Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

CIRED 20th International Conference on Electricity Distribution Prague, 8-11 June 2009

Paper 0660

SELECTIVE ARC-FLASH PROTECTION

Lauri KUMPULAINEN Samuel DAHL


Vamp Ltd – Finland Vamp Ltd – Finland
lauri.kumpulainen@vamp.fi samuel.dahl@vamp.fi

costs because of the damaged equipment but often very high


ABSTRACT economic losses due to interrupted industrial processes.

Arc-flash faults in MV and LV switchgear are severe


incidents causing safety hazard to personnel and damage to OVERVIEW OF ARC-FLASH PREVENTION
equipment. Substantial additional costs are often inevitable AND MITIGATION METHODS
due to interruption of the distribution process. For these
reasons, effective methods to reduce the impact of arc-flash The IEC switchgear standard 62271-200 [5] underlines the
incidents are needed. This paper shortly evaluates different prevention of internal arc fault, but recognises several other
arc-flash mitigation methods and motivates the use of measures. These methods are shortly evaluated below.
technology based on detection of light. The benefits of this
Arc-flash prevention
technology are discussed, and practical application
alternatives and examples are given. Prevention of arc-flash incidents should always be
emphasized. By careful design and maintenance of
equipment, and adequate training of personnel the risk can
INTRODUCTION be mitigated. There are also on-line monitoring
technologies, based on e.g. partial discharge or infrared
Arcing fault is a short circuit via ionized gas (air) between radiation detection or thermal monitoring. These methods
one live part and ground or between live parts. High power can be effective against faults caused by other factors than
arc-flash faults can be characterized as electrical explosions. direct human error.
They release large amounts of energy in the form of radiant
heat, intense light, and high pressure waves. The Arc-flash protection methods
temperature of the plasma can reach 20.000 K. The increase The impact of an arc-flash incident depends on the energy
of the temperature expands the volume of the air causing a of the incident. The energy depends on voltage, current, and
pressure wave. Because of the high temperature, circuit arcing time, and of course on the distance to arc. System
components can change physical state from solid to vapor. voltage is normally not one of the issues that can be
E.g. copper expands by a factor of 67.000 in vaporizing, changed. Thus the practical protection principles are
which significantly increases the pressure. In addition to increasing the distance to arc or providing a mechanical
danger caused by radiation, heat and pressure wave, there barrier between the operator and the arc, and reducing the
may be shrapnel and toxic gases, causing additional arcing time or current.
personnel hazard. [1], [2]
Passive protection
Most arc-flash faults start as single-phase to ground faults Personal protective equipment, withdrawable devices, and
and develop into three-phase faults. This emphasizes the arc-resistant switchgear with pressure relief devices are
importance of early detection of the arc in order to rapidly passive means to mitigate hazard to personnel. From safety
clear the fault. point of view, arc-resistant switchgear provides protection
to personnel as long as the doors are closed. However, open
Arc current is not the same as the bolted fault current, doors are very common in practice, and in injury scenarios
because of the arc resistance. Because electric arc is more or [6].
less unpredictable, exact values for arc resistance or current
cannot be given. Calculation formulas in standards are Limiting the fault current
based on extensive experimental data. Arcing current is Fault current can be limited by choosing transformers with
always lower that the bolted fault current [3], [4]. Especially higher impedance or by using current-limiting reactors, but
in low voltage, the arcing current can be less than half the this increases cost and system losses. A more widely used
value of the bolted fault current. It is important to note that method is current-limiting fuses which provide not only
low fault current may lead to longer fault clearing time and current limitation but rapid fault-clearance as well. The
thus higher risk and damage. serious drawback of current-limiting fuses is that they
operate rapidly when the current is high, but when current-
Hazard to personnel, in practice arc burns, is not the only limiting fuses do not operate in their current limiting range,
reason to apply arc-flash protection. The economic clearing times can be significantly longer [1]. Especially in
consequences can be substantial, including not only the

CIRED2009 Session 1 Paper No 0660


CIRED 20th International Conference on Electricity Distribution Prague, 8-11 June 2009

Paper 0660

low voltage, the arc-fault current is often less than 50% of The importance of the fault-clearance time is better
the bolted fault current. visualized in Figure 2, presenting results of 50kA arcing
fault tests without and with optical sensing based protection.
Rapid fault-clearing times In the first case, the copper has totally vaporized.
Time is the critical factor in limiting arc incident energy.
Bus differential protection provides rather fast fault-clearing
time, but it is often complicated and costly. Zone-selective
interlocking is a more cost-effective method, but not as fast
as bus differential. Neither of these methods provides
selective protection against faults in cable compartment.

