Professional Documents
Culture Documents
LNL 3300 M 5
LNL 3300 M 5
Table of Contents
revision 7 — 5
Table of Contents
9. Wiring ................................................................................................... 45
9.1 Communication Wiring ....................................................................................... 45
9.2 Input Power, Enclosure Tamper, and Power Fault Input Wiring ......................... 46
6 — revision 7
M Series Installation Guide
revision 7 — 7
Table of Contents
8 — revision 7
HARDWARE
INSTALLATION
GUIDELINES
M Series Installation Guide
1 Introduction
Important: In order to use the LNL-3300-M5 Intelligent System Controller (ISC), the
Migration Controllers (CASI) license bit must be enabled.
The Lenel M Series is a user-configurable controller enclosure for use with the OnGuard access control and
alarm management software platforms. The M5 controller provides distributed processing for the interface
of access control readers, keypads, alarm inputs and outputs back to a host system computer. Distributed
processing from the PXNplus CPU board within the M5 enclosure allows the controller to operate
independent of the host system computer with the majority of access control and alarm monitoring decisions
made locally at the controller.
The Lenel M Series provides instant response for door control and alarm sensing in the field, while leaving
the host system computer with more processing power for quickly executing daily operations such as alarm
response, database updates and reporting.
The Lenel M Series has five (5) card slots for controller boards. All boards plug into the controller
backplane making field configuration and maintenance easy and economical.
The Lenel M Series additionally incorporates flash memory technology that provides the ability to receive
its operating system and application remotely from the host system over the already established
communications path. This allows future firmware upgrades centrally from the host system without
requiring costly service trips to each location for firmware replacement. Both the modular design and the
flash memory technology of the Lenel M Series provide a simple migration path when considering future
host system upgrades.
The M5 controller consists of the following:
• Enclosure (all steel cabinet with key lock and tamper-switch-protected door)
• Power supply (user-provided)
• Battery backup power supply (user-provided)
• LNL-3300-M5 Intelligent System Controller (ISC)
Options include:
• LNL-1100-20DI Input/Output Control Module
• LNL-8000-MCOM RS-485 Interface Module
• Reader Processing boards:
- LNL-1320-2RP Dual Door Control Module
- LNL-1320-S2RP Supervised Dual Door Control Module
- LNL-1380-8RP Reader Interface Module
• Output boards:
- LNL-1200-16DO Digital Output Control Module
- LNL-1200-16DOR Relay Output Control Module
revision 7 — 11
Hardware Installation Guidelines
2 Installation
The following is a basic outline for installing and setting up the Lenel M Series system. Some steps may
have been done depending on what was ordered. Some steps are optional, depending on the additional
equipment to be used. These steps are noted.
Important: Do not apply power to any component until the installation is complete. Damage
to the components may occur if power is incorrectly applied.
1. Determine the cable clamps needed and obtain them before starting the installation.
During the installation, remember to:
• Label all connections/cables for ease of maintenance.
• Leave enough slack in the wiring so the cables can be “dressed”. This minimizes interference
during board removal or replacement.
2. Unpack your system. Refer to Introduction on page 11.
3. Mount the enclosure. Refer to Mounting on page 14.
4. Mount and install the power supply. Refer to Installing the Power Supply on page 17.
5. Mount and install the battery backup. Refer to Installing the Battery Backup on page 19.
6. Wire up the LNL-3300-M5 ISC. Be sure to configure and verify the switch settings. Refer to Wiring on
page 45.
7. If using networked controllers, verify that your network is up and running.
8. Install the reader board(s) into the enclosure and wire up the readers to the controller. Be sure to
configure and verify the switch settings, jumpers, and/or resistor packs.
9. If using digital inputs, insert the LNL-1100-DI into the enclosure and wire the inputs to the board. Be
sure to configure and verify the switch settings. Refer to Overview of the LNL-1100-20DI on page 57.
10. If using digital outputs, insert either the LNL-1200-16DO or LNL-1200-16DOR into the enclosure and
wire the outputs to the board. Be sure to configure and verify the switch settings. Refer to Overview of
the LNL-1200-16DO on page 67 and Overview of the LNL-1200-16DOR on page 77.
11. Test the wiring before you apply power. Refer to Pre-Power Up Testing on page 22
12. Configure your controller. Configure the controller using the Integrated Configuration Tool (ICT).
Refer to Web Configuration on page 47.
12 — revision 7
M Series Installation Guide
The authorized installation contractor should comply with the following rules:
• Neatly label cables at both ends.
(For example, labels should include: controller address number/device or reader number)
• Use individually shielded pairs of cables only. All wiring must comply with local, state, and federal
electrical codes and fire codes.
• Obey all national, state, and local electrical and safety codes.
• Obtain any required permits and/or inspections. Contact the local fire marshal for assistance if
necessary.
• Safety of customer personnel is the primary consideration of the installation.
• Neatly dress and tie or lace all wiring in a professional manner.
• Gather together and tape all unused conductors in multiple conductor cables.
• Shield all cabling and terminate properly.
Notes: This is an FCC Class A product. In a domestic environment, this product may cause radio
interference in which case the user may be required to take adequate measures.
Circuit board components are vulnerable to damage by electrostatic discharge (ESD). ESD can
cause immediate or subtle damage to sensitive electronic parts. An electrostatic charge can
build up on the human body and then discharge when you touch a board. A discharge can be
produced when walking across a carpet and touching a board, for example. Before handling
any board, make sure you dissipate your body’s charge by touching ground. This discharges
any static electricity build-up.
• Where practical, keep cables well separated from each other. Separate power cables from signal cables.
• Keep the break-out at the ends of signal cables as short as possible.
• Ground all shield drain wire(s) at the M5 controller using the grounding studs provided outside the
cabinet enclosure.
• For communication cables between controllers, ground shield to the upstream controller only.
revision 7 — 13
Hardware Installation Guidelines
2.4 Cabling
2.5 Mounting
Read the mounting and handling guidelines below before beginning to mount the controller.
14 — revision 7
M Series Installation Guide
Note: Do not apply power to any component during installation. Damage to components may occur
if power is incorrectly applied.
7. Find the nearest earth ground (electrical box, ground bus, etc.). Run wire from the M5 cabinet ground
terminal (cabinet bottom left) to earth ground point. Use wire size in accordance with local and national
electrical codes.
revision 7 — 15
Hardware Installation Guidelines
15
2
3
14 4
5 6
13
8
12
11
10
Callout Description
1 Mounting surface
3 Tamper switch
5 Slot J7
7 Slot J6 (empty)
16 — revision 7
M Series Installation Guide
Callout Description
11 Slot J1
The Lenel M Series requires a 12 VDC, 3 A minimum, power supply. Depending on system configuration, a
larger power supply may be required.
Note: For downstream controller enclosures, connect power to the LNL-8000-MCOM using the
same steps and guidelines to connect power to the LNL-3300-M5.
Notes: A readily accessible disconnect device shall be incorporated in the building installation wiring.
This equipment has been designed for connection to an IT power distribution system.
Note: There are three pairs of power connections on the LNL-3300-M5 ISC, all are in parallel. If
needed the other two pairs can supply power to the I/O boards.
revision 7 — 17
Hardware Installation Guidelines
TB1
VIN
1
GND
+ VIN 3
3
4 GND 4
-
VIN
GND
TMPR
PFLT
Callout Description
Notes: Controller earth grounding (AC grounding) is a critical element for proper operation.
Connect the GND signal to earth ground in one location within the system. Multiple earth
ground connections are not recommended and can cause ground loop problems.
Test AC power ground to ensure proper earth grounding. Using an ohmmeter, measure the
resistance between the enclosure ground stud and a known good earth ground (metal water
18 — revision 7
M Series Installation Guide
pipe or building structural steel frame). If resistance is greater than 50 ohms, it indicates poor
AC ground. A good earth ground must be made before completing the installation.
Do not ground both cable ends.
Observe polarity on the 12 VDC input. If the polarity is reversed, the fuse will blow to prevent
damage. If the fuse blows, replace with a fuse of the same type and rating.
Note: Make sure all power (AC input and battery backup) is disconnected before installing any of the
printed circuit boards.
Wiring Battery Backup with Built-in Relay for Fault Output (AC Power Fail)
6
1
TB1
NC 7 1
9
2K 8 2
2 COM 2K
NO 11
TB1
+ +
3 10
- -
+ 12
4 3
- 13 4
GND
NC
5
COM
14 6
15 8
16
Wiring Battery Backup with Built-in Relay for Fault Output (AC Power Fail) Callouts
Callout Description
revision 7 — 19
Hardware Installation Guidelines
Wiring Battery Backup with Built-in Relay for Fault Output (AC Power Fail) Callouts
Callout Description
3 Battery connections
16 FCC and CE compliance: shield grounds must be stripped back through the knockout hole
(strain relief) and grounded to external ground studs provided.
1. Connect the tamper switch to the LNL-3300-M5 on TB1-6 (GND) and TB1-7 (TMPR). Only use a
Normally Closed contact.
2. Connect AC power fail input from a battery backup unit to the LNL-3300-M5 on TB1-6 (GND) and
TB1-8 (PFLT).
The battery backup unit must supply either a Normally Closed dry contact or a sense line that is low
(GND), meaning no AC power failure.
20 — revision 7
M Series Installation Guide
TB1
VIN
GND
VIN
GND
VIN
2 6
GND
5
3 TMPR 7
4
PFLT 8
Callout Description
2.7.2 LNL-8000-MCOM
The LNL-8000-MCOM does not have dedicated inputs for enclosure tamper and UPS fault monitoring.
There are three options available to wire tamper and power fault switches in downstream controller
enclosures:
• Wire the tamper and power fault switches in series from the first controller enclosure to downstream
controller enclosures. Use conduit when wiring from one enclosure to the next, and ensure the conduit
is inaccessible. With this option, the user cannot determine which controller enclosure is reporting the
alarm.
• Wire the tamper and power fault switches to available inputs on the LNL-1100-20DI board.
• Wire the tamper and power fault switches to available reader port inputs.
The inputs on the LNL-1100-20DI, LNL-1320-2RP, and the LNL-1320-S2RP are monitor points configured
as unsupervised, Normally Closed contacts.
revision 7 — 21
Hardware Installation Guidelines
3 Pre-Power Up Testing
1. Measure the AC power supplied to the power supply (110 VAC or 220 VAC, depending on the power
supply installed).
Note: The power supply must have a dedicated circuit breaker. Do not plug into an outlet that is
controlled by an on/off switch.
2. Using an ohmmeter, test the reader power wiring to determine if a short circuit exists. Unplug each
reader connector and measure, from the reader connector going out to the readers between the + pin
(VO or 12V) to chassis and the + pin to the ground pin.
Refer to the following list of terminal blocks and pins for more information:
- LNL-1320-2RP and LNL-1320-S2RP:
– Reader Port 1: TB1-1: VO; TB1-2: GND
– Reader Port 2: TB3-1: VO; TB3-2: GND
- LNL-1380-8RP:
– Reader Port 1: TB1-1: 12V; TB1-2: GND
– Reader Port 2: TB1-5: 12V; TB1-6: GND
– Reader Port 3: TB2-1: 12V; TB2-2: GND
– Reader Port 4: TB2-5: 12V; TB2-6: GND
– Reader Port 5: TB3-1: 12V; TB3-2: GND
– Reader Port 6: TB3-5: 12V; TB3-6: GND
– Reader Port 7: TB4-1: 12V; TB4-2: GND
– Reader Port 8: TB4-5: 12V; TB4-6: GND
Result: A measurement of less than 100 ohms indicates a short circuit. Correct this condition before
applying power to the system.
3. If an LNL-1200-16DO is installed, check for a short circuit. Unplug each connector and measure from
chassis ground to all pins on the LNL-1200-16DO connector.
Result: A measurement of less than 100 ohms indicates a short circuit. Trace out the wiring to locate
the short circuit.
4. Reconnect all connectors.
5. On the LNL-3300-M5, disconnect the power input connector from Terminal Block 1 (TB1).
6. Use a voltmeter to measure the input voltage across TB1-3 (VIN) and TB1-4 (GND) on the
LNL-3300-M5.
Result: If the voltmeter reads -12 to -15 VDC, the wires are reversed.
Solution: Reverse the wires on TB1-3 (VIN) and TB1-4 (GND) so TB1-3 is the + voltage. The
voltmeter should read +12 to +15 VDC.
7. Reconnect the power input connector from TB1 connector removed in Step 5.
8. Apply power to the system.
22 — revision 7
M Series Installation Guide
4 Troubleshooting
This section provides information to help diagnose and solve various problems that may arise while
configuring or using the Lenel M Series and offers technical support contacts in case assistance is needed.
