Professional Documents
Culture Documents
Pump Test Rig R
Pump Test Rig R
Table of Contents
CHAPTER SECTION
DESCRIPTION PAGE NO
NO NO
I A INTRODUCTION 2
B FLUSHING OIL 11
C PLANNED MAINTENANCE 19
II G SPECIAL WRITE-UP 48
H OPERATION PROCEDURE 57
CHAPTER – I
SECTION – A
INTRODUCTION:
RESERVOIRS
STRAINERS AND FILTERS
INSTAERS AND FILTERS
PIPING UP
PREPARATION OF PIPES AND FITTINGS
CHAPTER – I
SECTION – B
FLUSHING OIL:
CHAPTER – I
SECTION – C
PLANNED MAINTENANCE:
CHAPTER – I
SECTION – D
FILTER ELEMENT CHANGE & REPORT:
CHAPTER – I
SECTION – E
TROUBLE SHOOTING:
TROUBLE SHOOTING
ROUTINE MAINTENANCE AND PERFORMANCE
CHECKS
CHAPTER – I
SECTION – F
HYDRAULIC SUMBOLS
CHAPTER – II
SECTION-G
SPECIAL WRITE-UP
Our special thanks to Thriveni Earth Movers Pvt. Ltd., Jamshedpur / Chennai, for having given the
responsibility of Designing, Manufacturing, Supplying, Commissioning and Proving the Hydraulic
Test Rig System for their Jamshedpur Works.
In this section of the Operation and Maintenance Manual, we have attempted to give various Write-
Ups, Explanations, Dos & Don’ts, and Cautions etc. As applicable. The purpose of this section is to
prepare the Users (Operation Personnel) and Maintenance Personnel to be thoroughly understanding
the functions of the various units and utilize effectively the Test Rig System.
We hereby request everyone concerned to give enough time to go into all details as given and be
aware of all notes, circuits etc., as explained without over-looking any points. You are also expected
to follow all instructions and practices in your Operation and Maintenance sequences for good
performance and long life of your systems.
SPECIAL WRITE-UP
1.0 PURPOSE:
The purpose of the Test Rig is to facilitate Running & Load Tests to be carried out on all Hydraulic
Pumps (Open-Loop & Closed-Loop), Hydraulic Motors and Directional Valves. Details of tests,
testing methods etc. are elaborated separately under Operations heading.
The Test Rig consists of the following broad sub-assemblies. We have attempted to describe each
sub-assembly in a detailed manner, for carrying the sequences of operation as well as maintenance
practices. Our approach will be useful for your team in understanding and carrying out both
operations as well as maintenance practices for achieving long life and trouble-free running of the Test
Rig.
Note: Individual sub-assemblies are described well under separate sections. You may refer,
those sections.
Your Operators are required to understand the purposes, basic hydraulics, method of testing as well as
limiting parameters of this Test Rig, so that you don’t face any problem during your actual testing. Let
your personnel give a patient reading of all sections for understanding. In case of doubt, they are to
get the same cleared with the manufacturer’s team.
Note: An appeal is made that the Operators are required to spend enough time in
understanding the Logics, Method of Operations, D0s & DON’Ts as well the limiting
parameters of the Test Rig, so that your Rig is not under excessive load & wrong application by
ignorance.
The following are the main sub-assemblies and the details may be seen from the below briefed texts.
The Hydraulic System / Power Pack is designed and manufactured as per the following drawings:
a) Schematic Drawing, HFPS/TEPL/1711/CKT/R5, in Sheet 1 of 2
b) Bill of Materials, HFPS/TEPL/1711/CKT/ R5, in Sheet 2 of 2
c) Layout Drawing, (Inner), HFPS/TEPL/1711/LAY/ R1, in Sheet 1 of 2
d) Layout Drawing, (Outer), HFPS/TEPL/1711/LAY/ R1, in Sheet 2 of 2
Note:
1) The details of the Power Pack and various elements used are explained, as below:
2) The item numbers are marked in brackets, as shown in our Schematic Drawing.
Reservoir / Tank, is a fabricated unit out of mild steel plates & structural, as per the size
and orientation. It has a working volume of 2,500 litres. So much of volume of oil (working
Medium, ISO/VG/ 68) is to be filled in for the first time and each time, at regular intervals.
Check for level of oil and top-it up with the same specified oil, whenever the oil level is low.