The fault arc can be detected by pressure sensors. At least Figure 2. Arc test results (50kA) with conventional
with high power arc the pressure rises fast. Reference [7] overcurrent protection (500ms) and with photosensor based
reports that pressure sensors have been removed, and the protection (47ms).
arc detection is based on photosensors alone.
IMPLEMENTATION OF ARC-FLASH
The fastest way to detect the arc is based on the detection of PROTECTION BASED ON DETECTION OF
light. According to [8], the evolution of the arc can be
directly traced by observing the luminous intensity. The
LIGHT
recent laboratory tests have verified that even a low power
arc can be detected by light sensitive sensors. The trip of the Dedicated arc protection relays
circuit breaker can then be initialized within a few Arc-flash protection is usually implemented by separate
milliseconds. In addition to light condition, in most system using arc flash detectors connected to dedicated arc
applications overcurrent is also required in order to protection relays. Overcurrent, earth fault etc. protection is
eliminate nuisance tripping caused by external light sources. carried out by other relays. A comprehensive, selective arc
flash protection system comprises of arc flash sensors, light
When using optical sensing, the longest delay in arc and current slave units collecting data from light sensors
protection comes from the operation time of the circuit and current transformers, and a master unit or several units
breaker. Maximum protection that can eliminate even the for final collection of all the data, and tripping the correct
pressure wave can be reached by arc eliminators. Instead on breaker, if both light and overcurrent are detected.
breaking the fault current these devices provide an
intentional bolted fault, extinguishing the arc within a few Arc flash sensors (Figure 3) can be point sensors or fiber
milliseconds. optic sensors. Selection of sensor type depends on the
application. According to practical experience, fiber optic
The impact of fault-clearing time is illustrated in Figure 1, loops are cost effective to apply in low voltage switchgear
comparing the incident energy levels (calculated according or motor control centres with multiple compartments.
to IEEE Std 1584™-2002 [9]) of different protection
approaches.

Comparison of incident energy


Breaker time 50ms
35,00

30,00

25,00
Figure 3. Point sensor and fiber optic loop sensor.
Energy / cal/cm^2

20,00

Advantages of point sensors are easy new and retrofit


15,00
installation and provision of exact fault location indication
10,00 as sensors are installed in each protected compartment. The
safety of the maintenance personnel can be enhanced even
5,00
further by personal point sensor, connected to clothes.
0,00 Regardless of the sensor type, it is essential that the whole
Conventional Zone selective Light & current Light & current
overcurrent interlocking based detection detection and
arc-flash protection system has continuous self-supervision
protection (100ms+50ms) (7ms+50ms) arc eliminator including the sensors and cables.
(400ms+50ms) (2ms)

Figure 1. Comparison of arc-flash incident energy levels of In multi-zone arrangements, master units must be able to
different protection methods. interchange data. Information on activated sensor can be

CIRED2009 Session 1 Paper No 0660


CIRED 20th International Conference on Electricity Distribution Prague, 8-11 June 2009

Paper 0660

distributed to all master units, so that all master units which


detect overcurrent can open the circuit breakers in their
zones. Similarly, information on locally detected
overcurrent can be passed to other units as a trip condition,
if one unit detects light but no overcurrent. Figure 4
presents an example of selective multiple zone protection.
With this arrangement, only the appropriate circuit breakers
operate. E.g. in a typical fault in the cable compartment of
outgoing feeders, only the faulty feeder is tripped.

Figure 5. An example of selective protection using


common numerical relays equipped with arc-flash
protection option.
Stand-alone arc protection units
A very cost effective solution for e.g. in wind power plants
and secondary substations are stand-alone arc protection
units. Figures 6 and 7 present examples of point sensor based
arc flash protection in a wind power plant.

Figure 4. An example of selective arc-flash protection


scheme with dedicated arc-flash protection system.

Numerical relays equipped with arc-flash protection


option
Numerical protection relays can be equipped with arc-flash
protection option. In practice this means sensor inputs to
which the arc flash sensors can directly be connected. This
way the total cost of the protection concept is minimal. The
arc sensor input may include e.g. two inputs for arc sensors,
one binary input and one output for receiving/sending arc
sensor data to other relays. The relays include high-speed Figure 6. Protection zones of a wind power plant equipped
overcurrent and earth fault stages dedicated to operation with point sensors.
with the arc flash sensors.