Refer to the appropriate section:
• Power Problems on page 23
• Reader Problems on page 24
• Door Strike Problems on page 25
• Contacting Technical Support on page 26
1. Use a voltmeter to check the power supply output. It should read 12 to 15 VDC. If there is no output,
make sure the power supply is not on a switched outlet. Be sure the circuit breaker for the power supply
is not tripped.
2. Make sure the power input connector is properly seated in TB1 on the LNL-3300-M5.
3. Make sure the LNL-3300-M5 is seated properly into the backplane and that no pins are bent on J6, the
48-pin connector.
4. Disconnect the power input connector from TB1 on the LNL-3300-M5. Remove the LNL-3300-M5 and
inspect the fuse. If the fuse is blown, replace it.
Note: Replace the fuse with one of the same type and rating. Do not power the unit back on until the
problem is identified and corrected.
a. Make sure that the wiring connections from the power supply to the LNL-3300-M5 are not
reversed. If these connections are OK, go to Step 4b.
b. Use an ohmmeter to check the resistance between TB1-3 (VIN) and TB1-4 (GND) on the
LNL-3300-M5. If the resistance is less than 200 ohms, there is a short from power to ground.
Isolate the fault by doing the following:
– Remove all boards from the backplane except the LNL-3300-M5. Add each board while
measuring the resistance on J6 pins 3 and 4. When the resistance falls below 200 ohms while a
board is plugged in, isolate the board. Continue checking the remaining boards for other
ground faults.
– Remove connectors one by one on the faulty boards until the fault condition disappears
(resistance goes above 200 ohms). Trace out wiring on these connectors to find and correct the
problem.
revision 7 — 23
Hardware Installation Guidelines
Consult your reader installation manual for potential problems that are not related to the LNL-3300-M5
controller. Also refer to the following sections:
• Using the LNL-1320-2RP on page 24
• Using the LNL-1320-S2RP on page 24
• Using the LNL-1380-8RP on page 25
1. Make sure that the reader selection voltage jumper (JP5) on the LNL-1320-2RP is properly set. Refer to
Setting the Reader Power Selection Jumper (J5) on page 92.
Caution: Do not set JP5 to 12 V for a 5 V reader. Doing so may permanently damage the
reader.
2. Make sure that the proper resistor packs are installed in the LNL-1320-2RP. Refer to Installing Resistor
Packs on page 34.
3. Check the wiring between the LNL-1320-2RP board and the reader. Refer to Reader Wiring on page 94
and the reader installation manual.
4. Make sure the connectors are firmly seated in TB1 (Reader Port 1) and TB3 (Reader Port 2) on the
LNL-1320-2RP board.
Problem: The reader has power, but the Status LEDs 1 (Reader Port 1) and 2 (Reader Port 2) on the
LNL-1320-2RP do not flash at all (no reader activity).
Resolution:
1. Make sure that the resistor packs are installed and are the correct value for the reader type being used.
2. Make sure that the DIP switch settings on the LNL-1320-2RP for address and reader technology/format
are correct. Refer to Setting the Device Address and Baud Rate on page 91.
3. Check the wiring between the reader and the LNL-1320-2RP. Refer to Reader Wiring on page 94 and
the reader installation manual.
1. Make sure that the reader selection voltage jumper (JP5) on the LNL-1320-S2RP is properly set. Refer
to Setting the Reader Power Selection Jumper (J5) on page 114.
24 — revision 7
M Series Installation Guide
Caution: Do not set JP5 to 12 V for a 5 V reader. Doing so may permanently damage the
reader.
2. Make sure that the proper resistor packs are installed in the LNL-1320-S2RP. Refer to Installing
Resistor Packs on page 34.
3. Check the wiring between the LNL-1320-S2RP board and the reader. Refer to Reader Wiring on
page 116 and the reader installation manual.
4. Make sure the connectors are firmly seated in TB1 (Reader Port 1) and TB3 (Reader Port 2) on the
LNL-1320-S2RP board.
Problem: The reader has power, but the Status LEDs 1 (Reader Port 1) and 2 (Reader Port 2) on the
LNL-1320-S2RP do not flash at all (no reader activity).
Resolution:
1. Make sure that the resistor packs are installed and are the correct value for the reader type being used.
2. Make sure that the DIP switch settings on the LNL-1320-S2RP for address and reader technology/
format are correct. Refer to Setting the Device Address and Baud Rate on page 113.
3. Check the wiring between the reader and the LNL-1320-S2RP. Refer to Reader Wiring on page 116 and
the reader installation manual.
1. Check the wiring between the LNL-1380-8RP board and the reader. Refer to Wiring on page 161 and
the reader installation manual.
2. Make sure the connectors are firmly seated in the terminal block for the affected reader on the
LNL-1380-8RP board.
Problem: The reader has power, but Status LED 3 on the LNL-1380-8RP do not flash at all (no reader
activity).
Resolution:
1. Make sure that the DIP switch settings on the LNL-1380-8RP for address and reader technology/format
are correct. Setting the Device Address and Baud Rate on page 159.
2. Check the wiring between the reader and the LNL-1380-8RP. Refer to Wiring on page 161 and the
reader installation manual.
Problem: The door reader LED lights on the reader, but the door strike does not operate.
Resolution:
1. Check the wiring from the door strike to the reader board. Also refer to the door strike manufacturer’s
installation instructions.
revision 7 — 25
Hardware Installation Guidelines
For assistance installing, operating, maintaining, and troubleshooting this product, refer to this document
and any other documentation provided. If you still have questions, contact Lenel Technical Support during
normal business hours (Monday through Friday, excluding holidays, between 8:30 a.m. and 5:30 p.m.,
Eastern Time).
Please be ready at the equipment before calling for technical support.
• Toll Free: 866-788-5095
• Fax Line: +1 585-248-9185
• Email: tech@lenel.com
• Web site: www.lenel.com
26 — revision 7
M Series Installation Guide
5 UL Certified Installations
The system is to be installed within a protected premise. In a subassembly, the operating temperature range
must be 0° to 49°C (32° to 120°F); the humidity range must be 0 to 85% RH.
This system must be installed in accordance with the National Electrical Code (NFPA 70), and the local
authority having jurisdiction.
For UL Installations, the central supervisory station equipment must be UL Listed to:
• Information Technology Equipment, UL 60950
For UL Installations, use UL Listed information technology equipment. The computer minimum platform
requirements are as follows:
• Intel Pentium 4 dual core processor
• 3.4 GHz clock speed
• 4 GB RAM
• 6 GB of hard drive space for OnGuard
• DVD-ROM drive
• One (1) USB port
• Operating systems:
- Windows Server 2012 R2
- Windows Server 2012
- Windows 8/Windows 8.1
- Windows 7 SP1
• Database systems:
- Microsoft SQL Server 2014 (32 and 64-bit) and Express
- Microsoft SQL Server 2012 SP1 (32 and 64-bit), or SQL 2012 Express
- Oracle 12cR1 Server 64-bit (12.1.0.1) with 32-bit Client installed if OnGuard is running on the
same server as the database
• Access control/proprietary burglary systems:
- OnGuard 7.x (7.x.xxx) using DOC-1042-EN-US M Series Installation Guide
• The LNL-3300-M5 ISC must have firmware version 1.2xx or later installed
Refer to the release notes for the supported firmware versions. The release notes are located on the root
directory of the OnGuard installation disc.
• NEC ExpressCluster X R3 Fault Tolerant software
Equipment must be installed in a temperature controlled environment, maintained between 0° and 49°C (32°
and 120°F) by the HVAC system. 24 hours of standby must be provided for the HVAC system.
HVAC rated modules were not evaluated by UL for Lenel OnGuard UL1076 product Listing.
revision 7 — 27
Hardware Installation Guidelines
In addition to the main power supply and secondary power supply that are required to be provided at the
central supervisory station, the system must be provided with an uninterruptable power supply (UPS) with
sufficient capacity to operate the computer equipment for a minimum of 15 minutes. If more than 15 minutes
is required for the secondary power supply to supply the UPS input power, the UPS must be capable of
providing input power for at least that amount of time. A means for disconnecting the input to the UPS while
maintaining continuity of power to the automation system must be provided, in order to perform
maintenance and repair service.
The UPS must comply with the Standard for Uninterruptable Power Supply Equipment, UL1778 or the
Standard for Fire Protective Signaling Devices, UL1481.
Be sure to use the recommended cabling, which is the shielded wiring required for use on all modules.
Communication circuits and network components connected to the telecommunications network shall be
protected by secondary protectors for communication circuits. These protectors shall comply with the
Standard for Secondary Protectors or Communications Circuits, UL 497A. These protectors shall be used
only in the protected side of the telecommunications network.
A metal conduit must be used when connecting all UL enclosures. This is required for all UL installations.
Do not exceed 1000 receiver accounts for UL.
All receiving equipment shall be completely duplicated with provision for switchover to the backup system
within 30 seconds. The backup system shall be fully operational within 6 minutes of the loss of the primary
system. This allows 30 seconds for the backup system to be fully energized and connected to the necessary
communication lines and other devices, followed by 5-1/2 minutes for the system to boot up, conduct
memory tests, file system check, security verifications, and prepare for full system operation. The backup
computer must have the capabilities of the primary, such as memory, speed, and the like.
Failure of the main computer system, hard disk, and alarm monitor must be programmed to switchover to
the backup system, and indicate an audible, or obvious visual indication.
A fault tolerant system may be used in lieu of complete duplication of the system if every component in the
fault tolerant system, including the software and power supply, is duplicated.
All OnGuard system solutions that are to be UL1076 compliant systems must also meet the requirements
specified in Section 25A of the UL1076 (Proprietary Burglar Alarm Units and Systems Standard for Safety).
This requirement outlines the need for host monitoring redundancy. Host monitoring redundancy can be
accomplished in many ways, but the standard is clear as to receiving equipment methods, recovery time,
surge suppression and system configurations. Contact Lenel if configuration assistance is required.
Priority features (alarm, loss of line voltage, opens, shorts, etc.) must be programmed for an audio and a
visual indication at the central supervisory station equipment, and to create a printout. The condition must be
recorded. This indication shall not be silenced without acknowledgment.
Bypass of protective features, such as auto-bypass for forced arm, must not be programmed for UL. The
Ethernet connection must be maintained continuously.
Use Marking - Commercial, Proprietary, Multiplex, Encrypted Line Security Burglar Alarm System Control
Unit and Access Control Unit.
28 — revision 7
M Series Installation Guide
Lenel AES Firmware is embedded (installed) in the LNL-3300-M5 (firmware version 1.2xx) for suitability
as "Encrypted Line Security Equipment." (Refer to the release notes for the supported firmware versions.
The release notes are located on the root directory of the OnGuard installation disc.)
Note: If the central supervisory station receives a "Communication Loss" message, a compromise
attempt on the communication line may have occurred.
Network addressing of devices shall not make use of public domain name servers.
5.1 Power
The standby power system for the HVAC system may be supplied by an engine-driven generator alone. Use
of a standby battery is not required.
All external interconnecting power sources must be UL Listed access control/proprietary burglar power
limited power supplies. AC supply lines shall not be routed in the same conduit or harness as low voltage
lines.
For the UL certification, the power supply that must be used is the LNL-AL400ULX or LNL-AL600ULX-
4CB6 with additional hardware mounted in LNL-CTX or LNL-CTX-6 enclosures. Other power supplies
will be certified for use at a future date.
For the ULC Certification, hardware must be mounted in an LNL-CTX or LNL-CTX-6 enclosure. All power
supplies must be UL, ULC, or cUL Listed for security applications, and power-limited.
Output 4 hr. of Stand-by & 24 hr. of Stand-by & 5 60 hr. of Stand-by &
5 minutes of Alarm Minutes of Alarm 5 Minutes of Alarm
M3000 12 VDC/ Stand-by = 4.0 amps Stand-by = 1.0 amp Stand-by = 300 mA
12 AH Alarm = 4.0 amps Alarm = 4.0 amps Alarm = 4.0 amps
Battery
M-5 UTC 12 VDC/ Stand-by = 6.0 amps Stand-by = 1.0 amp Stand-by = 300 mA
F&S 7 or 12 AH Alarm = 6.0 amps Alarm = 6.0 amps Alarm = 6.0 amps
PS/C-6 or Battery
AL400UL
The following combinations must be used in a UL type installation with OnGuard 7.x or later, which are
approved for use. For UL certification, a UL Listed power supply and one of the following enclosures must
be used:
revision 7 — 29
Hardware Installation Guidelines
• M/5
• M/5-E
• M/5-P
• M5-PX
• M/5-PXN
• M/5-PXNplus
• Micro5
• Micro5-E
• Micro5-P
• Micro5-PX
• Micro5-PXN
• Micro5-PXNplus
• Mirco/5
• Micro/5-E
• Micro/5-P
• Micro/5-PX
• Micro/5-PXN
• Micro/5-PXN
• Micro/5-PXNplus
• M5
• M5-E
• M5-P
• M5-PX
• M5-PX
• M5-PXN
• M5-PXNplus
• M3000
• M3000-PXNplus
• M3PPMSP
• M3PPMSP-DN
• M3PPMPP
Multiple combinations of Lenel access hardware can be used within the UL approved enclosure.
