ABB High Voltage Switchgear CNTS 201
Page 2 (10)
RATINGS
Apparatus
SF 6-gas circuit-breaker type LTB 145D1/B
DESCRIPTION
The SF6-gas circuit breaker type LTB145D1/B is of the auto-puffer type intended for use in
conventional open air switchyards.
A complete three-phase circuit-breaker consists of three breaker poles, connected to a common
operating device through mechanical linkages. The operating device is provided with shunt releases
for closing and opening operation and has motor-charged closing spring for closing of the circuit-
breaker.
During the closing operation the opening spring is charged.
The breaker pole consists of a breaking unit with two main circuit terminals, a hollow support insulator
enclosing the insulating rod and a link gear in a housing of cast aluminum. The circuit- breaker poles
can alternatively be mounted on separate base frames or on a common pole beam.
The breaking unit consists of a breaking chamber insulator with upper and lower terminals. To the
upper terminal the current path with the fixed contacts is connected and to the lower terminal a
current path with the moving contacts.
The moving contacts are connected to the linkage system in the mechanism housing through an
insulating rod.
TECHNICAL INFORMATION
Type of circuit-breaker LTB 145D1/B
Minimum clearance between live parts and earth See dimension print
Total length of break per pole 68 mm
Number of breaks per pole 1
Mass of complete circuit breaker See dimension print
Resistance in main circuit ≤ 40 µΩ
Closing time ≤ 40 ms
Opening time 20-25 ms
Break time 40 ms
Gas pressure range at 20℃ 0.43 - 0.50 MPa(abs)
Rated power consumption at rated operating voltage Closing coil 200 W
Opening coil 200 W
Maximum terminal load Static 1500 N
Dynamic 3000 N
Ambient temperature -40 to +40℃
Earthquake withstand capability 0.5 g
Circuit-breaker operating mechanism One device type BLK 222
Method of closing Through stored energy in closing spring
ensuring trip-free closing.
ABB High Voltage Switchgear CNTS 201
Page 4 (10)
DESIGN DAT A
Apparatus
SF 6-gas circuit-breaker type LTB 145D1/B
DRAWlNGS
DIELECTRIC TESTS
Type of test Standard Requirement Test value Report
IEC62271-100
Phase to earth 650 650
Lightning impulse voltage test. CI.6.2.6.2
Dry Between phase kV, peak 650 -
LI 1.2/50µS, pos + neg DL593-2006
Across open gap 650+70 650+70
CI.4.2
Phase to earth 275 275
SATS 07-S22
IEC62271-100 Dry Between phase kV, rms 275 -
CI.6.2.6.2 Across open gap 275+70 275+70
Power frequency voltage test,60s
DL593-2006 Phase to earth 275 275
CI.4.2 Wet Between phase kV, rms 275 -
Across open gap 275 275+70
Lightning impulse voltage test on
Control and auxiliary circuit
Auxiliary and control circuit, IEC60255-5 kV, peak 5 5
as a whole to earth
1.2/50µS
SATS 08-A05
Power frequency voltage test on IEC 62271-100 Control and auxiliary circuit 2000 2000
V, rms
Auxiliary and control circuit,60s CI.6.2.10 as a whole to earth
Appl. volt kV - - - 84 84 -
Making
Peak current kA - - - 100 100 -
a. c. comp kA 4(±20%) 12(±20%) 24(±20%) 40 40 40
Requirement
Make/Breakcurrent
d. c. comp % <20 <20 <20 <20 <20 51
a. c. kV 126 126 126 - 126 126
Recovery voltage 1)
equiv .d.c kV 178 178 178 - 178 178
u1 kV - - 133 - 133 133
t1 µs - - 44 - 67 67
uc kV 272 273 266 - 249 249
TRV
t2 µs - - 264 - 268 268
µs
2)
t3 39 55 - - - -
td µs 2-6 2-8 2-13 - 2 2
4)
Appl. volt kV 22.6-23.9 22.6-23.2 23.3-23.5 124.7 10.3-11.8 -
Making
Peak current kA 6.5-7.0 19.0-19.1 42.3-49.4 59.4 70.2-101.5 -
make/break a. c. comp kA 4.2-4.4 11.7-12.2 24.4-25.2 41.4 33.8-41.5 40.8-42.3
Corresponding tests
5)
current d. c. comp % <20 <20 <20 <20 17-31
3) 3) 3)
Recovery voltage DC kV 176-180 181-185 122-126 102.5-103.1 96.7-111.7
Measured TRV peak value kV 270-275 272-277 266-269 248-251 236-247
u1 kV - - 141 147 147
t1 µs - - 47 - 70 70
uc kV 281 278 269 256 256
Prospective TRV
t2 µs - - 227 242 242
2)
t3 µs 40.0 48.0 - - -
td µs 5.9 3.6 2.49 1.08 1.08
Report SATS 07-A56
1)In case of syntetic testing(current injection method)
2)In case of two parameter TRV
3)a.c. recovery voltage after 0.1s
4)Applied d.c. voltage
5)d.c. component at current zero. Correct current asymmetry has been verified by prospective current measurements
ABB High Voltage Switchgear CNTS 201
Page 8 (10)
Prospective TRV t3 2)
µs - -
td µs 0.9 1.6
um kV 169 161
Source uT kV 25 63
and
line side tdL µs <0.1 <0.1
Stot kV/µs 7.42 7.47
Report SATS 07-A56
1)In case of syntetic testing(current injection method)
2)In case of two parameter TRV
3)a.c. recovery voltage after 0.1s
ABB High Voltage Switchgear CNTS 201
Page 9 (10)
TRV t3 2)
µs 37.4 24.1
td µs 5.6 3.6
Uc/t3 kV/µs 9.36 14.02
Appl. volt kV - -
Making
Peak current kA - -
make/break a.c.comp kA 2.9 12.3-12.4
Corresponding tests