Use the Oil Level Gauges (Item No.2) for your checking the oil level.
Filling-in the oil may be done using a Filtration System or a Porta-Filter, with built-in Filters.
Initially, additional volume of oil may be used to fill the lines and the space in the Elements.
You need to top it up, with the same oil, as & when required.
The reservoir fabrication is done using CO2 gas welding. It is de-burred, sand-blasted and
Painted inside with Epoxy painting and for surfaces outside first with Red-Oxide primer and
Finally with Enamel painting. The reservoir is also provided with four Clean-out Doors,
Access plates, Lifting Hooks, Baffle Plates, Suction Port Bulk heads / Suction Header / Return
/ Drain Port Bulk Heads / Threaded ports, as required.
Reservoir, forms the storage for the oil / hydraulic medium. The large volume allows
the oil temperature to remain close to ambient temperature.
Various Accessories are used for enhancing the performance of the system. The following
Accessories are fitted in the reservoir, which are placed for specific purposes
and for enhancement of overall performance:
Drain Valves, with Drain Plugs[Item No.4]
Float Switch cum Temperature Switch [Item No.5],
Air Breathers, [Item No. 3 , Qty.2Nos.]
Visual Level Indictor, [Item No.2, Qty.3 Nos.]
Suction Strainers, [Item No.7 - (3 Nos), for the main suction lines of main
pumps.
Additional Suction Strainer, [Item No.102, Qty.1 No.]
A common Suction Header (Line) is provided to facilitate all pumps’ suction flow requirement. This
header is as big as 6” NB and takes care of flow to all pumps (your Test Pumps as well as Motor
Filling Pumps and Pilot Pressure Pump), as per schematic drawing. A Suction line Butterfly Valve 6”
NB, (Item No.10, quantity one number is provided with electrical Limit Switch facility, for safe-
guarding the pumps from cavitation problems & to avoid dry-run of the pumps (in case the above
valve is remaining closed, at the time of your running the pumps. This Valve will facilitate your any
maintenance need to remove any pump for repair / replacement.
Further a set of Butterfly Valves of different sizes, together with electrical Limit-Switches, are fitted in
the individual suction lines. The purposes of these Valves with Limit Switches are for safety and
maintenance requirement, as and when needed, in future.
The below mentioned Butterfly Valves are fitted from the Suction Header leading to individual pumps.
Also, flexible Suction Line Hoses are provided for your enabling different Pumps’ Suction lines to be
connected. All suction lines are with combination of rigid pipes & flexible pipes for easy handling
and noise suppression, as well as avoidance of vibration. They are listed as shown in the table below:
REMARKS,
S NO. ITEM No. DESCRIPTION Qty.
if any
Butterfly Valve, (3”NB) with Limit
1 8 1 Set
Switch, LS1
Butterfly Valve, (4”NB) with Limit
2 9 1 Set
Switch, LS2
Butterfly Valve, (6”NB) with Limit
3 10 1 Set
Switch, LS3
Butterfly Valve, (2”NB) with Limit
4 45 1 Set
Switch, LS4
Butterfly Valve, (2.1/2”NB) with Limit
5 46 1 Set
Switch, LS5
Butterfly Valve, (1”NB) with Limit
6 56 1 Set
Switch, LS6
Butterfly Valve, (1”NB) with Limit
7 59 1 Set
Switch, LS8
Butterfly Valve, (1”NB) with Limit
8 75 1 Set
Switch, LS9
CAUTION 1: Kindly ensure that the Butterfly Valves are open in the corresponding suction
lines of the respective pumps when they are being switched on. This will enable dry run of the
pump and failure of the pumps.
CAUTION 2: Also make sure that the suction line is closed, by closing the respective Butterfly
Valves in the line leading to the pumps, In case, the pump is to be removed from the stand ( for
replacement or any maintenance/repair). In case the Butterfly Valve is open without pump
connected, it may lead to draining of the entire Reservoir Oil. It will cause heavy financial loss
to your company. Every Butter-fly Valve is also provided with one number Electrical Limit
Switch
for isolation of the respective Pumps.
CAUTION 3: Running any pump with the Butter-fly valve is closed condition will cause
cavitional problem and pump ceasing. It will be a failure of the pump readily. So, all Limit-
Switches are electrically interlocked for safety.
The above three Caution Points are important and clearly understood by the Operating &
Maintenance Team at your end.