The minimum configuration for the M Series consists of a UL approved enclosure and the LNL-3300-M5
ISC.
For proprietary burglar alarm applications, the LNL-1100-20DI Input Control Module is required. For
access control applications, one of the following is required:
30 — revision 7
M Series Installation Guide
All card readers must be evaluated by UL, must be ULC or cUL Listed, and be Wiegand compatible.
To comply with UL, use only the following compatible card readers with the LNL-3300-M5 ISC:
• 940
• 941
• 970
• 971
• 972
• 973
• 430/435
• 1000/1010
Up to 128-bit format.
revision 7 — 31
Hardware Installation Guidelines
• The enclosure tamper switch must be connected to the LNL-3300-M5 ISC as shown in Input Power,
Enclosure Tamper, and Power Fault Input Wiring on page 46.
• The exit request input circuit and initiating device must be contained within the secured area. The exit
device circuit must be connected to listed switches or exit devices.
• The door strike power must be provided from a listed burglar alarm system power supply. If the door
strike circuit is arranged as fail secure (door remains locked upon loss of power), listed emergency
panic hardware must be provided to allow exit from the secured area. A fail-safe configuration results in
the door strike circuit unlocking in case of a power loss.
• Alarms in OnGuard must be set using the following priority list, with 1 being the highest priority and 7
being the lowest:
- 1 = Fire alarm and industrial supervision
- 2 = Hold-up or panic alarm
- 3 = Burglar alarm
- 4 = Watchman or guard tour
- 5 = Fire-alarm supervision
- 6 = Burglar-alarm supervision
- 7 = Industrial supervision
• The number of separate signals on a single channel must be limited to 1000.
32 — revision 7
LNL-3300-M5
INTELLIGENT
SYSTEM
CONTROLLER
M Series Installation Guide
The LNL-3300-M5 is an Intelligent System Controller (ISC) that provides real-time processing for the I/O
interfaces connected to it. The database for the subsystem configuration and card holders are stored in flash
memory. The event log buffer is stored in battery-backed memory.
The LNL-3300-M5 communicates with the host via on-board 10-BaseT/100Base-TX Ethernet port. The
alternate host communication port is an optional 10-BaseT/100Base-TX Ethernet port using a Lantronix
Micro125 interface daughter board, p/n MO11AA003-01R, or equivalent. The I/O modules are connected
via an internal communication bus. Downstream enclosures are communicated to by means of a 2-wire
RS-485 interface (TB-2).
revision 7 — 35
LNL-3300-M5 Intelligent System Controller
LNL-3300-M5 Board
S2
11
4 3 2 1 S1
1
ON
10
1
2
3
4
5
6
9
J4
TB2
1
GND
TR-
TR+
3
2
J6
8
3
J1
7
J7
BR/CR2325
BR/CR2330
TB1
VIN
BT1
GND
VIN
GND
6 VIN
GND
5
TMPR
PFLT
8
Callout Description
9 Status LEDs
36 — revision 7
M Series Installation Guide
Callout Description
10 DIP switches
11 Reset switch
6.2.1 Overview
With firmware version 1.194 or later, security enhancements were made regarding the default login account.
These enhancements restrict the conditions in which the default login account is enabled, exposing the Lenel
controllers to unauthorized access.
Since the credentials (user name and password) for default login account are well-known and are the same
on all of the controllers, it is important to reduce the possibility that the default login account is left enabled
on controllers at customer sites.
Note: Ensure at least one user-defined account exists on the controller prior to updating to version
1.194 or later. Doing so eliminates the need to visit the controller and toggling DIP SW1 to
enable the default login account.
revision 7 — 37
LNL-3300-M5 Intelligent System Controller
• A user-defined account cannot be assigned “password” as its password (cannot be the same as the
password for the default login account)
• An error message appears if the credentials for the default login account are used when the credentials
are not valid (see Error/Warning Messages on page 3 for details.)
• A warning message appears if the default login account is successfully logged into and no user-defined
accounts have been created yet (see Error/Warning Messages on page 3 for details.)
• When attempting to log out or apply settings to the controller, two checks are now made:
- If the DIP switches are set to the normal operating mode
- If at least one user-defined account has been created
If either check fails, an appropriate error message appears. (see Error/Warning Messages, on page 38 for
details.)
Note: The following screens were generated using the LNL-3300 ISC. These screens are similar to
those generated by other controllers.
The Login Failed screen appears if you attempt to log in using the credentials for the default login account
and DIP SW1 is in the OFF position.
The Login Failed screen also appears if you attempt to log in using the credentials for the default login
account and DIP SW1 is in the ON position, but the 5-minute login time window has expired.
38 — revision 7
M Series Installation Guide
The No User-defined Accounts screen appears when you successfully log into the controller, but no user-
defined accounts are detected.
No User-defined Accounts
revision 7 — 39
LNL-3300-M5 Intelligent System Controller
When logging out, if either logout check (DIP switch settings or user-defined account) fails, the
Configuration Manager screen appears.
Configuration Manager
If either, or both, condition exists, you must acknowledge the appropriate warning by checking the box next
to I understand and wish to proceed before the Yes button under Do you wish to proceed? is enabled.
40 — revision 7
M Series Installation Guide
Install jumper J4 to terminate the 2-wire RS485 communication bus on TB2. Only terminate the units at
each end of the communication bus. For more information, refer to Communication Wiring on page 45.
Use the four S1 DIP switches to configure the operating mode for the LNL-3300-M5. DIP switches are read
on power-up (except where noted).
1 2 3 4 Definition
X X ON X Disable TLS secure link. Switch only reads when logging on.
ON ON OFF OFF Bulk Erase prompt mode at power up. For more information, refer
to Bulk Erase Function on page 51.
All other switch settings are unassigned and reserved for future use. X = Not applicable/not used.
Notes: In factory/OEM modes, the downloaded configuration/database is not saved to flash memory.
The following are factory default communication parameters:
Network: Static IP Address: 192.168.0.251
Gateway Mask: 255.255.255.0
Communication Address: 0
Primary Host Port: IP server, no data security, Port 3001
Alternate Host Port: Disabled
revision 7 — 41
LNL-3300-M5 Intelligent System Controller
Unless otherwise stated, use the following information to configure the LNL-3300-M5 for dual network
card interface (NIC) operation.
The ETHLAN-LITE/ETHLAN-MICR device plugs directly onto the LNL-3300-M5 panel and provides the
ability to configure the controller for dual NIC operation.
The standoffs for the ETHLAN-LITE/ETHLAN-MICR come in a separate package. The following diagram
illustrates the positioning.
INSERT
STANDOFFS
HERE
DO NOT DISPOSE
[Qty 3]
42 — revision 7
M Series Installation Guide
1. At the command prompt, type ARP-A to verify that there is at least one entry in the ARP table. If there
is at least one entry, proceed to Step 3.
2. If there is no other entry listed in the ARP table besides the local machine, ping another IP machine on
the network to build the ARP table. You must ping a host other than the machine on which you are
working.
3. After the entry is listed in the ARP table, use the following command to ARP the IP address:
arp -s <IP Address> <Ethernet/Hardware Address>
where the <IP address> is the numerical address (example: 192.168.002.203) and the
<Ethernet/Hardware Address> is the address labeled on the Micro Serial Server device
(example: 00-80-a3-2b-02-3b).
Note: The ARP/ping method only works during the first two minutes of LNL-ETHLAN-MICR
operation. If this process is not completed in time, then the LNL-ETHLAN-MICR must be
rebooted and the ARP/ping process redone.
4. Ping the IP address to have the device acknowledge the IP assignment. There should be replies from the
IP address if the ARP command was accepted.
Note: The ETHLAN-MICR will not save this learned IP address permanently; this procedure is
intended as a temporary measure to allow an administrator to Telnet into the LNL-ETHLAN-
MICR for configuration. Once the power is recycled on the device, the IP programming that is
done with the arp command will be lost.
After doing this, telnet into the IP address to complete the rest of the device configuration. For more
information, refer to Establish Network Communication on page 44.
Note: BOOTP and RARP are disabled using commands when configuring the device for use. DHCP
is disabled when the device is shipped from Lenel. However, if an NVR reset is performed on
the device, DHCP, BOOTP, and RARP will all be re-enabled and if there is a DHCP server on
the network the unit will obtain an IP address automatically and you will not be able to use the
ARP command for programming. If there is no DHCP server on the network, the DHCP option
revision 7 — 43
LNL-3300-M5 Intelligent System Controller
within the device will be disabled again once a static IP address is successfully programmed
into the device.
5. Remove all power from the LNL-3300-M5 for at least 15 seconds and then reapply power.
6. Use the access control software to define the LNL-3300-M5 as a LAN panel at the IP address that was
assigned. The panel will come online.
44 — revision 7
M Series Installation Guide
9 Wiring
The LNL-3300-M5 communicates to the host via: on-board Ethernet 10-BaseT/100Base-TX port and/or the
optional Lantronix Ethernet 10-BaseT/100Base-TX Micro125 interface.
TB2 is a 2-wire RS-485 interface that communicates to downstream controllers via the LNL-8000-MCOM
(installed in downstream M5 enclosures). This interface allows multi-drop communication on a single bus of
up to 4,000 feet (1,200 m). Use shielded twisted pair (minimum 24 AWG) cable with 120 ohm impedance.
Notes: Install termination jumper, J4, only on the units at each end of the RS-485 communication line.
Install the termination jumper ONLY on the panel at each end of the RS-485 line. Failure to do
so will compromise the communication channel.
Communication Wiring
2 3
TB2
GND 1
1
TR-
TR+ 3
Callout Description
1 Shield
2 Drain wire
revision 7 — 45
LNL-3300-M5 Intelligent System Controller
9.2 Input Power, Enclosure Tamper, and Power Fault Input Wiring
The LNL-3300-M5 requires 12 VDC power, 3 A minimum. Depending on system configuration, a larger
power supply may be required.
There are three pairs of connections for power, all are in parallel. If needed, the other two pairs can supply
power to other I/O boards.
Connect the incoming +12 VDC power to TB1-3, and ground (12 VDC return) to TB1-4. Locate power
source as close to the unit as possible. Connect power with minimum 18 gauge wire.
TB1
1
VIN
GND
+ 3
VIN 3
1
GND 4
- 4
VIN
GND
5 TMPR
PFLT 8
Figure Input Power, Enclosure Tamper, and Power Fault Input Wiring Callouts
Callout Description
Notes: Connect the GND signal to earth ground in one location within the system. Multiple earth
ground connections can cause ground loop problems and are not recommended.
Observe polarity on 12 VDC input.
There are two dedicated inputs for cabinet tamper (TMPR) and UPS fault monitoring (PFLT). Normal (safe)
condition is a closed contact. If these inputs are not used, install a jumper wire.
46 — revision 7
M Series Installation Guide
10 Configuration
To configure the LNL-3300-M5 ISC, use the embedded web configuration page to complete basic
configuration, such as:
• Communication address
• Connection type
• Data security
• Port number
• User accounts
For more advanced configuration options, use a host application, such as the OnGuard software.
Notes: After configuring the LNL-3300-M5 using the web interface, make sure to place DIP switch
SW1 in the OFF position to enable the settings made.
All boards have a static certificate that reflects a static IP address. This causes a warning to
initially appear when trying to log in that states a problem with this website’s security
certificate. Although it is not recommended, proceed to the website.
revision 7 — 47
LNL-3300-M5 Intelligent System Controller
1. In System Administration, open Access Folders and select the LNL-3300-M5 tab.
2. Click [Configuration Web Page].
The configuration web page launches in a browser.
You may also access the configuration web page by going to the device IP address from within the
browser.
3. Click the link to the Login page. Log in using your user name and password. For more information,
refer to Default Login Security Enhancements on page 37.
4. The Home page indicates the type of device and has a Notes field. Enter a description here and click
[Save Notes].
5. To configure network settings, click [Network].
• If you are using DHCP, specify a host name.
By default, the host name consists of “MAC” followed by the numbers of the device MAC address.
With DHCP, IP settings will be automatically configured.
• For a static IP address, specify the IP address, subnet mask, and default gateway.
6. Click [Accept].
7. To configure the host, click [Host Comm].
a. Specify the controller’s communication address. This is the address used for RS-485, also must
match the setting in the access control software, even for IP communications.
b. Configure the following:
– Connection Type: Choose from IP Server, Serial-RS232, Serial-modem, Serial-RS485
(LNL-3300-M5 only) and Serial-Cobox (LNL-3300-M5 only). Currently, the IP Client
connection type is not supported.
– Data Security: The controller is capable of Password/AES encryption.
– Port Number (default 3001): Must match setting in the access control software.
