Professional Documents
Culture Documents
PD195Z-E33
PD195Z-E33
CAUTION:
◆ Make sure only the qualified technicians perform the installation and
maintenance;
◆Before performing wiring operation to the meter, make sure the input signal and
the power supply are switched off;
◆The proper voltage detecting device should be used to guarantee no voltage in
any part of the meter;
◆The electrical parameters supplied should be within the rated range;
The following situations may result in damages to the meter or cause mistakes in
the operation of the meter.
◆The voltage of the auxiliary power supply goes beyond the rated range.
◆The frequency of the power distribution system goes beyond the rated range.
◆The input polarity of the voltage or the current is incorrect.
◆Remove or connect the communication plugs without powering off.
◆Connect the terminal wires against the related instructions.
1 2
Menu 5.2 Extreme value and demand .......................................................................... 27
5.3 Digital Input.................................................................................................... 27
Safety instructions ..................................................................................................... 2
5.4 Relay output ................................................................................................... 27
1. Product description ................................................................................................ 5
6. Common problems and solutions........................................................................ 28
2. Technical parameter ............................................................................................... 5
Communication .................................................................................................... 28
2.2 Function parameter ......................................................................................... 7 Inaccurate measurement ..................................................................................... 29
5. Communication .................................................................................................... 22
3 4
Insulation Signal, power supply, output terminals to case resistance>100MΩ
1. Product description
Working power supply
PD195Z‐E33 can measure basic electrical variables such as voltage, current and
Rated range DC:‐40 ~ ‐60V
power, energy, demand and Max./Min. values of 21 DC circuits. Extension modules
Power consumption <5VA
EK1 have digital input and relay output functions. Communication interface on the
Withstand voltage >2kV
meter makes it simple to connect the meter to smart distribution system and
Voltage input
energy management system to share monitoring data and energy quality data.
Model Function Range DC:‐48V(max overvoltage:‐60V)
PD195Z‐E33 main current, power, energy, demand, Max./Min. value; Impedance 1.6 MΩ/phase
module one RS485 communication interface; Power consumption About 0.1 VA /phase
main module is the required module. Over voltage Instantaneous: two times of rated value during 10 seconds
5 6
Isolation voltage 2000 VAC (1 min) 3. Installation and wiring
Scanning time 1 ms 3.1 Outline dimension
Filtering time 30 ms 3.1.1 PD195Z‐E33 main module dimension
Real‐time clock 72 63.5
Time clock Error<0.5s/d
EMC
BCM100-M
35
90
Radiated, radio‐frequency, electromagnetic field immunity IEC 61000‐4‐3‐III
90
35
V
element)
Active power P 0.5 0‐‐5.7 kW 0‐‐9999 MW
Import/Export active
energy
Import/Export active
35
90
energy of 12 months
Import/Export active
7 8
3.2 Wiring
PC
L -
RS232
N + 71 72 73 74 70
RS485
Digital input
1 2 58 59 11 12
L N A B U+ U-
Power supply Communication Voltage input
15 16 17
+ + + + + + + + +
- - - - - - - - -
L
PD195Z‐E33 N
EK1
- - -
+ + + Note:
1. Auxiliary power supply: DC:‐48V
Current input
2. Rated current of fuse:0.5A
I-
54 55 56 57
Definition of wiring terminals is as follows,
Power supply 1,2 DC:‐40V~‐60V
Current signal 30‐57 Current input
Current input Current input Current input
Voltage signal 11,12 Voltage input
I- I- I-
42 43 44 45 46 47 48 49 50 51 52 53 Energy pulse output 47,48 Active energy pulse output
RS485
+ + + + + + + + + communication 58,59 Corresponding to A, B and S severally
- - - - - - - - - Relay output 15—17 Two relay outputs, 16 is common end
EM2D Digital input 70—74 Four digital inputs, 70 is common end
9 10
4. Setting operation Circuit indication sign Corresponding to circuits
B‐This part show unit of data, order of magnitude and other indication information;
C‐The three rows show measured data.