One of the electric motors, used for the main drive (for testing the Pumps) is of 250 HP (Item No.17).
This motor has got the specification, as mentioned below:
250HP X 1440 RPM, 415VAC, 3-Ph, 50Hz, 4-Pole, B3, TEFC, Squirrel Cage, Class F Insulation and
suitable for taking variable speed of operation by a Frequency Controlled Unit. So, its speed could be
controlled from 1100 RPM to 2100RPM, as per the recommendations of the motor manufacturer,
ABB.
So your pumps could be run / tested at standard speed, namely at 1500 RPM, or at any speed between
1100 RPM to 2100 RPM, as per your test conditions, for your pumps as required; And the torque
available at that drive speed, will depend on the graphs, provided by ABB showing the relationship
between Speed VS Torque. For any clarifications, please refer to the characteristic curves attached to
the motor catalogue, in the respective section of this manual.
The Motor is mounted on a machined motor plate, (Item No.18) which is then mounted on a Base
Frame, (ITEM No.6) together with Anti-Vibration Pads (Item No.19), between the motor plate and the
base frame.
The drive to the Test Pump (Item No.14) is given from the motor using universal mounting bracket
(Item No.16) and flexible chain coupling (Item No.15). The universal mounting bracket is machined
in such a way that it could give accurate alignment to the pump mounting on its face, keeping the
alignment as per the drive standards specified by the Data Hand Books, i.e., avoiding any
misalignment of the shafts of pump & motor. This bracket will also be suitable to mount different
pumps having various mounting face dimensions, as per your requirement specified by you. Any
additional mounting bracket if required, the same may be made by you.
Likewise, on the delivery of the pumps’ side a flexible hose are considered, before the flows are taken
to the loading valves as per the test procedures.
The delivery hoses are with different sizes to suit your different flow rate capacities of the pumps. The
different sizes are given to facilitate, different delivery port sizes available with the pumps. Different
port sizes are fixed as per the flow velocities recommended by the Data Hand Books, to avoid
turbulence flow pattern. You are advised to follow the recommended velocities as per Vickers
Practices, to avoid heat up, turbulence, cavitation etc. on the suction side of the pump.
The second electric motor, used for the main drive (for testing the Pumps & hydraulic motors) is of 50
HP (Item No.52) . This motor has got the specification, as mentioned below:
50HP X 1440 RPM, 415VAC, 3-Ph, 50Hz, 4-Pole, B3, TEFC, Squirrel Cage, Class F Insulation and
suitable for taking variable speed of operation by a Frequency Controlled Unit. So, its speed could be
controlled from 1100 RPM to 2100RPM, as per the recommendations of the motor manufacturer,
ABB.
So your pumps could be run / tested at standard speed, namely at 1500 RPM, or at any speed between
1100 RPM to 2100 RPM, as per your test conditions, for your pumps as required; And the torque
available at that drive speed, will depend on the graphs, provided by ABB showing the relationship
between Speed VS Torque. For any clarifications, please refer to the characteristic curves attached to
the motor catalogue, in the respective section of this manual.
The Motor is mounted on a machined motor plate, (Item No.53) which is then mounted on a Base
Frame, (ITEM No.6) together with Anti-Vibration Pads (Item No.54), between the motor plate and the
base frame.
The drive to the test pump is given from the motor using universal mounting bracket (Item No.51) and
flexible chain coupling (Item No.50). The universal mounting bracket is machined in such a way that
it could give accurate alignment to the pump mounting on its face, keeping the alignment as per the
drive standards specified by the Data Hand Books, i.e., avoiding any misalignment of the shafts of
pump & motor. This bracket will also be suitable to mount different pumps having various mounting
face dimensions, as per your requirement specified by you. Any additional mounting bracket if
required, the same may be made by you.
The delivery hoses are with different sizes to suit your different flow rate capacities of the pumps. The
different sizes are given to facilitate, different delivery port sizes available with the pumps. Different
port sizes are fixed as per the flow velocities recommended by the Data Hand Books, to avoid
turbulence flow pattern. You are advised to follow the recommended velocities as per Vickers
Practices, to avoid heat up, turbulence, cavitation etc. on the suction side of the pump.
Special Consideration # 1
Such use of the flexible hoses on the delivery side and suction side of the individual pumps as well as
use of anti-vibration pads, allow us to decrease the noise level of the overall drive as well as it helps us
in keeping the vibration under control.