When using an IP Server connection, the controller may be configured to allow all IP addresses or only
authorized IP addresses.
c. Configure an alternate host port if needed. Dual path communication is available on the
LNL-3300-M5 only. If you opt not to use dual path communication, set this option to Disabled.
d. Click [Accept].
8. To view information, click [Device Info].
You may view the time and product ID, as well as properties that have been configured, such as
firmware version, serial number, device name, DIP switches, etc.
9. To configure user accounts, click [Users].
User accounts may be created, edited, or deleted. Each user account has an associated user name and
password, as well as a level and notes.
a. One of three different levels may be assigned to users. Level 1 provides full control. For Levels 2
and 3, refer to the following table.
48 — revision 7
M Series Installation Guide
For pages that cannot be viewed, the message is displayed when users attempt to access the page:
“This page is unavailable due to one of the following reasons: your user level is not authorized to
view this page, or another level 1 user is logged in at this time.”
b. Select the password strength.
– Low: The minimum password length must be six characters. None of the password strength
criteria will be enforced.
– Medium: The minimum password length must be six characters. Two of the password strength
criteria must be met.
– High: The minimum password length is eight characters. Three of the password strength
criteria must be met. Additionally, strong passwords are checked to make sure that they are not
based on the user name.
Password strength criteria:
– Uppercase alphabet characters
– Lowercase alphabet characters
– Arabic numerals (0-9)
– Non alphanumeric characters ` ! ? $ ^ * ( ) _ - + = { [ } ] : ; @ ~ # | < , > . ? /
Characters " , \, &, = and % are invalid characters and cannot be used for passwords.
c. Specify the Session Timer (5 to 60 minutes). Click [Save].
d. You may disable the web server by selecting the check box. When this option is selected and DIP
switch SW1 is off, all ports except for the host communication port are disabled. The configuration
web page cannot be used to access the device.
e. Select the Enable door forced open filter check box if you do not want a forced open alarm if the
door is opened within three seconds of it being closed.
10. For configuration of auto-save, click [Auto-Save].
a. On this page, you may restore the last save or clear all the settings.
b. Choose to disable or enable Auto-Save.
revision 7 — 49
LNL-3300-M5 Intelligent System Controller
If Auto-Save is enabled, volatile memory is written to flash. The frequency of this action is
specified in the timer (30 seconds to 30 minutes). Click [Save Settings].
11. You may click [Restore/Default] if you need to reload the factory settings or the current operating
settings.
12. When you have completed configuring the device, click [Apply Settings], [Apply Settings, Reboot], and
then [Log Out]. If the IP address has changed, you will need to log in with the new IP address to
continue.
Set up this controller as you would any other controller by using the LNL-3300-M5 Form in the Access
Panels folder. The Access Panels folder is located in System Administration.
Complete the form and its tabs as applicable for the installation site.
50 — revision 7
M Series Installation Guide
11 Other Functions
A lithium backup battery powers the static RAM and the real time clock when input power is removed. This
battery should be replaced annually.
The LNL-3300-M5 is typically shipped with an insulator installed between the battery holder and the
battery. Remove the insulator from the battery holder after installation. Reinstall the insulator if the
LNL-3300-M5 will be stored for a long period of time.
Use battery types BR2325, CR2325, BR2330, or CR2330.
Note: If data in the static RAM is determined to be corrupt after power up, all downloaded
configuration database is considered invalid and is erased. All configuration data must be re-
downloaded.
Note: If clearing the memory does not correct the initialization problem, contact Technical Support.
revision 7 — 51
LNL-3300-M5 Intelligent System Controller
12 Status LEDs
Note: Do not cycle power while data is written to, or read from, the flash memory.
LED Description
5 Unassigned
6 Unassigned
52 — revision 7
M Series Installation Guide
13 Specifications
The LNL-3300-M5 is intended for use in low voltage, Class 2 circuits only.
The following specifications are subject to change without notice.
• Primary Power: 12 VDC, ± 10%, 330 mA maximum (does not include other I/O modules connected to
the backplane)
• Memory and Clock Backup: 3 Volt Lithium, type BR2325, CR2325, BR2330, or CR2330
• Host:
- Primary: Onboard 10-BaseT/100Base-TX Ethernet
- Alternate: Optional 10-BaseT/100Base-TX using a Lantronix Micro125 Serial-to-Ethernet
interface daughter board, p/n MO11AA003-01R, or equivalent
• Internal: Communication to M5 I/O boards: 9,600 to 115,200 bps, asynchronous
• External:
- TB2: 2-wire RS-485 to downstream controller enclosures
- 9600, 19200, 38400, or 115200 bps, asynchronous
• Inputs: Two (2) non-supervised, dedicated for cabinet tamper and power fault monitoring
• Cable Requirements:
- Power: One (1) twisted pair, 18 AWG
- RS-485: 24 AWG, 4,000 ft (1,200 m) maximum, shielded twisted pair, 120 ohm impedance
- Ethernet: Cat 5 minimum
- Alarm Input: One (1) twisted pair, 30 ohms maximum loop resistance
• Environmental:
- Storage Temperature: -67 to +185°F (-55 to +85°C)
- Operating Temperature: +32 to +158°F (0 to +70°C)
- Humidity: 5 to 95% RHNC
• Mechanical:
- Width: 4.56 in. (115.8 mm)
- Length: 10.25 in. (260.4 mm)
- Height: 0.8 in. (20.3 mm)
- Weight (without connectors): 5.3 oz. (150 g) nominal
The following specifications apply to the LNL-3300-M5 with the Lantronix Serial-to-Ethernet Module:
• Mechanical:
- Width: 4.56 in. (115.8 mm)
- Length: 10.25 in. (260.4 mm)
- Height: 1.27 in. (32.26 mm)
- Weight (without connectors): 6.2 oz. (175 g) nominal
• Lantronix Serial-to-Ethernet Module Support:
- Standoff size: Diameter 125 inch x 7/16 inch long
- Supplier: Richco, Inc. part number LMSP-7-01, 3 pieces (not supplied)
revision 7 — 53
LNL-3300-M5 Intelligent System Controller
54 — revision 7
LNL-1100-20DI
INPUT CONTROL
MODULE
M Series Installation Guide
The LNL-1100-20DI is an Input Control Module that provides sensor monitoring via twenty (20) digital
inputs that can be configured to support unsupervised or supervised alarm input circuits.
The LNL-1100-20DI includes two (2) processors, each monitoring ten input circuits. The first processor (A)
monitors inputs 1IN through 10IN. The second processor (B) monitors inputs 11IN through 20IN. This
board occupies two consecutive addresses on the communication bus.
1
1IN
1IN
TB1
2IN
2IN
3IN
3IN
4IN
4IN
5IN
5IN
10
5 1
1
6IN
6IN
TB2
7IN
7IN
8IN
8IN
9IN
9IN
10IN
10IN 2
10
A1
A2
A3
A4
B1
B2
B3
3
B4
1
11IN
11IN
TB3
12IN
12IN
13IN
8 7 6 5 4 3 2 1
S1
13IN
14IN ON
14IN
15IN
15IN
10
4
1
16IN
16IN
TB4
17IN
17IN
18IN
18IN
19IN
19IN
20IN
20IN
10
Callout Description
1 Status LEDs
3 S1 DIP switches
revision 7 — 57
LNL-1100-20DI Input Control Module
Callout Description
58 — revision 7
M Series Installation Guide
Use the on-board DIP switches to set the device address and communication baud rate on the
LNL-1100-20DI.
• Switches 1 to 5 are used to select the communication address for the first processor (A). The second
processor (B) is assigned the next address value.
• Switches 6 and 7 are used to select the communication baud rate.
Note: Currently, OnGuard only supports a baud rate of 38,4000 bps. Be sure to set both DIP switches
6 and 7 to the ON position.
Selection S8 S7 S6 S5 S4 S3 S2 S1
Address 15 OFF ON ON ON ON
revision 7 — 59
LNL-1100-20DI Input Control Module
Selection S8 S7 S6 S5 S4 S3 S2 S1
Address 23 ON OFF ON ON ON
Address 27 ON ON OFF ON ON
Address 29 ON ON ON OFF ON
Address 30 ON ON ON ON OFF
38,400 bps ON ON
60 — revision 7
M Series Installation Guide
Typically, these inputs are used to monitor door position, request to exit, or alarm contacts. Input circuits can
be configured as unsupervised or supervised. When unsupervised, reporting consists of only the open or
closed states.
When an input circuit is configured for supervision, the LNL-1100-20DI also monitors the following
abnormal circuit conditions:
• open circuit,
• shorted circuit,
• grounding of either side of the circuit*
• the introduction of a foreign voltage*
* Grounded and foreign voltage states are not UL 294 required and therefore not verified by UL.
A supervised input circuit requires adding two resistors to the circuit to facilitate proper reporting. The
standard supervised circuit requires 1K Ohm, 1% resistors and should be located as close to the sensor as
possible. Custom end of line (EOL) resistances may be configured via the host software.
The input circuit wiring configurations shown are supported, but may not be typical.
revision 7 — 61
LNL-1100-20DI Input Control Module
5
1K,1%
1
1
1K,1%
1K,1%
2
1K,1%
10
4
Callout Description
62 — revision 7
M Series Installation Guide
17 Status LEDs
revision 7 — 63
LNL-1100-20DI Input Control Module
18 Specifications
The LNL-1100-20DI is intended for use in low voltage, Class 2 circuits only.
64 — revision 7
LNL-1200-16DO
OUTPUT CONTROL
MODULE
M Series Installation Guide
The LNL-1200-16DO is an Output Control Module that provides digital output control via sixteen (16) open
collector outputs rated at 40 mA maximum per output. An external DC power source is required for the
digital outputs, 24 VDC maximum. The external DC power source is common to all outputs.
D8
D7
D9
TB1
D10
1
+VDC
DO-1
+VDC
DO-2
+VDC
DO-3
+VDC
1
8
DO-4
D12
D11
TB2 D13
D14
1
+VDC
DO-5
+VDC
DO-6
+VDC
DO-7
+VDC
DO-8
8
2
1
2
3
4
1
+VDC
DO-9
+VDC
DO-10
+VDC
3
DO-11
+VDC
8
DO-12
TB3
D16 4
D15
TB4 D17
D17
1
+VDC
DO-13
+VDC
DO-14
+VDC 5
DO-15
+VDC ON
S1
8
DO-16
D20
D19
1
2
3
4
5
6
7
8
TB5 D5
D6
DC IN
GND
revision 7 — 67
LNL-1200-16DO Output Control Module
3 Status LEDs
5 DIP switches
68 — revision 7
M Series Installation Guide
Use the on-board DIP switches to set the device address and communication baud rate on the
LNL-1200-16DO.
• Switches 1 to 5 select the device address.
• Switches 6 and 7 select the communication baud rate.
Note: Currently, OnGuard only supports a baud rate of 38,4000 bps. Be sure to set both DIP Switches
6 and 7 to the ON position.
Selection S1 S2 S3 S4 S5 S6 S7 S8
Address 15 ON ON ON ON OFF
revision 7 — 69
LNL-1200-16DO Output Control Module
Selection S1 S2 S3 S4 S5 S6 S7 S8
Address 23 ON ON ON OFF ON
Address 27 ON ON OFF ON ON
Address 29 ON OFF ON ON ON
Address 30 OFF ON ON ON ON
Address 31 ON ON ON ON ON
38,400 bps ON ON
70 — revision 7
M Series Installation Guide
For typical use of the digital output, refer to the figure below. The open collector output drives an external
relay, which in turn drives an output device.
Note: Inductive load (relay or strike) switching causes EMI (electromagnetic interference) that can
interfere with normal operation of other equipment. To minimize premature contact failure and
to increase system reliability, use a contact protection circuit. Locate the protection circuit as
close to the load as possible (12 inches [30cm] recommended). The circuit's effectiveness
decreases if it is located further away.
5 8
2
1 +
TB1
3 7
1
1
4
+VDC
DO-1
2
+VDC
DO-2
6 +VDC
6 DO-3
+VDC
DO-4
3
TB5
+
1
DC IN
9 -
GND
2
Callout Description
1 Output device
2 To DC power source
3 Fuse
4 External relay
revision 7 — 71
LNL-1200-16DO Output Control Module
Callout Description
72 — revision 7
M Series Installation Guide
22 Status LEDs
revision 7 — 73
LNL-1200-16DO Output Control Module
23 Specifications
The LNL-1200-16DO is intended for use in low voltage, Class 2 circuits only.
74 — revision 7
LNL-1200-16DOR
OUTPUT CONTROL
MODULE
M Series Installation Guide
The LNL-1200-16DO is an Output Control Module that provides digital output control via sixteen (16) open
collector outputs rated at 40 mA maximum per output. An external DC power source is required for the
digital outputs, 24 VDC maximum. The external DC power source is common to all outputs.