4.3 Basic variables measurement
: to move upward/switch to former page/modify parameter/increase value at selected bit
The meter can measure voltage, current, power, demand, energy and max./min.
: to move downward/switch to the next page/modify parameter
value. These variables can be checked through front panel, but some parameters
: to revert to upper level of menu/change display item
only can be read through communication. The following table show display pages of
:to enter the page of a selected item
basic variables
注:“ ”can switch U/I/P/EP/T display voltage
“ ”can switch 21 parameters under the interface of I/P/EP U=220.7V
I2=5.012A I10=5.011A
I3=5.013A I11=5.012A
I12=5.013A
#2 current #5 current
A‐Circuit indication: the device can measure twenty one single phase circuits at I4=5.021A (L2 flashing)
most. When “L1” is in static mode, the three rows from up to down correspond I5=5.022A I13=5.021A
I6=5.023A I14=5.022A
to “1”,“2” and “3” circuits severally.
I15=5.023A
11 12
#3 current #6 current Time
I18=50.73A The left picture show the time is 16:37:30, Oct. 28th,
I19=71.7A
#2 power #5 power
#3 power #6 power
P18=7058W
#7 power(L4 flashing)
P21=7053W
13 14
Negative active energy of No. 01 circuit or move the decimal point; “ ” key is used to return; “ ” key is used to confirm
EP01‐ = 6800kWh the entering menu and modified value.
4.2 For details of setup menus, please see the Setup Menu Character Code
Description Table
Negative active energy of No. 05 circuit
Password
~ User’s password
Setting operation: “ ” key is used to shift the menu and move the numerical value …
to left; “ ” key is used to shift the menu, increase or decrease the numerical value
15 16
zone or fixed
Screen 0 is displayed below the zone
3~100‰
screen value
:off
When a percentage of the Work mode
Flash :remote control
rating value is exceeded,a
alarming 30~120% :alarm
numeric flashing is
Pulse width
displayed 0~99.99s Pulse width
Relay output
Meter address
~ To set meter address: 1~247 Item
... Alarm item
Baud rate
~ To select baud rate: 1200‐9600 Alarm value
0~9999 Alarm value
Communicatio
:Modbus‐RTU
n protocol
:DLT645
value)
Calculation
: slip zone
mode
Demand : fixed zone
Calculation
17 18
4.3 Setup operation examples 4.3.2 Communication setup
4.3.1 System setup To set communication address to be 12, select baud rate as 9600, set data format to
To change password to 112, set cycle display and clear energy data, the operation be E81 odd check mode, the operation process is as follows,
process is as follows,
19 20
4.3.3 Alarm setup 5. Communication
To set relay output as alarm mode, set pulse width to be 10s, select alarm item as 5.1 Physical layer
line voltage, set alarm value to 110%, set hysteresis value to be 5%, set delayed 1) RS485 communication port, asynchronous half two‐way pattern;
response time to 10s, the operation process is as follows, 2) Speed 2400~9600bps settable, default as 9600 bps;
3)Bytes transmission format (N81, E81, O81):1 initial byte, 8 data bytes (1 odd and
even check bytes), and 1 stop byte.
Address Code: Slave address range only 1~247 are used in our system while other
addresses are reserved. The address of each terminal must be unique, only the
terminal is addressed will respond to the query from the host.
Function Code: It shows the function to be carried out by the terminal which is
addressed. The following list shows function codes and responding definitions and
functions supported by the mter.
Code Meaning
Data Code: It contains the data for a specific function which the terminal carries or
the collected data that the terminal responds the query to the host computer. The
contents of these data may be numerical value, reference address or set value. For
example: The function code instructs the terminal to read a register, the data code
indicates that from which register to start and how much data to be read. The
content of returned slave data code includes the data length and the relating data.