Special Consideration # 2
The use of universal face plate and flexible coupling, duly machined, will allow your mounting any
pump, having different mounting dimensions upon its face / flanges for suitably mounting on the
universal face plate. Any additional universal flexible plate may be manufactured by you, in case of
any new mounting facility is to be created.
These pumps are to be mounted with either 250 HP Motor or 50 HP Motor, depending upon the flow
rate levels and test pressures. As you know, the drive power will be a function of flow rate (in LPM)
and test pressure, (in Bar). Your selection of drive motor should be based on the power required to run
your selected pumps. Since the maximum power available in the above two stations are limited to 250
HP & 50 HP, your selection of Test Station will depend on your final power requirement and its
availability. You may arrive at the power required using the formula, namely, Q(in LPM) X P(in Bar)
/ 378.5. The Power Unit will be in HP and our assumed efficiency factor of the Drive as 85%.
Your pumps (Items Nos,14 or 49) may be mounted on the Universal Mounting Bracket (Item Nos.16
or 51), using the Chain drive coupling (Item Nos. 15 or 50). Pumps bolts are to be suitably selected
and torqued to required clamping levels depending on the pumps to be tested. For the tightening
torque values of the Screws, please refer to table given separately). The Test Pumps and the
mounting screws are in the scope of TEML.
Depending upon the number of Suction Ports on the Pump (to be tested), suction hoses are to be
connected using the correct hose diameter given under Suction Header, Refer Section 2.1.2 above.
On the delivery side, (please refer to section 2.1 7) there are multiple delivery hoses are provided,
which are to be selected, based on the type of pump (Open-loop or Closed-loop) and hydraulic motor.
You may refer to the details of the delivery line hoses (size wise indicated / tabulated for your ready
understanding and use. Please be clear with the selection of right size hoses accordingly. (If you are in
doubt, you may consult HFPS Team, for clarification).
Further, multiple number of Drain Ports are provided with hoses, for connecting the drain ports (from
the Piston pumps or motors) when they are being tested. Generally, the pumps such as gear type or
vane type are not provided with any drain ports on its body. But, other pumps, namely Axial Piston
Pumps or Radial Piston Pumps as well as all Hydraulic Motors ( Gear / Vane / Piston) are provided
with Drain Ports.
Note: Only one drive, either 250 HP or 50 HP can be driven at any time. The PLC is
programmed to cater to the need accordingly. This point is to be noted by the Operator
concerned and the Test Rig is handled accordingly.
CAUTION: Drain ports from the Piston Pumps & Hydraulic Motors are to be connected back
to tank, prior to your starting any testing with the Test Rig, using the Spare Hoses duly fitted
with Quick Disconnect Couplings. Non-connection of these Drain Ports ( from the Test Pumps)
will lead to failure of the Test Pumps. You may face some bursting of the hoses / pipe lines /
fittings or the pump itself, depending on the least resistance path of oil to escape. Your
ignorance may even cause fatal accidents leading to death or injury to Operators. Enough care
should be exercised in the regard by all concerned.
The following information may be noted regarding the Delivery Ports and used by the Operator, as
suggested by us.
2.1.7.5
One more Delivery Ports are meant for Motor Lines filling, for closed-loop Motor testing.
OPERATION PROCEDURE
Brief Procedure for Operation of the Test Rig (This Notes are prepared to make the PLC Software
preparation enabling customer operate easily the Test Requirements).
I. PUMP OPEN-LOOP TESTS ( Drive 250 HP) This is for Flow Rates over 150 LPM but
less than 600 LPM)
a) PUMPS could be single / Double / Triple types. Mount the Pump on the respective
base / establish mechanical link with 250 HP Motor, using the Flexible Drive Coupling.
The items involved are M1, 17 & 14.
b) Establish Suction Ports / Delivery Ports & also Drain Port Connections. Depending on
type of Pump ( i.e., Single / Double / Triple), Keep the Suction Line Valves Open and
avail the output of LS1 , LS2, LS3, LS4, & LS5.
g) Delivery of the Pump is to be taken thru’ the “Check Valve Bridge # 1) and further
thru’ Pressure Line Filters 25, Flow Meter Block 40 and Loading Valve 41. The
Delivery Line from D1 is already connected to all above Units and remains established
as per piping arrangement.
h) The Remote Relief Valve 43 could be used from Operator’s Cabin for physical
Loading.
i) Pressure Line Filters’ (25) Clogging Switches ‘CLS3’ & ‘CLS4’ as well as Pressure
Transducer ‘PT3’, Temperature Switch ‘TS3’ and Flow Meter ‘FM3’ outputs are to
looked for / activated. The outputs from these are important for our Study & Data
Collection. For completion of the Circuit to be in order, Port D2 ( Delivery Port) will
not be used. Also make sure in T Block 122, the return from Check Block Bridge
j) # 1 is connected back to Reservoir ( it should remain blocked towards D2. This is
important).