TB1
1
NC
K1
K1
C
NO
NC
K2
K2
C
NO
K3
C K3
NO
C
K4
K4
NO
10
1
NC
K5
K5
NO
NC
K6
K6
NO
C
K7
K7
NO
C
1
K8
K8
NO
10
TB2
1
2
3
4
TB3
1
NC
K9
K9
NO
K10
NC
K10
C
16DOR
NO 2
K11
C
K11
NO
K12
C
K12
NO
10
3
1
NC
K13
K13
NO
K14
NC
K14
C ON
1
2
3
4
5
6
7
8
NO
S1
K15
C
K15
NO
C
K16
K16
NO
10
TB4
2 Status LEDs
revision 7 — 77
LNL-1200-16DOR Output Control Module
3 DIP switches
78 — revision 7
M Series Installation Guide
Use the on-board DIP switches to set the device address and communication baud rate on the
LNL-1200-16DOR.
• Switches 1 to 5 select the device address.
• Switches 6 and 7 select the communication baud rate.
Note: Currently, OnGuard only supports a baud rate of 38,4000 bps. Be sure to set both DIP Switches
6 and 7 to the ON position.
Selection S1 S2 S3 S4 S5 S6 S7 S8
Address 15 ON ON ON ON OFF
revision 7 — 79
LNL-1200-16DOR Output Control Module
Selection S1 S2 S3 S4 S5 S6 S7 S8
Address 23 ON ON ON OFF ON
Address 27 ON ON OFF ON ON
Address 29 ON OFF ON ON ON
Address 30 OFF ON ON ON ON
Address 31 ON ON ON ON ON
38,400 bps ON ON
80 — revision 7
M Series Installation Guide
Eight (8) Form-C and eight Form-A contact relays control door lock mechanisms or alarm signaling devices.
The relay contacts are rated at 2 A @ 30 VAC/DC, dry contact configuration.
When controlling power to the door strike, the Normally Open and Common poles are used. When
momentarily removing power to unlock the door, as with a magnetic lock, the Normally Closed and
Common poles are used. If the relay does not have a Normally Closed pole, the relay must be configured by
the host to be energized when in the locked state. Check with local building codes for proper egress door
installation.
Note: Excessive load switching causes contact wear and premature failure. Inductive load (strike)
switching causes EMI (electromagnetic interference) which may interfere with normal
operation of other equipment. To minimize premature contact failure and to increase system
reliability, use a contact protection circuit. Locate the protection circuit as close to the load as
possible [12 inches (30cm) recommended]. The circuit’s effectiveness decreases if it is located
further away.
Use a sufficiently large gauge wire to avoid voltage loss on the load current.
revision 7 — 81
LNL-1200-16DOR Output Control Module
1 2
4
TB1
3
NC K1
NO
NC
K2
NO
C
K3
5
NO
C
K4
NO
10
Callout Description
1 DC strike
2 To DC power source
82 — revision 7
M Series Installation Guide
Callout Description
3 Fuse
4 TB1 on LNL-1200-16DOR
1 2
TB1
1
3 NC
K1
C
NO
NC
K2
C
NO
K3
5
NO
NO K4
10
Callout Description
1 AC strike
2 To AC power source
3 Fuse
4 TB1 on LNL-1200-16DOR
revision 7 — 83
LNL-1200-16DOR Output Control Module
27 Status LEDs
84 — revision 7
M Series Installation Guide
28 Specifications
The LNL-1200-16DOR is intended for use in low voltage, Class 2 circuits only.
revision 7 — 85
LNL-1200-16DOR Output Control Module
86 — revision 7
LNL-1320-2RP
DUAL DOOR
CONTROL
MODULE
M Series Installation Guide
The LNL-1320-2RP is a Dual Door Control Module that provides two (2) reader interface ports.
The LNL-1320-2RP accepts data from readers with Clock/Data, Wiegand, F/2F, supervised F/2F signaling
and door hardware. The LNL-1320-2RP provides LED status, strike control and reader power of 5 VDC or
12 VDC.
Each of the two reader interface ports provides inputs for door position monitoring and request-to-exit
(REX). The LNL-1320-2RP also has three Form-C relay outputs used for strike control, alarm contact
shunting and auxiliary device control for each reader.
TB1
1
VO
GND
DISP
LED
REX+
WD0
WD1
1
DC+
Not Used
10
6 CLK DO
1
NC
K1
C
K1
NO
C
K2
NC
K2
NO
C
K3
NC
K3
NO
2
9
TB2
J6
+5V
J5
+12V
3 2 1
4
TB3
1
VO
GND
DISP
LED
REX+ 3
WD0
WD1
DC+
Not Used
10
5 CLK DO
1
NC
K4
K4
NO 4
C
K5
K5
NC
NO
C
ON
S1
K6
NC
K6
NO
9
TB4
1
2
3
4
5
6
7
8
revision 7 — 89
LNL-1320-2RP Dual Door Control Module
3 Status LEDs
4 DIP switches
5 Reader Port 2
6 Reader Port 1
90 — revision 7
M Series Installation Guide
30 Configuration
Configuring the LNL-1320-2RP consists of setting the device address and the power selection jumper.
Use the on-board DIP switches to set the device address and communication baud rate on the
LNL-1320-2RP.
• Switches 1 to 5 select the device address.
• Switches 6 and 7 select the communication baud rate.
Note: Currently, OnGuard only supports a baud rate of 38,4000 bps. Be sure to set both DIP Switches
6 and 7 to the ON position.
Selection S1 S2 S3 S4 S5 S6 S7 S8
Address 15 ON ON ON ON OFF
revision 7 — 91
LNL-1320-2RP Dual Door Control Module
Selection S1 S2 S3 S4 S5 S6 S7 S8
Address 23 ON ON ON OFF ON
Address 27 ON ON OFF ON ON
Address 29 ON OFF ON ON ON
Address 30 OFF ON ON ON ON
Address 31 ON ON ON ON ON
38,400 bps ON ON
Power to the reader is selectable: 5 VDC or 12 VDC @ 300 mA maximum per reader port. This selection is
made via jumper J5 and is available for both reader ports. Readers requiring a different voltage or current
capability must be powered separately.
92 — revision 7
M Series Installation Guide
+12V
+5V
1
revision 7 — 93
LNL-1320-2RP Dual Door Control Module
31 Reader Wiring
The reader ports on the LNL-1320-2RP support the following reader types:
• Clock/Data
• Wiegand
• F/2F
• Supervised F/2F
The following are basic reader cable requirements. For more information, refer to Specifications on
page 107.
• F/2F and supervised F/2F readers require a shielded 4-conductor cable.
• Clock/Data and Wiegand readers require a shielded 5-conductor cable.
Wiegand Reader
1 2
TB1
TB3
or
1
1
3 VO
2
4 GND
DISP
4
5 LED
REX+
6
6 WD0
7 WD1
7
DC+
Not Used
10
CLK DO
Callout Description
1 Wiegand reader
94 — revision 7
M Series Installation Guide
Callout Description
Magnetic Reader
1 2
TB1
TB3
or 1
1
3 VO
4 2
GND
DISP
4
5 LED
REX+
6 WD0
6
7 WD1
7
DC+
Not Used
10
CLK DO
Callout Description
1 Magnetic reader
revision 7 — 95
LNL-1320-2RP Dual Door Control Module
F/2F Reader
1 2
TB1
TB3
or
1
1
3 VO
2
4 GND
DISP
4
5 LED
REX+
WD0
7
6 WD1
DC+
Not Used
10
CLK DO
Callout Description
1 F/2F reader
96 — revision 7
M Series Installation Guide
1 2
TB1
TB3
or
1
1
3 VO
2
4 GND
3
5 DISP
4
6 LED
REX+
WD0
7 7 WD1
DC+
8
Not Used
10
CLK DO
Callout Description
Typically, the door position monitor switch uses the Normally Closed (NC) contact and the REX uses the
Normally Open (NO) contact.
For the LNL-1320-2RP, the door position monitor and REX switches can be wired in several different
configurations.
These configurations are downloaded from the host and may be changed.
revision 7 — 97
LNL-1320-2RP Dual Door Control Module
Unsupervised inputs for the door position monitor and REX switches are wired to TB1 for the first reader,
and TB3 for the second reader. End-of-Line (EOL) resistors are not required.
TB1
TB3
2
or
1
VO
2
GND
3
DISP
LED
5
REX+
WD0
WD1
8
DC+
Not Used
10
CLK DO
Callout Description
Unsupervised inputs for the door position monitor and REX switches are wired directly to the F/2F reader
configured for 2-State Supervision. See the reader’s documentation for the proper connection terminals.
End-Of-Line (EOL) resistors are not required.
98 — revision 7
M Series Installation Guide
4
2
5
Callout Description
1 F/2F reader
2 To LNL-1320-2RP
4 Ground connection
6 Data 1 connection
Supervised inputs for the door position monitor and REX switches are wired directly to the F/2F reader
configured for 4-State Supervision: open, closed, short, and cut. See the reader’s documentation for the
proper connection terminals. EOL resistors typically require two 1K ohm resistors as shown in the figure
below. Install the EOL resistors as close to the switch as possible.
revision 7 — 99
LNL-1320-2RP Dual Door Control Module
4
2
5
1K,1%
1K,1%
7
1K,1%
1K,1%
2 To LNL-1320-2RP
4 Ground connection
6 Data 1 connection
There are two options for door strike wiring on the LNL-1320-2RP: internal relay and external relay.
100 — revision 7
M Series Installation Guide
Note: Excessive load switching causes contact wear and premature failure. Inductive load (strike)
switching causes EMI (electromagnetic interference) that can interfere with normal operation
of other equipment. To minimize premature contact failure and to increase system reliability,
use a contact protection circuit. Locate the protection circuit as close to the load as possible
(12 inches [30cm] recommended). The circuit's effectiveness decreases if it is located further
away.
Use sufficiently large gauge wire for the load current to avoid voltage loss.
revision 7 — 101
LNL-1320-2RP Dual Door Control Module
Callout Description
1 AC strike
2 To AC power source
3 Fuse
5 Suppression MOV
102 — revision 7
M Series Installation Guide
1 DC strike
2 To DC power source
3 Fuse
5 Suppression diode
Instead of using the on-board relay to control the door strike, an external relay may be used. This external
relay is controlled by the reader LED output.
If the LED in the reader is driven by the Reader LED signal, TB1-4 or TB3-4, a blocking diode must be
added to the circuit. This blocking diode should be a Schottky barrier rectifier, type 1N5817 or equivalent
(20 volt @ 1 A).
- The external relay’s coil current must be restricted to 40 mA.
- The 5 volt relay coil resistance must be 125 or greater ohms.
- The 12 volt relay coil resistance must be 300 or greater ohms.
Note: Excessive load switching causes contact wear and premature failure. Inductive load (strike)
switching causes EMI (electromagnetic interference) that can interfere with normal operation
of other equipment. To minimize premature contact failure and to increase system reliability,
use a contact protection circuit. Locate the protection circuit as close to the load as possible
revision 7 — 103
LNL-1320-2RP Dual Door Control Module
(12 inches [30cm] recommended). The circuit's effectiveness decreases if it is located further
away.
5
1
TB1
TB3
4
or
6 1
1
3
VO
GND
DISP
7 4
LED
8 REX+
11
9 WD0
WD1
DC+
10
Not Used
10
CLK DO
Callout Description
1 AC strike
2 AC transformer
3 Fuse
4 External relay
8 Suppression diode
11 Suppression MOV
104 — revision 7
M Series Installation Guide
5
1 2
4
TB1
1 TB3
or
3 6 1
VO
GND
DISP
7 4
LED
8 REX+
8
WD0
9
WD1
DC+
10
Not Used
10
CLK DO
Callout Description
1 DC strike
2 To DC power source
3 Fuse
4 External relay
8 Suppression diode
revision 7 — 105
LNL-1320-2RP Dual Door Control Module
32 Status LEDs
106 — revision 7
M Series Installation Guide
33 Specifications
• Primary Power (from LNL-3300-M5): 12 VDC, ± 10 %, 155 mA maximum (plus reader current)
• Relay Outputs: 6 outputs, Form-C, 2 A @ 30 VAC/DC, resistive
• Inputs: 4 unsupervised, two per reader port
• Reader Interface:
- Reader Power: 5 VDC or 12 VDC regulated (jumper selectable), 300 mA maximum each reader
port
- Reader LED Output/External Relay: Open collector, 40 mA sink maximum
- Reader Data Input: TTL compatible inputs
- Communication: 9600, 19200, 38400, or 115200 bps, asynchronous
• Cable Requirements:
- Alarm Inputs: 1 twisted pair per input, 22 AWG shielded. 30 ohms maximum loop resistance
- Outputs: As required for the load
- Reader Data: Use shielded cables;
– 5 VDC: 18 AWG, 200 ft. maximum, reader powered by reader processing board
– 12 VDC: 20 AWG, 500 ft. maximum, reader powered by LNL-1320-2RP; 18 AWG, 3000 ft.
maximum, reader powered locally
Notes: The above specifications are based on the typical 12 volt reader drawing 125 mA. Reader
power requirements vary between different models.