The selectivity of arc flash protection can be increased by


connecting arc flash sensors of the outgoing feeder to the
overcurrent relay of the feeder. If an arc fault occurs in the
feeder area, only the feeder breaker will open, leaving the
rest of the substation operational. This is very beneficial,
because many arc faults occur in cable compartments.
Figure 5 presents an example of arc flash protection carried
out carried out by common numerical relays with arc flash
protection option.

In figure 5 it should be noted that selective protection and


indication of fault location is easily achieved by installing
light sensors in busbar compartment, circuit breaker
compartments, and in feeder compartments.
Figure 7. Selective arc flash protection of the tower cable and
the MV switchgear of a wind power plant.

CIRED2009 Session 1 Paper No 0660


CIRED 20th International Conference on Electricity Distribution Prague, 8-11 June 2009

Paper 0660

Figure 8 presents the arc-flash protection scheme of a 4 Asset protection along with safety aspects should be taken
generator power plant. Each generation unit is equipped with into account as in any system design. Combination of
its own stand-alone arc protection unit. General trip follows if sensing of light and overcurrent has proved to be a very
the fault is in the busbar compartment or in a circuit breaker efficient method. This method can be applied by dedicated
compartment, while a selective trip is initialized if the fault is arc flash protection system or by using common numerical
in a cable compartment. protection relays equipped with arc protection option. For
the most demanding cases, ultra fast arc eliminating
technology is available.

REFERENCES

[1] T. Dugan, 2007, “Reducing the arc flash hazard”,


IEEE Industry Applications Magazine, p. 51-58,
May/June 2007.

[2] R.H. Lee, 1987, “Pressures developed by arcs”, IEEE


Figure 8. Selective arc-flash protection of a power plant. Transactions on Industry Applications, Vol. IA-23, p.
760-763, July 1987.
ARC ELIMINATORS
With light and current based arc flash protection the arcing [3] M. Murphy, 2008, “How to form a bounding arc flash
time consists of the operation time of the protection relay study for your site”, Proceedings IEEE IAS Electrical
(2-15ms) and the operation time of the circuit breaker Safety Workshop, Dallas, Texas, March 18-21, 2008.
(typically 50-80ms). In some cases even shorter arcing time
is needed, often in order to limit the rise of the pressure. For [4] D.M. Doan, 2008, “Designing a site electrical system
these purposes, arc quenching devices can be applied. When with arc flash energy under 20 cal/cm2”, Proceedings
the arc is detected by the arc protection relay, the relay trips IEEE IAS Electrical Safety Workshop, Dallas, Texas,
the quenching device within 2-5ms and sends the tripping March 18-21, 2008.
signal to the circuit breaker. The quenching device makes
the short circuit at ultra high speed, and the arc is quenched. [5] IEC, 2003, “IEC International Standard 62271-200,
The bolted short circuit current flows through the quenching High-voltage switchgear and controlgear - Part 200:
device until the circuit breaker opens. AC metal-enclosed switchgear and controlgear for
rated voltages above 1 kV and up to and including 52
kV”

[6] R.A. Jones, D.P. Liggett, M. Capelli-Schellpfeffer, T.


Macalady, L.F. Saunders, R.E., Downey, B. McClung,
A., Smith, S., Jamil, V. Saporita, 2000, “Staged tests
Figure 9. Arc eliminator. increase awareness of arc-flash hazards in electrical
equipment”, IEEE Transactions on Industry
Combination of arc quenching device with current limiting Application, Vol. 36, No 2, March/April 2000.
fuses is a potential solution to overcome the limitations of
current limiting fuses. The quenching device makes a bolted [7] H.B. Land, C.L Eddins, J.M. Klimek, 2004,
fault which lead to high current and rapid operation of the “Evolution of Arc Fault Protection Technology at
fuse. This mitigates the stress to the equipment. APL”, Johns Hopkins APL Technical Digest, Volume
25, Number 2, 2004.
For low voltage systems the quenching device makes the
busbar potential free within 2ms. Arc eliminator for medium [8] B. Melouki, M. Lieutier, A. Lefort, 1996, “The
voltage system is able to extinguish the arc within 5ms. correlation between luminous and electric arc
characteristics”, Journal of Physics D: Applied
CONCLUSION Physics, Volume 29, Number 11, November 1996.
This paper has given on overview of methods to mitigate [9] IEEE, 2002, “IEEE Std 1584™-2002, IEEE Guide for
arc flash hazard. Because arcing time is the most critical Performing Arc-Flash Hazard Calculations”
factor, the fastest, optical sensor based protection methods
are preferred. Other important issues are the selectivity and
self-supervision of the protection system.

CIRED2009 Session 1 Paper No 0660

View publication stats

You might also like