Note:1
In case the Pump to be tested is a Double or Triple Pumps, similar exercise is to be carried out
using Delivery Ports D3 and D5 for Checking the Flow rate using the other Flow Meters (33 & 26).
We assume that the other two Flows are of the order of less than 15 LPM and Less than 60 LPM
respectively.
Also the D4 port should not be connected and also the T Block (123) will divert the Oil to
Reservoir. Necessary Plugging of the T Block is important.
Note 2:
In case, the Pump is a Single or Double type and its Flow rates are less than 150 LPM and the
second Delivery is less than 60 LPM, the other Part of the Circuit with Drive Motor 50 HP could be
used as the Prime Mover. The Tests are to be run is similar manner as shown in Note 2 Using the
corresponding Controls as shown in the Circuit.
Note 3:
In case the Test Pump is less than 60 LPM of flow discharging capacity, then such pumps will be
run by 50 HP Motor and the Flow verification will be done by using the Port D5. This pump will be
only an open-loop pump and the controls such as Pressure Line Filter (23) and Clog Indicator (CLS1),
Flow Block (26), PT
II. PUMP, Closed-Loop type, TESTS (Drive 250 HP) This is for Flow Rates over 150
LPM but Less than 600 LPM).
The Closed-Loop Pump will be of single type / section only. If the maximum Flow of the Pump
is less than 600 LPM, the Drive Motor 250 HP would be considered for the test.
Note:
The Maximum Pressure capability of the Test depends on the Maximum Flow rate and the
Input Power available. The Customer would check for Total Power requirement and the tests would
be done limiting the Pressure (Loading) and Speed of operation. Customer is requested to verify the
Power Availability and decide on the Flow rate and Working Pressure, as maximum available which
will decide on the Power availability, limiting to 250 HP.
a) The Test Pump will be driven by the Drive 250 HP Motor (if the Flow rate is above 150 LP but
less than 600 LPM)
The Test Pump would be connected to the Drive Motor 250 HP The Pump will not have a
separate Suction port (as found in the Open-Loop Pump. In this case, the Ports D1 and D2 will be
connected to the two Ports (normally called as P & S, by the Pump manufacturers).
The two main Ports of the Pump will be connected to D1 & D2 ports. The Charge Pump,
generally, integral with the main pump will be provided with a Suction Port Connection with Port 57.
The Limit Switch (LS6 / LS7) will be used for ensuring the line remaining open.
The Pump when run by the Drive Motor 250 HP will deliver thru’ D1 and will go thru’ the Check
Valve Bridge (38), Pressure Line Filters (25), Flow Meter Block (40) and Loading Valve (42). The
Remote Relief Valve (43) could be used by the Operator for Loading the Pump.
In this condition the all the Electrical Controls like, CLS3, CLS4, PT3, TS3 & FM3 all will be
functional for getting values for our study and data collection.
During the Test the T Block (122) will be blocked to Reservoir, but will be connected to Port D2.
In this arrangement it will be possible to change the Delivery Ports of the Pump for ensuring the Flow
passing in the opposite direction. This feature is achieved by suitably operating the Swash Plate of the
Pump with reverse polarity. In this case the entire testing set up will remain the same and the test
results are obtainable.
The Function of the 2 HP X 11LPM, Motor Pump Assembly is to support any features such as “Brake
Release, Pilot Control and / or Case Filling (for Pumps or Motors)
This System is provided with Suction Line Ball Valve, which is monitored by Limit Switch (LS8);
Other Functions such as Brake Release ( 2 ports are provided) , Pilot Control and Case Filling Line are
selected by Energising corresponding Solenoids, namely, S1, S2, S3 & S4 respectively.
a) The Test Pump will be driven by the Drive 250 HP Motor or 50 HP Motor (if the Flow rate is
above 60 LPM but less than 150 LPM)
Likewise, if the output of the Closed-Loop Pump is less 150 LPM, but more than 60 LPM, , the Drive
Motor 250 HP or 50 HP could be used ( depending on the maximum pressure test requirement
(ultimately keeping the total power as the factor to decide. For this the Ports D3 & D4 will be used
connecting the Flow rate thru’ check Valve Bridge #2 and the corresponding Pressure Line Filter (24),
Flow Block (33) and Loading Valve (34). The Remote Relief Valve also could be used by the
Operator. This Valve is placed in the Operator’s Cabin for easy regulation.