Excessive voltage drop on long cable runs may require a larger cable gauge or powering the
reader from a local power source. Refer to the power specification for the reader being
installed.
• Environmental:
- Storage Temperature: -67 to +185°F (-55 to +85°C)
- Operating Temperature: +32 to +158°F (0 to +70°C)
- Humidity: 5 to 95% RHNC
• Mechanical:
- Width: 3.5 in. (88.9 mm)
- Length: 10.25 in. (260.4 mm)
- Height: 0.69 in. (17.5 mm)
- Weight (without connectors): 4.5 oz (126 g) nominal
revision 7 — 107
LNL-1320-2RP Dual Door Control Module
108 — revision 7
LNL-1320-S2RP
DUAL DOOR
CONTROL
MODULE
M Series Installation Guide
The LNL-1320-S2RP is a Dual Door Control Module that provides four (4) supervised inputs
(two per reader interface port).
The LNL-1320-S2RP accepts data from readers with Clock/Data, Wiegand, F/2F, supervised F/2F signaling
and door hardware. The LNL-1320-S2RP provides LED status, strike control and reader power of 5 VDC or
12 VDC.
Each of the two reader interface ports provides inputs for door position monitoring and request-to-exit
(REX). The LNL-1320-S2RP also has three Form-C relay outputs used for strike control, alarm contact
shunting and auxiliary device control for each reader.
VO
GND
DISP
LED
REX+
WD0
WD1
DC+
1
DC-
1 10
6 REX-
NC
K1
C
K1
NO
C
K2
NC
K2
NO
C
K3
NC
K3
NO 2
9
TB2
J6
+5V
4 3 2 1 J5
+12V
TB3
1
VO
GND
DISP
LED
REX+ 3
WD0
WD1
DC+
DC-
1 10
REX-
5
NC
K4
K4
C
NO 4
C
K5
K5
NC
NO
C
ON
S1
K6
K6
NC
NO
9
1
2
3
4
5
6
7
8
TB4
revision 7 — 111
LNL-1320-S2RP Dual Door Control Module
3 Status LEDs
4 DIP switches
5 Reader Port 2
6 Reader Port 1
112 — revision 7
M Series Installation Guide
35 Configuration
Configuring the LNL-1320-S2RP consists of setting the device address and the power selection jumper.
Use the on-board DIP switches to set the device address and communication baud rate on the
LNL-1320-S2RP.
• Switches 1 to 5 select the device address.
• Switches 6 and 7 select the communication baud rate.
Note: Currently, OnGuard only supports a baud rate of 38,4000 bps. Be sure to set both DIP Switches
6 and 7 to the ON position.
Selection S1 S2 S3 S4 S5 S6 S7 S8
Address 15 ON ON ON ON OFF
revision 7 — 113
LNL-1320-S2RP Dual Door Control Module
Selection S1 S2 S3 S4 S5 S6 S7 S8
Address 23 ON ON ON OFF ON
Address 27 ON ON OFF ON ON
Address 29 ON OFF ON ON ON
Address 30 OFF ON ON ON ON
Address 31 ON ON ON ON ON
38,400 bps ON ON
Power to the reader is selectable: 5 VDC or 12 VDC @ 300 mA maximum per reader port. This selection is
made via jumper J5 and is available for both reader ports. Readers requiring a different voltage or current
capability must be powered separately.
114 — revision 7
M Series Installation Guide
+12V
+5V
1
revision 7 — 115
LNL-1320-S2RP Dual Door Control Module
36 Reader Wiring
The reader ports on the LNL-1320-S2RP support the following reader types:
• Clock/Data
• Wiegand
• F/2F
• Supervised F/2F
The following are basic reader cable requirements. For more information, refer to Specifications on
page 130.
• F/2F and supervised F/2F readers require a shielded 4-conductor cable.
• Clock/Data and Wiegand readers require a shielded 5-conductor cable.
Wiegand Reader
1 2
TB1
TB3
or
1
1
3 VO
2
4 GND
DISP
4
5 LED
REX+
6
6 WD0
7 WD1
7
DC+
DC-
10
REX-
Callout Description
1 Wiegand reader
116 — revision 7
M Series Installation Guide
Callout Description
Magnetic Reader
1 2
TB1
TB3
or 1
1
3 VO
4 2
GND
DISP
4
5 LED
REX+
6 WD0
6
7 WD1
7
DC+
DC-
10
REX-
Callout Description
1 Magnetic reader
revision 7 — 117
LNL-1320-S2RP Dual Door Control Module
F/2F Reader
1 2
TB1
TB3
or
1
1
3 VO
2
4 GND
DISP
4
5 LED
REX+
WD0
7
6 WD1
DC+
DC-
10
REX-
Callout Description
1 F/2F reader
118 — revision 7
M Series Installation Guide
1 2
TB1
TB3
or
1
1
3 VO
2
4 GND
3
5 DISP
4
6 LED
REX+
WD0
7 7 WD1
DC+
8
DC-
10
REX-
Callout Description
Typically, the door position monitor switch uses the Normally Closed (NC) contact and the REX uses the
Normally Open (NO) contact.
For the LNL-1320-S2RP, the door position monitor and REX switches can be wired in several different
configurations.
These configurations are downloaded from the host and may be changed.
revision 7 — 119
LNL-1320-S2RP Dual Door Control Module
Either two 1K ohm resistors, or a 6.8K and 18K ohm resistor set must be installed as shown in the following
figures. Install the EOL resistors as close to the switch as possible to maximize supervision’s effectiveness.
In addition to detecting contact open or contact closed, the LNL-1320-S2RP also monitors for the following
abnormal circuit conditions: open circuit, shorted circuit, grounding of either side of the circuit, or the
introduction of a foreign voltage.
Note: Grounded and foreign voltage states are not required by UL 294 and therefore not verified by
UL.
TB1
TB3
or
1
VO
GND
DISP
LED
1K,1%
REX+
2 1K,1% WD0
WD1
1K,1%
DC+
3
1K,1% DC-
10
REX-
Callout Description
120 — revision 7
M Series Installation Guide
Callout Description
TB1
TB3
or
1
VO
GND
DISP
6.8K,5% LED
REX+
2 18K,5% WD0
WD1
6.8K,5%
DC+
3 DC-
18K,5%
10
REX-
Unsupervised inputs for the door position monitor and REX switches are wired directly to the F/2F reader
configured for 2-State Supervision. See the reader’s documentation for the proper connection terminals.
End-Of-Line (EOL) resistors are not required.
revision 7 — 121
LNL-1320-S2RP Dual Door Control Module
4
2
5
Callout Description
1 F/2F reader
2 To LNL-1320-S2RP
4 Ground connection
6 Data 1 connection
Supervised inputs for the door position monitor and REX switches are wired directly to the F/2F reader
configured for 4-State Supervision: open, closed, short, and cut. See the reader’s documentation for the
proper connection terminals. EOL resistors typically require two 1K ohm resistors as shown in the figure
below. Install the EOL resistors as close to the switch as possible.
122 — revision 7
M Series Installation Guide
4
2
5
1K,1%
1K,1%
7
1K,1%
1K,1%
2 To LNL-1320-S2RP
4 Ground connection
6 Data 1 connection
There are two options for door strike wiring on the LNL-1320-S2RP: internal relay and external relay.
revision 7 — 123
LNL-1320-S2RP Dual Door Control Module
Note: Excessive load switching causes contact wear and premature failure. Inductive load (strike)
switching causes EMI (electromagnetic interference) that can interfere with normal operation
of other equipment. To minimize premature contact failure and to increase system reliability,
use a contact protection circuit. Locate the protection circuit as close to the load as possible
(12 inches [30cm] recommended). The circuit's effectiveness decreases if it is located further
away.
Use sufficiently large gauge wire for the load current to avoid voltage loss.
124 — revision 7
M Series Installation Guide
Callout Description
1 AC strike
2 To AC power source
3 Fuse
5 Suppression MOV
revision 7 — 125
LNL-1320-S2RP Dual Door Control Module
1 DC strike
2 To DC power source
3 Fuse
5 Suppression diode
Instead of using the on-board relay to control the door strike, an external relay may be used. This external
relay is controlled by the reader LED output.
If the LED in the reader is driven by the Reader LED signal, TB1-4 or TB3-4, a blocking diode must be
added to the circuit. This blocking diode should be a Schottky barrier rectifier, type 1N5817 or equivalent
(20 volt @ 1 A).
- The external relay’s coil current must be restricted to 40 mA.
- The 5 volt relay coil resistance must be 125 or greater ohms.
- The 12 volt relay coil resistance must be 300 or greater ohms.
Note: Excessive load switching causes contact wear and premature failure. Inductive load (strike)
switching causes EMI (electromagnetic interference) that can interfere with normal operation
of other equipment. To minimize premature contact failure and to increase system reliability,
use a contact protection circuit. Locate the protection circuit as close to the load as possible
126 — revision 7
M Series Installation Guide
(12 inches [30cm] recommended). The circuit's effectiveness decreases if it is located further
away.
5
1
TB1
TB3
4
or
3 6 1
1
VO
GND
DISP
7 4
LED
REX+
11 8
WD0
9
WD1
DC+
10 DC-
REX-
10
AC Door Strike Wiring using External Relay Callouts
Callout Description
1 AC strike
2 AC transformer
3 Fuse
4 External relay
8 Suppression diode
11 Suppression MOV
revision 7 — 127
LNL-1320-S2RP Dual Door Control Module
5
1 2 4
TB1
TB3
or
3 6 1
1
VO
GND
7 4
DISP
LED
8 8 REX+
WD0
9
WD1
DC+
10 DC-
REX-
10
DC Door Strike Wiring using External Relay Callouts
Callout Description
1 DC strike
2 To DC power source
3 Fuse
4 External relay
8 Suppression diode
128 — revision 7
M Series Installation Guide
37 Status LEDs
revision 7 — 129
LNL-1320-S2RP Dual Door Control Module
38 Specifications
• Primary Power (from LNL-3300-M5): 12 VDC, ± 10 %, 155 mA maximum (plus reader current)
• Relay Outputs: 6 outputs, Form-C, 2 A @ 30 VAC/DC, resistive
• Inputs: 4 unsupervised, two per reader port
• Reader Interface:
- Reader Power: 5 VDC or 12 VDC regulated (jumper selectable), 300 mA maximum each reader
port
- Reader LED Output/External Relay: Open collector, 40 mA sink maximum
- Reader Data Input: TTL compatible inputs
- Communication: 9600, 19200, 38400, or 115200 bps, asynchronous
• Cable Requirements:
- Alarm Inputs: 1 twisted pair per input, 22 AWG shielded. 30 ohms maximum loop resistance
- Outputs: As required for the load
- Reader Data: Use shielded cables;
– 5 VDC: 18 AWG, 200 ft. maximum, reader powered by reader processing board
– 12 VDC: 20 AWG, 500 ft. maximum, reader powered by LNL-1320-2RP; 18 AWG, 3000 ft.
maximum, reader powered locally
Notes: The above specifications are based on the typical 12 volt reader drawing 125 mA. Reader
power requirements vary between different models.
Excessive voltage drop on long cable runs may require a larger cable gauge or powering the
reader from a local power source. Refer to the power specification for the reader being
installed.
• Environmental:
- Storage Temperature: -67 to +185°F (-55 to +85°C)
- Operating Temperature: +32 to +158°F (0 to +70°C)
- Humidity: 5 to 95% RHNC
• Mechanical:
- Width: 3.5 in. (88.9 mm)
- Length: 10.25 in. (260.4 mm)
- Height: 0.69 in. (17.5 mm)
- Weight (without connectors): 4.5 oz (126 g) nominal
130 — revision 7
LNL-1340-M2K
FOUR READER
INTERFACE
MODULE
M Series Installation Guide
The LNL-1340-M2K board is a Reader Interface Module that provides four (4) reader interface ports. The
LNL-1340-M2K accepts data from readers with F/2F and supervised F/2F signaling and door hardware. The
LNL-1340-M2K provides 10 inputs (unsupervised/supervised), eight (8) Form-C control relays, and a 12
VDC power supply to power readers and other devices.
The LNL-3300-M5 Intelligent System Controller board can be mounted directly on the LNL-1340-M2K
board. The LNL-1340-M2K can only be installed in an M2000 enclosure. If the LNL-3300-M5 board is
mounted on the LNL-1340-M2K board, it is powered by the LNL-1340-M2K board's internal power supply.
Power for the LNL-1340-M2K board is supplied from an 18 VAC transformer. The LNL-1340-M2K
supports the charging of an optional 12 Volt, 7 Ah rechargeable sealed lead-acid battery for UPS operation.