21 22
Check Code: The error check code (CRC) takes up two bytes, including 16 bits binary Data range 1~247 0x02 0x0000 0x0001~0x000C CRC16
value. The CRC value is calculated by the transmitting device, and then to be added Message
0x01 0x02 0x00 0x00 0x00 0x04 0x79 0xC9
to the data frame. The receiving devices calculate the CRC value again and compare example
it with the value in CRC. If the two values are not equal, the CRC makes an error. Data address function data code
CRC check code
5.1.3 Report Command Format Slave structure data code byte of register register value
(1)Read the status of relay output(Function code 0x01) respons Byte 1 byte 1 byte 1 byte 1 byte 2 bytes
request Remark: the register value in the slave response indicates the status of digital input.
Data range 1~247 0x01 0x0000(fixed) 0x0001~0x0002 CRC16
Beginning from the lowest bit of the byte, each number corresponds to the status of
Message
0x01 0x01 0x00 0x00 0x00 0x02 0xBD 0xCB a channel of digital input. “1” indicates the switch is closed, while “0” indicates the
example
switch is open. In the upper list the register value “0x02” is “0000 0010” in binary
frame address function data code system which means second loop of digital input is closed.
CRC check code
structure code code byte of register register value (3)Read data register value(function code 0x03/0x04)
slave
Frame address function data code
Byte 1 byte 1 byte 1 byte 1 byte 2 bytes
CRC check code
response
structure code code initial register address number of register
Message
0x01 0x01 0x01 0x03 0x11 0x89 Byte 1 byte 1 byte 2 bytes 2 bytes 2 bytes
example Host
0x03/
request data range 1~247 0x0000 Max 100 CRC16
Remark: the register value in the slave response indicates the status of the relay. 0x04
Beginning from the lowest bit of the byte, each number corresponds to the status of message
0x01 0x03 0x00 0x06 0x00 0x06 0XE4 0x36
a channel of relay output. “1” indicates the relay is closed, while “0” indicates the example
relay is open. In the upper list, the register value “0x03” corresponds to “0000
frame address function data code
0011” in binary system which means the first and second channels of relays are CRC check code
structure code code byte of register register value
closed. slave
byte 1 byte 1 byte 1 byte 12 bytes 2 bytes
response
(2)Read the status of digital input(Function code 0x02) message
0x01 0x03 0x0C (12‐byte data) (CRC16)
Frame address function data code example
Host CRC check code
structure code code initial switch address number of switches
request
Byte 1 byte 1 byte 2 bytes 2 bytes 2 bytes
23 24
Remark: the initial register address in host inquiry is the initial address of the data (5)Remotely‐controlled multi‐relay output(function code 0x0F)
collected from primary grid or secondary grid. The number of registers indicates the data code
length of the data. In the upper list the register address “0x00 0x06” indicates the frame address function number relay CRC check
initial relay number of
initial address of phase voltage float data of three phases, and the number of register structure code code of data action code
address relay
“0x00 0x06” indicates the length of the data is six words (three float data occupy six byte value
host
registers). byte 1 byte 1 byte 2 bytes 2 bytes 1 byte 1 byte 2 bytes
request
0x0001~
data range 1~247 0x0F 0x0000 0x01 CRC16
0x0004
(4)Remotely‐controlled single relay output(function code 0x05)
message
data code 0x01 0x0F 0x00 0x00 0x00 0x02 0x01 0x03 0x9E 0x96
frame address function CRC check example
initial relay
structure code code relay action value code
frame address function data code CRC check
address
host
structure code code initial relay address number of relay code
byte 1byte 1byte 2 bytes 2 bytes 2 bytes
slave
request
byte 1 byte 1byte 2bytes 2bytes 2 bytes
data range 1~247 0x05 0x0000~0x0003 0xFF00/0x0000 CRC16
response
message 0xD4
message
0x01 0x0F 0x00 0x00 0x00 0x02
0x01 0x05 0x00 0x00 0xFF 0x00 0x8C 0x3A
example 0x0A
example
data code Remark: in the host inquiry, beginning from the lowest bit of relay action value, each
frame address function CRC check
initial relay
bit corresponds to a channel of relay output. “1” indicates the relay is closed, while
structure code code relay action value code
slave address
“0” indicates the relay is open. In the upper list, relay action value “0x03”is “0000
response
0011”in binary system, which means the first and second channels of relay output
byte 1 byte 1 byte 2 bytes 2 bytes 2 bytes
are closed.
