Se Bronco - Lote Iv

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

Date: 01-05-2023

Author: DLANDIVAR

STORK

SE BRONCO

LOTE IV
ESTANDAR DE EVALUACION, NORMA DE REFERENCIA:
Table of Contents

IR_00007.IS2 .............................................................................................................................................................. 4

IR_00008.IS2 .............................................................................................................................................................. 6

IR_00009.IS2 .............................................................................................................................................................. 8
IR_00007.IS2

Inspection Date 05/08/2023 Location SE BRONCO

Equipment CP_2003763 Equipment Name TAB.DISTRIBUCION

Ambient Air
Wind Speed
Temperature

Load (%) Max Rated Load

Exception
Potential Problem
Temperature

Recommended Action Repair Priority

Emissivity 0.95 Reflected Temperature 22.00 °C

Camera Manufacturer Fluke Corporation Camera Ti400

Image Info

Name IR_00007.IS2

Emissivity 0.95

Background Temperature 22.00 °C

Calibration Range -20.00 °C to 80.00 °C

Image Range 32.57 °C to 52.87 °C


IR Sensor Size 320X240

Camera Serial Number Ti400-17040090

DSP Version 4.2.4

Image Time 08/03/2017 17:54:54 PM

Marker Info

Marker Name Maximum Minimum Average Emissivity BG Temp Std.Dev Delta-T


Hot 52.9 °C 52.9 °C 52.9 °C 0.95 22.0 °C 0.00
Cold 32.6 °C 32.6 °C 32.6 °C 0.95 22.0 °C 0.00
A0 45.2 °C 40.0 °C 43.1 °C 0.95 22.0 °C 0.99
A1 42.9 °C 39.2 °C 41.3 °C 0.95 22.0 °C 0.89
A2 42.4 °C 38.1 °C 40.7 °C 0.95 22.0 °C 0.98
IR_00008.IS2

Inspection Date 05/08/2023 Location SE BRONCO

Equipment PTOT_2003762 Equipment Name TRANSFORMADOR

Ambient Air
Wind Speed
Temperature

Load (%) Max Rated Load

Exception
Potential Problem
Temperature

Recommended Action Repair Priority

Emissivity 0.95 Reflected Temperature 22.0 °C

Camera Manufacturer Fluke Corporation Camera Ti400

Image Info

Name IR_00008.IS2

Emissivity 0.95

Background Temperature 22.0 °C

Calibration Range -20.0 °C to 80.0 °C

Image Range 27.9 °C to 45.6 °C


IR Sensor Size 320X240

Camera Serial Number Ti400-17040090

DSP Version 4.2.4

Image Time 08/03/2017 17:57:07 PM

Marker Info

Marker Name Maximum Minimum Average Emissivity BG Temp Std.Dev Delta-T


A0 40.8 °C 35.3 °C 39.0 °C 0.95 22.0 °C 0.92
A1 40.1 °C 34.7 °C 38.9 °C 0.95 22.0 °C 0.86
A2 38.9 °C 31.1 °C 36.2 °C 0.95 22.0 °C 2.12
IR_00009.IS2

Inspection Date 05/08/2023 Location BRONCO

Equipment PTOT_2003762 Equipment Name TRANSFORMADOR

Ambient Air
Wind Speed
Temperature

Load (%) Max Rated Load

Exception
Potential Problem
Temperature

Recommended Action Repair Priority

Emissivity 0.95 Reflected Temperature 22.00 °C

Camera Manufacturer Fluke Corporation Camera Ti400

Image Info

Name IR_00009.IS2

Emissivity 0.95

Background Temperature 22.00 °C

Calibration Range -20.00 °C to 80.00 °C

Image Range 26.78 °C to 43.91 °C


IR Sensor Size 320X240

Camera Serial Number Ti400-17040090

DSP Version 4.2.4

Image Time 08/03/2017 17:58:49 PM

Marker Info

Marker Name Maximum Minimum Average Emissivity BG Temp Std.Dev Delta-T


A0 40.4 °C 35.7 °C 39.0 °C 0.95 22.0 °C 0.97
A1 40.1 °C 28.4 °C 38.3 °C 0.95 22.0 °C 2.03
A2 40.4 °C 34.0 °C 38.6 °C 0.95 22.0 °C 1.71
Summary:
1.- Tablero de Distribución 440 vac : Normal.
2.- Transformador de Potencia 160 Kva : Normal.