Note: For LNL-3300-M5 controller board installation and specifications, refer to Overview of the
LNL-3300-M5 on page 35.
revision 7 — 133
LNL-1340-M2K Four Reader interface Module
11 13 14 17
12 15 16
10
18
19
7
S2
1
S1
TB7
1
ON
4
3 2
3
6
4
LNL-3300-
6
JP1
1
HI
2
LO
M5
JP2
3
4
5
5
6
TB2
J4
1
GND
TR-
LNL-1340-
TR+
3
J6
20
M2K
S1
1
2
3
4
ON
5
J7
6
7
8
4
J1
1
K8 K7 K6 K5 K4 K3 K2 K1
TB8
J7
K8 K7 K6 K5 K4 K3 K2 K1
8
21
BR/CR2325
BR/CR2330
TB1
BT1
VIN
GND
VIN
GND
VIN
GND
2 TMPR
PFLT
8
22
26 25 24 23
134 — revision 7
M Series Installation Guide
10 Mounting Holes 4x
20 JP2: Set to Lo
22 12 Volt Battery
revision 7 — 135
LNL-1340-M2K Four Reader interface Module
LNL-3300-M5 Board
S2
11
4 3 2 1 S1
1
ON
10
1
2
3
4
5
9
J4
TB2
1
GND
TR-
TR+
3
2
J6
8
7b
7a
J1
7
J7
BR/CR2325
BR/CR2330
TB1
VIN
BT1
GND
VIN
GND
6 VIN
GND
5
TMPR
PFLT
8
136 — revision 7
M Series Installation Guide
7a Card puller
Warning
The card puller must be removed from the LNL-3300-M5 board before mounting it to the
LNL-1340-M2K board. Install two (2) mounting screws [7b] in the holes made vacant from
the card puller.
9 Status LEDs
10 DIP switches
11 Reset switch
revision 7 — 137
LNL-1340-M2K Four Reader interface Module
40 Configuration
Configuring the LNL-1340-M2K consists of setting the device address and the power selection jumper.
Use the on-board DIP switches to set the device address and communication baud rate on the LNL-1340-
M2K.
• Switches 1-5 select the device address.
• Switch 6 and 7 select the communication baud rate.
Note: Currently, OnGuard only supports a baud rate of 38,4000 bps. Be sure to set both DIP switches
6 and 7 to the ON position.
All other configuration settings are set via the host software.
Selection S1 S2 S3 S4 S5 S6 S7 S8
Address 15 ON ON ON ON OFF
138 — revision 7
M Series Installation Guide
Selection S1 S2 S3 S4 S5 S6 S7 S8
Address 23 ON ON ON OFF ON
Address 27 ON ON OFF ON ON
Address 29 ON OFF ON ON ON
Address 30 OFF ON ON ON ON
Address 31 ON ON ON ON ON
38,400 bps ON ON
Input power for the LNL-1340-M2K/LNL-3300-M5 assembly is provided by a wall mount 18 VAC
transformer @ 2.78 A (334 VA) connected to TB8 pins 1 and 2. The internal supply supplies power to the
LNL-1340-M2K/LNL-3300-M5 assembly, and charging current for a 12 V, 7 Ah rechargeable battery. 12
VDC output is also available to power local devices (door strikes, annunciator devices, etc.), and
downstream LNL-1340-M2K enclosures. The UPS 12 V battery is connected to TB8 pin 7 (+) and TB8 pin
8 (-). There is a dedicated input for cabinet tamper, connected to TB8-5 and TB8-6. Normal (safe) condition
is a closed contact.
revision 7 — 139
LNL-1340-M2K Four Reader interface Module
TB8-3 GND
Warning
The grounding lug on the LNL-3300-M5, identified as “CGND” (located next to the Ethernet jack), must be
connected to the chassis/earth ground stud on the M2000 enclosure. It is recommended to use braided wire
and make the connection is as short as possible.
140 — revision 7
M Series Installation Guide
41 Wiring
DRAIN WIRE
SHIELD
TB2 TB7
1 1
GND GND
SHIELD
TR- TR-
TR+ TR+
3 3
Each of the four (4) reader ports on the LNL-1340-M2K Reader Interface Module supports F/2F and
supervised F/2F type readers.
F/2F and supervised F/2F readers require a shielded 4-conductor cable. For more information, refer to
Specifications on page 154.
revision 7 — 141
LNL-1340-M2K Four Reader interface Module
1
3
1 VO
4
2 GND
5
3 DI
6 4 DOx
4
(LED)
1 F/2F reader
2 TBx on LNL-1340-M2K
142 — revision 7
M Series Installation Guide
1. Supervised F/2F readers: Door contacts and REX can be wired through the Reader Edge or they can
be wired to the LNL-1340-M2K as a Board Edge configuration.
2. F/2F readers: Door contacts and REX inputs must be wired to the LNL-1340-M2K inputs as a Board
Edge configuration. Note that F/2F is an Unsupervised F/2F protocol only, and does not relate to
supervision of the door contacts. For more information, refer to Input Wiring on page 145.
Typically, the door position monitor switch uses the Normally Closed (NC) contact and the REX uses the
Normally Open (NO) contact. For the LNL-1340-M2K Reader Interface Module, the door position monitor
and REX switches are wired to the F/2F reader. These configurations are downloaded from the host and may
be changed.
For 4-State Supervision, supervised inputs for the door position monitor and REX switches are wired
directly to the F/2F reader configured for 4-State Supervision. See the reader’s documentation for the proper
connection terminals. End-of-Line (EOL) resistors typically require two 1K ohm resistors. Install the EOL
resistors as close to the switch as possible (within 12 inches [30cm] recommended).
revision 7 — 143
LNL-1340-M2K Four Reader interface Module
4
2
5
6
1K,1%
1K,1%
7
1K,1%
1K,1%
1 F/2F reader
2 To LNL-1340-M2K
4 Ground connection
5 Data 1 connection
For 2-State Supervision, unsupervised inputs for the door position monitor and REX switches directly to the
F/2F reader. configured for 2-State Supervision. See the reader’s documentation for the proper connection
terminals. End-of-Line (EOL) resistors are not required.
144 — revision 7
M Series Installation Guide
4
2
5
2 To LNL-1340-M2K
4 Ground connection
6 Data 1 connection
Typically, these inputs are used to monitor door position, request to exit, or general purpose alarm contacts.
Input circuits can be configured as unsupervised or supervised. When unsupervised, reporting consists of
only the open or closed states.
When an input circuit is configured for supervision, the LNL-1340-M2K board also monitors the following
abnormal circuit conditions: open circuit, shorted circuit, grounding of either side of the circuit*, or the
introduction of a foreign voltage*. A supervised input circuit requires adding two resistors to the circuit to
revision 7 — 145
LNL-1340-M2K Four Reader interface Module
facilitate proper reporting. The standard supervised circuit requires 1K Ohm, 1% resistors and should be
located as close to the sensor as possible. Custom End-of-Line (EOL) resistances may be configured via the
host software.
* Grounded and foreign voltage states are not UL 294 required and therefore not verified by UL.
The input circuit wiring configurations shown are supported, but may not be typical:
1
1K,1%
1K,1%
1K,1%
Callout Description
5 Terminal Blocks: TB1 (Inputs 1-5) and TB2 (Inputs 6-10) on LNL-1340-M2K
Warning
Door position monitor and REX inputs must be wired to the LNL-1340-M2K when using F/2F readers. EOL
resistors are typically two 1K ohm resistors as shown below. The EOL resistors should be installed as close
to the switch as possible.
146 — revision 7
M Series Installation Guide
TB1-1 DI 1 TB2-1 DI 6
TB1-3 DI 2 TB2-3 DI 7
TB1-5 DI 3 TB2-5 DI 8
TB1-7 DI 4 TB2-7 DI 9
TB1-9 DI 5 TB2-9 DI 10
An external relay may be used to control a door strike. This external relay is controlled by the reader DOx
output on the LNL-1340-M2K.
If the LED in the reader is driven by the Reader port DOx signal, a blocking diode must be added to the
circuit. This blocking diode should be a Schottky barrier rectifier, type 1N5817 or equivalent (20 volt @ 1
A).
- The external relay’s coil current must be restricted to 40 mA.
- The 12 volt relay coil resistance must be 300 or greater ohms.
revision 7 — 147
LNL-1340-M2K Four Reader interface Module
6
1 2
4
5
3 1
1
VO
GND
DI
4
DOx
4
7
8
8
10
1 DC strike
2 To DC power source
3 Fuse
4 External relay
5 TB1 on LNL-1340-M2K
148 — revision 7
M Series Installation Guide
6
1
4
3 5 1
1
VO
GND
DI
4
DOx
4
7
9 8
10
11
1 AC strike
2 AC transformer
3 Fuse
4 External relay
5 TB1 on LNL-1340-M2K
8 Suppression diode
11 Suppression MOV
The LNL-1340-M2K board has eight (8) Form-C contact relays for controlling door strikes or other devices.
Relay contact rating: 2 A @ 30 VAC/DC maximum.
Note: Excessive load switching causes contact wear and premature failure. Inductive load (strike)
switching causes EMI (electromagnetic interference) which may interfere with normal
operation of other equipment. To minimize premature contact failure and to increase system
reliability, a contact protection circuit must be used. Locate the protection circuit as close to the
revision 7 — 149
LNL-1340-M2K Four Reader interface Module
load as possible (12 inches [30cm] maximum recommended). The circuit's effectiveness
decreases if it is located farther away.
Use sufficiently large gauge wire for the load current to avoid voltage loss.
4
6
3 NO
NC
K2
NO
NC
K1
C
1
150 — revision 7
M Series Installation Guide
1 DC strike
2 To DC power source
3 Fuse
5 Suppression diode
1 2
6
3 NO
NC
K2
C
NO
NC
K1
C
1
1 AC strike
2 To AC power source
3 Fuse
5 Suppression MOV
revision 7 — 151
LNL-1340-M2K Four Reader interface Module
42 Status LEDs
152 — revision 7
M Series Installation Guide
43 UL 294 Installations
For UL294 installations, the LNL-1340-M2K has been evaluated to the following:
LNL-1340-M2K 1 2 4 4
revision 7 — 153
LNL-1340-M2K Four Reader interface Module
44 Specifications
Note: Excessive voltage drop on long cable runs may require a larger cable gauge or powering the
reader from a local power source. Refer to the power specification for the reader being
installed.
• Environmental:
- Storage Temperature: -67 to +185°F (-55 to +85°C)
- Operating Temperature: +32 to +122°F (0 to +50°C)
- Humidity: 5 to 95% RHNC
• Mechanical:
- Width: 8.375 in (212.7 mm)
- Length: 11.375 in (289.1 mm)
- Height:
1.04 in (26.5 mm) without LNL-3300-M5
1.27 in (32.26 mm) with LNL-3300-M5
- Weight (without connectors):
12.0 oz. (340.2 g) nominal without LNL-3300-M5
17.3 oz. (491.0 g) nominal with LNL-3300-M5
154 — revision 7
LNL-1380-8RP
READER
INTERFACE
MODULE
M Series Installation Guide
The LNL-1380-8RP is a Reader Interface Module that provides eight (8) reader interface ports. The
LNL-1380-8RP accepts data only from readers with supervised F/2F signaling.
The door position and Request-to-Exit (REX) inputs are reported through the F/2F reader data line. The
LNL-1380-8RP also provides LED status, external strike relay control, and 12 VDC reader power.
LNL-1380-8RP Board
TB1
1
12V
GND
12 DATA
LED
12V
GND
11
DATA 8
LED
TB2
1
1
12V
GND
10
DATA
LED
12V
GND
9
DATA
LED
8
2
1
2
3
4
3
TB3
12V
GND
8 DATA
LED
12V
GND
7 DATA
8
LED
4
3
2
1
TB4
J3
1
12V
GND
6 DATA
LED ON
1
2
3
4
5
6
7
8
12V
S1
GND
5
DATA
8
LED
1 Status LEDs
4 DIP switches
revision 7 — 157
LNL-1380-8RP Reader Interface Module
5 Reader 8
6 Reader 7
7 Reader 6
8 Reader 5
9 Reader 4
10 Reader 3
11 Reader 2
12 Reader 1
158 — revision 7
M Series Installation Guide
46 Configuration
Configuring the LNL-1380-8RP consists of setting the device address and the power selection jumper.
Use the on-board DIP switches to set the device address and communication baud rate on the
LNL-1380-8RP.
• Switches 1 to 5 select the device address.
• Switches 6 and 7 select the communication baud rate.
Note: Currently, OnGuard only supports a baud rate of 38,4000 bps. Be sure to set both DIP Switches
6 and 7 to the ON position.