LOAD GRAPH
ELECTRICAL SECTION:
This section includes information of Electrical requirement for the operation of Hydraulic Pump
Test rig. Electrical maintaining or service work to be attended by qualified personnel only.
Condition:
The system is operated from a three phase source providing the voltages and related parameters
listed in the electrical circuit.
Main electrical panel is on the Left side of the test rig. The remote pendent with HMI and Data
Logger for recording is provided in a separate Cabin arrangement at the right front corner of
the Test rig which is protected with sigh glass. Operator will be inside this cabin during testing.
Power Circuit.
Power Circuit for 250 HP Motor with VFD and related controls.
Power Circuit for 50 HP Motor with VFD and related controls.
Solenoid valve,
Temperature Controller
Oil Level Switches.
Limit Switches
Filter Clog Switches
PLC is used with Expansion Unit input and output modules also unit with Analog input/output
Module, Relay Modules, SSR Relays,
0-20mA output supply operation with POT arrangement,
0-10V DC output supply operation with POT.
Refer to the Hydraulic Power supply Electrical schematic d provided for detailed understanding.
PANEL:
Is fabricated in CRCA Steel Sheet of 2mm thick including doors, partition sheets of 1.6mm and Gland
Plates of 3mm thick.
External, Internal & Mounting Plates has been painted with Texture Finish
Cable Incoming and outgoing is from BACK DOWN Entry.
Hydraulic Pump Test Rig of 50 HP & 250 HP Capacity Page 66
HI-TECH FLUID POWER SYSTEMS
For Incoming supply, BUSBAR connection, Power Socket, Transformer connection and other panel
accessories wiring please refer page No. 8 of 22 in electrical drawings section.
Test Procedures
WHAT IS HMI?
An HMI is a software application that presents information to an operator or user about the state of a
process, and to accept and implement the operators control instructions. Typically information is
displayed in a graphic format
MAIN SCREEN
SELECT DESIRED TEST AND SCREEN WILL CHANGE AS BELOW (Selected 250HP
Closed Loop Pump Testing)
250 HP
VALVE TESTING
INTERLOCKS SCREENS
INTER LOCKS
LS1: Suction Ball Valve. If the Ball Valve is in closed condition 25HP Pump will not start.
Valve to be Open for System Start up
LS2: Suction Ball Valve. If the Ball Valve is in closed condition 2HP Pump will not start.
Valve to be Open for System Start up
LS3: Suction Ball Valve for Charge Pump. If the Ball Valve is in closed condition, Main
Motors 250HP & 50HP will not start. Valve to be Open for System Start up
LS4: This is the Main Suction Ball Valve. This should be opened along with LS3, LS5, LS6,
and LS7 & LS8. If this is closed Main Motors 250HP & 50HP will not start. Valve to be Open
for System Start up
LS5: Suction Line Ball Valve for 2” (should be opened if the pump suction is connected to this
line and the same should be selected in the HMI so that the system will Know this valve is
open or closed during operation)
LS6: Suction Line Ball Valve for 2 1/2” (should be opened if the pump suction is connected to
this line and the same should be selected in the HMI so that the system will Know this valve is
open or closed during operation)
LS7: Suction Line Ball Valve for 4” (should be opened if the pump suction is connected to this
line and the same should be selected in the HMI so that the system will Know this valve is
open or closed during operation)
LS8: Suction Line Ball Valve for 6” (should be opened if the pump suction is connected to this
line and the same should be selected in the HMI so that the system will Know this valve is
open or closed during operation)
CLS1: This filter is used in the 60LPM Pump line, if this filter is chocked then your main
motor will trip and give the signal as CLS1 clogged (As an action plan you have to change the
filter element)
CLS2: This filter is used in the 150LPM Pump line, if this filter is chocked then your main
motor will trip and give the signal as CLS2 clogged (As an action plan you have to change the
filter element)
CLS3 & CLS4: This filters are used in the 600LPM Pump line as Parallel connection, if this
filter is chocked then your main motor will trip and give the signal as CLS3 or CLS4 clogged
(As an action plan you have to change the filter element)
CLS5 & CLS6: This filters are used in the chiller unit line with series connection, which helps
in system oil filtration. if this filter is chocked then Chiller unit will trip and give the signal as
CLS5 or CLS6 clogged (As an action plan you have to change the filter element)
CLS7: This Filter is used in the Main tank where the drain oil is received from the Drain tank.
