08L05229 Carteret General Hospital - Chiller Replacement Morehead City, NC standard

8 Confidential and Proprietary CTV-SVC51A-EN


Repair Authorization
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power
cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have
discharged. Failure to disconnect power and discharge capacitors before servicing could result in
death or serious injury.

Note: For additional information regarding the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR.

At the earliest opportunity, order and install fan kits into the starters of affected units. Refer to
Table 2 to determine quantities needed.
1. Fill out the “IT Fan Request Form,” p. 12. The form must be completed fully and accurately in
order for fans to be sent.
2. Fax the completed form to Betty Maier of La Crosse Technical Service at 608-787-3024 or scan
the completed form and submit it by e-mail to bmaier@trane.com.
Note: Only those units shown on the list of affected units are eligible to receive fans via this
bulletin.
3. Install the EMM18 fan onto the IT starter using the literature that ships with the fan kit.
Notes:
• Installation instructions are included with the fan kits. The 24 V IT fans are wired to the control
terminal block of the IT. Regardless of fan type, the 24 V IT fan should be wired with its red wire
to the “1” terminal and its black wire to the “-” terminal.
• In some installations, the starter may have inadequate clearance alongside it to allow for the
installation of the fan (see Figure 1, right photo). For these cases, a special fan kit will be needed.
Eaton has developed a modified fan kit that allows for alternate mounting. The retrofit list will
identify starters in your territory that need these special kits.

Table 2. Count of unit serial numbers by EMM18 fan kit type


EMM18 Fan Kit Type
Servicing Sales Office special standard Total
Albuquerque 2 2
Asheville 1 1
Atlanta, GA 3 3
Baltimore, MD 1 1
Baton Rouge, LA 2 2
Birmingham, AL 4 4
Boise, ID 1 1
Boston 5 2 7
Central Ontario 2 11 13
Chattanooga, TN 1 1
Chicago, IL 3 6 9
Cleveland, OH 1 1
Dallas 3 3
Detroit, MI 4 5 9
Greenville, SC 3 3

CTV-SVC51A-EN Confidential and Proprietary 9


Table 2. Count of unit serial numbers by EMM18 fan kit type (continued)

EMM18 Fan Kit Type


Servicing Sales Office special standard Total
Harrisburg, PA 2 2
Honolulu, HI 2 2
Houston 2 2 4
Houston, TX 6 6
Indianapolis, IN 6 2 8
Jackson, MS 2 2
Kansas City 1 1
Kansas City, KS 1 2 3
Las Vegas, NV 4 2 6
Los Angeles, CA 1 1
Macon, GA 1 1
Memphis, TN 1 1
Miami, FL 3 6 9
Milwaukee, WI 3 2 5
Mobile, AL 1 2 3
Montreal 3 3
New Orleans, LA 4 4
New York 5 5
Norfolk, VA 1 1
North Jersey 4 4
Oklahoma City, OK 2 2
Omaha 6 6
Orlando, FL 4 3 7
Ottawa 1 1
Phoeniz, AZ 5 5
Providence 1 1
Raleigh, NC 2 4 6
Rochester, NY 3 5 8
Spokane 12 12
Springdale, AR 1 3 4
Springfield, MO 2 2
St. Louis, MO 2 1 3
Tampa, FL 2 2
Tulsa 5 4 9
Twin Cities, MN 1 1
WashingtonD.C. 1 4 5
Wilmington, NC 1 1

Total 61 145 206

10 Confidential and Proprietary CTV-SVC51A-EN


Figure 1. Fan mounting: standard (left) vs. special (right)

Labor and Travel Authorization


This bulletin authorizes the following labor to be claimed against it:
• 2.5 hours travel per jobsite.
• One hour labor per unit.
Note: Only the units listed in Table 1 may have labor claimed against this bulletin. This bulletin
does not affect any solid state starters shipped after September 3, 2009.

Expiration Date
This bulletin expires September 30, 2010.

Questions
Contact the CenTraVac™ Support Team with questions regarding this confidential service bulletin.
To contact them, send a message to techservice@trane.com or call 877-788-7263 (US & Canada)
or 651-407-4393 (International) and select menu options 4-2-2.

CTV-SVC51A-EN Confidential and Proprietary 11


IT Fan Request Form

# of standard kits needed: _______ # of special kits needed: _______

Please ship the fans to:


Trane Office: ___________________________________________
Street Address: ___________________________________________
___________________________________________
City: ___________________________________________
State: _______ Zip: _______
Attn: ___________________________________________
Phone: _______-_______-___________

Fax or e-mail this completed form to Betty Maier at:


Fax: 608-787-3024
e-mail: bmaier@trane.com

Literature Order Number CTV-SVC51A-EN


Date March 2010
Supersedes New

www.trane.com
Trane has a policy of continuous product and product data improvement and reserves the right to
For more information, contact your local Trane change design and specifications without notice. Only qualified technicians should perform the
office or e-mail us at comfort@trane.com installation and servicing of equipment referred to in this bulletin.