Selection S1 S2 S3 S4 S5 S6 S7 S8
Address 15 ON ON ON ON OFF
revision 7 — 159
LNL-1380-8RP Reader Interface Module
Selection S1 S2 S3 S4 S5 S6 S7 S8
Address 23 ON ON ON OFF ON
Address 27 ON ON OFF ON ON
Address 29 ON OFF ON ON ON
Address 30 OFF ON ON ON ON
Address 31 ON ON ON ON ON
38,400 bps ON ON
• On the first LNL-1380-8RP installed in the controller enclosure, place the shorting plug on Pins 2 and 3
on the J3 jumper.
• On the second LNL-1380-8RP installed in the controller enclosure, place the shorting plug on Pins 1
and 2 on the J3 jumper.
160 — revision 7
M Series Installation Guide
46.3 Wiring
Note: The 12V output for Reader Port 7 on the second LNL-1380-8RP is not current-limited.
revision 7 — 161
LNL-1380-8RP Reader Interface Module
4 Ground connection
162 — revision 7
M Series Installation Guide
2 TB1 on LNL-1380-8RP
For 2-State Supervision, wire unsupervised inputs for the door position monitor and REX switches directly
to the F/2F reader. See the reader’s documentation for the proper connection terminals. End-Of-Line (EOL)
resistors are not required.
revision 7 — 163
LNL-1380-8RP Reader Interface Module
1 F/2F reader
2 To LNL-1380-8RP
4 Ground connection
6 Data 1 connection
For 4-State Supervision, wire supervised inputs for the door position monitor and REX switches directly to
the F/2F reader. See the reader’s documentation for the proper connection terminals. EOL resistors typically
require two 1K ohm resistors. Install the EOL resistors as close to the switch as possible (within 12 inches
[30cm] recommended).
164 — revision 7
M Series Installation Guide
2 To LNL-1380-8RP
4 Ground connection
6 Data 1 connection
An external relay may be used to control a door strike. This external relay is controlled by the reader LED
output on the LNL-1380-8RP. The external relay can be wired for AC or DC current.
If the LED in the reader is driven by the Reader LED signal, TB1-4 or TB3-4, a blocking diode must be
added to the circuit. This blocking diode should be a Schottky barrier rectifier, type 1N5817 or equivalent
(20 volt @ 1 A).
- The external relay’s coil current must be restricted to 40 mA.
- The 5 volt relay coil resistance must be 125 or greater ohms.
revision 7 — 165
LNL-1380-8RP Reader Interface Module
Note: Excessive load switching causes contact wear and premature failure. Inductive load (strike)
switching causes EMI (electromagnetic interference) that can interfere with normal operation
of other equipment. To minimize premature contact failure and to increase system reliability,
use a contact protection circuit. Locate the protection circuit as close to the load as possible
(12 inches [30cm] recommended). The circuit's effectiveness decreases if it is located further
away.
5
1
4
TB1
3 6 1
1
12V
V
READER 1
GND
7 4
DATA
LED
11 8
12V
V
9
READER 2
GND
DATA
10 LED
1 AC strike
2 AC transformer
3 Fuse
4 External relay
8 Suppression diode
11 Suppression MOV
166 — revision 7
M Series Installation Guide
5
1 2 4
TB1
3 6 1
1
12V
V
READER 1
GND
7 4
DATA
LED
8 8
12V
V
9
READER 2
GND
DATA
10 LED
8
DC Door Strike Wiring using External Relay Callouts
Callout Description
1 DC strike
2 To DC power source
3 Fuse
4 External relay
8 Suppression diode
revision 7 — 167
LNL-1380-8RP Reader Interface Module
47 Status LEDs
168 — revision 7
M Series Installation Guide
48 Specifications
Notes: The above specifications are based on the typical 12 volt reader drawing 125 mA. Reader
power requirements vary between different models.
Excessive voltage drop on long cable runs may require a larger cable gauge or powering the
reader from a local power source. Refer to the power specification for the reader being
installed.
• Environmental:
- Storage Temperature: -67 to +185°F (-55 to +85°C)
- Operating Temperature: +32 to +158°F (0 to +70°C)
- Humidity: 5 to 95% RHNC
• Mechanical:
- Width: 3.5 in. (88.9 mm)
- Length: 10.25 in. (260.4 mm)
- Height: 0.69 in. (17.5 mm)
- Weight (without connectors): 3.7 oz (104 g) nominal
revision 7 — 169
LNL-1380-8RP Reader Interface Module
170 — revision 7
LNL-8000-MCOM
RS-485 INTERFACE
MODULE
M Series Installation Guide
The LNL-8000-MCOM is an RS-485 Interface Module that connects the first controller enclosure, which
contains the LNL-3300-M5 Intelligent System Controller (ISC), to downstream controller enclosures.
The LNL-8000-MCOM accepts 12 VDC power and two-wire RS-485 communication.
A local 12 VDC power supply powers the I/O modules in the controller enclosure. The LNL-3300-M5
(located in the first controller enclosure) communicates with the downstream controller enclosure using
multi-drop two-wire RS-485.
revision 7 — 173
LNL-8000-MCOM RS-485 Interface Module
50 Wiring
Terminal Block 2 (TB2) is a two-wire RS-485 interface that communicates to upstream and downstream
controller enclosures.
TB2 on the LNL-3300-M5 (located in the first M5 enclosure) is wired to TB2 on the LNL-8000-MCOM in
each downstream enclosure.
This interface allows multi-drop communication on a single bus up to 4,000 ft. (1,200 m).
Use shielded twisted pair (24 AWG minimum) cable with 120 ohm impedance.
1 Shield
2 Drain wire
3 TB2 on LNL-8000-MCOM
174 — revision 7
M Series Installation Guide
The LNL-8000-MCOM requires 12 VDC power, 3 A minimum. This power is passed through to the back
plane to power the I/O modules in the M5 enclosure.
There are three pairs of connections for power, all in parallel, on Terminal Block 1 (TB1). If needed, the
other two pairs can supply power to the other I/O boards.
To wire the input power:
Notes: Depending on the system configuration, a larger power supply may be required.
Connect the GND signal to earth ground in one location within the system. Multiple earth
ground connections are not recommended as they can cause group loop problems.
Observe polarity on the 12 VDC input.
2 TB1 on LNL-8000-MCOM
revision 7 — 175
LNL-8000-MCOM RS-485 Interface Module
The LNL-3300-M5 has two dedicated inputs for enclosure tamper (TMPR) and UPS fault monitoring
(PFLT). The LNL-8000-MCOM installed in downstream controller enclosures does not have these
dedicated inputs.
There are three options available to wire tamper and power fault switches in downstream controller
enclosures:
• Wire the tamper and power fault switches in series from the first controller enclosure to downstream
controller enclosures. Use conduit when wiring from one enclosure to the next, and ensure the conduit
is inaccessible. With this option, the user cannot determine which controller enclosure is reporting the
alarm.
• Wire the tamper and power fault switches to available inputs on the LNL-1100-20DI board.
• Wire the tamper and power fault switches to available reader port inputs.
The inputs on the LNL-1100-20DI, LNL-1320-2RP, and the LNL-1320-S2RP are monitor points configured
as unsupervised, Normally Closed contacts.
For more information regarding wiring details, refer to:
• LNL-1320-2RP Reader Wiring on page 94
• LNL-1320-S2RP Reader Wiring on page 116
• LNL-1100-20DI Alarm Input Wiring on page 61
176 — revision 7
M Series Installation Guide
51 Specifications
• Primary Power: Not applicable. Power is passed through and supplies power to the controller
enclosure back plane.
• Communication: Two-wire RS-485 at 9600, 19200, 38400, or 115200 bps, asynchronous, passed
through to the back plane.
• Cable Requirements:
- Power: 1 twisted pair, 18 AWG
- RS-485: 24 AWG; 4,000 ft. (1,200 m) maximum; shielded twisted pair; 120 ohm impedance
• Environmental:
- Storage Temperature: -67 to +185 °F (-55 to +85 °C)
- Operating Temperature: +32 to +158 °F (0 to +70 °C)
- Humidity: 5 to 95% RHNC
• Mechanical:
- Width: 3.5 in. (88.9 mm)
- Length: 10.25 in. (260.4 mm)
- Height: 0.6 in. (15.24 mm)
- Weight (without connectors): 3.4 oz (96.5 g) nominal
revision 7 — 177
LNL-8000-MCOM RS-485 Interface Module
178 — revision 7
M Series Installation Guide
Index
A D
AC DC
door strike wiring door strike wiring
external relay ........... 104, 127, 149, 166 external relay ........... 105, 128, 148, 167
internal relay... 101, 102, 124, 125, 148 internal relay............ 102, 103, 125, 126
LNL-1200-16DOR ............................... 83 Default login security enhancements.................. 37
Alarm Device address
input wiring, LNL-1100-20DI ..................... 61 setting
LNL-1100-20DI ................................... 59
B LNL-1200-16DO.................................. 69
Battery LNL-1200-16DOR ............................... 79
clock LNL-1320-2RP..................................... 91
backup LNL-1320-S2RP ................................ 113
LNL-3300-M5............................... 51 LNL-1340-M2K ................................. 138
install backup ............................................... 19 LNL-1380-8RP................................... 159
memory DIP switches
backup LNL-1100-20DI........................................... 59
LNL-3300-M5............................... 51 LNL-1200-16DO ......................................... 69
Baud Rate LNL-1200-16DOR ...................................... 79
setting LNL-1320-2RP ............................................ 91
LNL-1100-20DI ................................... 59 LNL-1320-S2RP........................................ 113
LNL-1200-16DO.................................. 69 LNL-1340-M2K ........................................ 138
LNL-1200-16DOR ............................... 79 LNL-1380-8RP .......................................... 159
LNL-1320-2RP..................................... 91 LNL-3300-M5 ............................................. 41
LNL-1320-S2RP................................. 113 Door
LNL-1340-M2K ................................. 138 AC strike wiring
LNL-1380-8RP................................... 159 external relay ........... 104, 127, 149, 166
Bulk erase function internal relay... 101, 102, 124, 125, 148
LNL-3300-M5 ............................................. 51 LNL-1200-16DOR ............................... 83
DC strike wiring
C external relay ........... 105, 128, 148, 167
internal relay... 102, 103, 125, 126, 147
Cable LNL-1200-16DOR ............................... 82
length ........................................................... 14 dual control module
routing.......................................................... 14 LNL-1320-2RP..................................... 89
Clock LNL-1320-S2RP ................................ 111
real time wire to reader............................... 94, 116
LNL-3300-M5 ...................................... 51 external relay strike wiring ............... 103, 126
Communication internal relay strike wiring................ 100, 123
wiring position monitor wiring ...................... 97, 119
LNL-3300-M5 ...................................... 45 Door strike
LNL-8000-MCOM ............................. 174 troubleshooting ............................................ 25
Configuration
host application E
LNL-3300-M5 ...................................... 50
LNL-1320-2RP ............................................ 91 Electrostatic Discharge (ESD) ............................ 13
LNL-1320-S2RP........................................ 113 Enclosure tamper
web LNL-3300-M5 ............................................. 20
first-time login ...................................... 47 LNL-8000-MCOM ...................................... 21
web page ...................................................... 47 wiring
revision 7 — 179
Index
180 — revision 7
M Series Installation Guide
revision 7 — 181
Index
182 — revision 7
M Series Installation Guide
DC door strike
external relay ........... 105, 128, 148, 167
internal relay... 102, 103, 125, 126, 147
LNL-1200-16DOR ............................... 82
door position monitor ......................... 97, 119
dual door control module to reader..... 94, 116
enclosure tamper
LNL-1340-MK2 ................................. 139
LNL-3300-M5 ...................................... 46
LNL-8000-MCOM ............................. 176
external relay door strike .................. 103, 126
input power
LNL-8000-MCOM ............................. 175
internal relay door strike................... 100, 123
LNL-8000-MCOM .................................... 174
outputs
relay ...................................................... 81
power
LNL-3300-M5 ...................................... 46
power fault
LNL-8000-MCOM ............................. 176
power fault input
LNL-3300-M5 ...................................... 46
reader interface module to reader .............. 162
supervised inputs to F/2F
reader ......................... 99, 100, 122, 123
supervised inputs to LNL-1320-S2RP....... 120
supervised inputs to LNL-1320-S2RP,
1K/1K EOL ........................................ 120
supervised inputs to LNL-1320-S2RP,
6.8K/18K EOL ................................... 121
supervised inputs to LNL-1340-M2K 143, 144
supervised inputs to LNL-1380-8RP ......... 164
unsupervised inputs to F/2F reader..... 98, 121
unsupervised inputs to LNL-1320-2RP ....... 98
unsupervised inputs to LNL-1380-8RP ..... 163
revision 7 — 183
UTC Fire & Security Americas Corporation, Inc.
1212 Pittsford-Victor Road
Pittsford, New York 14534 USA
Tel 866.788.5095 Fax 585.248.9185
www.lenel.com
docfeedback@lenel.com