If this is chocked than your drain tank motor 0.5HP will trip (As an action plan you have to
change the filter element) PLEASE NOTE IF THIS MOTOR IS UNDER TRIP CONDITION
AND THE OIL IN THE DRAIN TRAY IS FULL IT MAY OVER FLOW ON THE FLOOR)
THIS LINE IS TO BE MONINTERED REGULARLY.
LVLS1: This Level switch has 2 level sensing, fixed on the Main tank. if switch indicates
High level then the drain system stops. If the level switch indicates Low level then Main
system trips. Always maintain the oil level Mainly when you test the Large flow pumps.
LVLS2: This Level switch has 2 level sensing fixed on the drain tank. if switch indicates High
level then the motor starts and oil will be transferred to the main tank. If the level switch
indicates Low level then the motor stops. This is an automatic process. Do not disturb the level
switch. It this malfunctions. Oil will overflow on the floor.
Other inter locks like Oil temperature High VFD trip due to High load etc. Is
considered. Which you can see on the HMI scree.
All alarm will be displayed in the alarm screen. This should be cleared manually after
attending the issue.
ALARM SCREEN
CHAPTER – III
SECTION-I
CATALOGUES OF ACCESSORIES AND HYDRAULIC UNITS
01 Level Gauge 80
02 Filler Breather 81
03 Suction Strainer 82
04 Drain Valve 83
06 Chain Coupling 86
07 Electric Motor 87
08 VFD 98
13 Coupling 153
25 Heater 215
LEVEL GAUGE
FILLER BREATHER
SUCTION STRAINER
DRAIN VALVE
CHAIN COUPLING
ELECTRIC MOTOR
VFD DRIVE
ANTI-VIBRATION PAD
FLOW METER
GEAR PUMP
COULING
CHECK VALVE
PRESSURE GAUGE
PISTON PUMP
MINIMIZE COUPLING
MICROBORE HOSE
DATALOGGER
BUTTERFLY VALVE
HEATER
CHAPTER – IV
SECTION – J
Test Certificate of major brought out items
CHAPTER – V
SECTION – K
BILL OF MATERIALS
S No Description Model Code Qty Make
1 Reservoir 2500 Ltrs 1 No HFPS
2 Level Gauge LG06-05 3 No’s Hydro
3 Filler Breather FSB-25 2 No’s Hydro
4 Drain Valve 3/4" 1 No Legris
Oil Level and Temperature
5 RTLI/L500 1 No Vidyuth
switch
6 Base Frame Suitable 1 No HFPS
7 Suction Strainer SC3-150 3 No’s Hydro
Suction line Butterfly Valve
8 2IWNGSL/PN/16-80 (3") M 1 No L&T
with limit switch
Suction line Butterfly Valve
9 2IWNGSL/PN/16-100 1 No L&T
with limit switch
Suction line Butterfly Valve
10 2IWNGSL/PN/16-150 (6") 1 No L&T
with limit switch
3" SSC 3" BSP FEMALE
11 Suction Line Flexible Hose STRAIGHT X STRAIGHT OAL 1 No Parker
- 3 MTR (MS FITTING)
4" SSC 4" FLANGE AS PER
DRAWING BEND X
12 Suction Line Flexible Hose 1 No Parker
STRAIGHT OAL - 3 MTR (MS
FITTING)
6” SSC 6" FLANGE AS PER
13 Suction Line Flexible Hose DRAWING OAL - 3 MTR (MS 1 No Parker
FLANGE)
Customer Scope of
14 Test Pump Suitable 1 No
Supply
15 Chain Coupling NT-2020 1 No Nu-Tech
16 Universal Mounting Bracket Suitable 1 No HFPS
CHAPTER – V
SECTION – L
ELECTRICAL DRAWINGS