message
0x01 0x05 0x00 0x00 0xFF 0x00 0x8C 0x3A
example
(6)Write setup register (function code 0x10)
Data code
Remark: in host request, the relay action value “0xFF00” indicates the relay is closed,
number
Frame Address Functio
while “0x0000” indicates the relay is open. If user wants to perform remotely structure code n code
initial relay Check code
number of relay of data Write
control, please make sure the relay is working in “remotely control” mode. address value
Host byte
reque
st Bytes 1 byte 1 byte 2 bytes 2 bytes 1 byte 2N bytes 2 bytes
Message
0x01 0x10 0x08 0x0A 0x00 0x01 0x02 0x0064 0x2ED1
example
25 26
Data code (a) Remote control mode
Frame Address Funcito In this mode, relay action model must select “Remotely control mode”. Delay is
Check code
structure code n code Register Register length set as electrical level mode or delay time N * 100ms.
Slave initial
respo address
nse (b) Alarm mode
Bytes taken 1 byte 1 byte 2 bytes 2 bytes 2 bytes
In this mode, the relay action must select “Off‐limit alarm mode”, “Item” indicates
Message
example
0x01 0x10 0x08 0x0A 0x00 0x01 0x2ED1 to select electrical variable, “Delay” indicates to set alarm delay time, “Value”
indicates to set alarm threshold value, “Reset” indicates to set hysteresis value.
Remark: Please refer to Appendix 1 MODBUS‐RTU Communication information Item Format Instruction Item Format Instruction
address list when writing setup register. Wrong writing may cause abnormal Un > xxxx V High voltage alarm DI2 ‐‐ Second digital input closed
operation. Please be careful. Un < Low voltage alarm DI2 Second digital input closed
xxxx V ‐‐
5.2 Extreme value and demand open
Meter can record max. and min. value of voltage, current and power. It also can save I > xxxx A High current alarm DI3 ‐‐ Third digital input closed
the extreme values in present month, last month and the month before last. As for I < xxxx A Any phase current alarm DI3 ‐‐ Third digital input open
detailed extreme values information, please refer to communication information DI1 ‐‐ First digital input closed DI4 ‐‐ Fourth digital input closed
list. DI1 ‐‐ First digital input open DI4 ‐‐ Fourth digital input open
Meter can measure the demand of three‐phase current, total active power, total
reactive power and total apparent power. Measurement method of demand can be 6. Common problems and solutions
set through communication. Extreme values and demand only can be read through
Communication
communication but not be shown on the display window.
No return data from the meter
5.3 Digital Input
EK1 module is equipped with four digital inputs. Digital input module adopts dry
First ensure that the meter communication setting information such as slave
node resistance switching signal input mode. The meter is in‐built with +15V
address, baud rate and checkout mode is consistent with the host computer; if
power supply, no need with external power supply available for monitoring fault
there is no data return for communication of many meters at field, please check
alarm node, open and close state, hand‐cart position, capacitance compensation
whether the field communication bus is connected accurately and reliably and
cabinet start state. The information can be sent through communication port to
whether the RS485 converter works normally.
distant smart monitoring system, to realize easily the automatic open or close with
remote control or by alarming relay functions.
Even if there is only single or a few meters have the abnormal communication, the
5.4 Relay output
corresponding communication line shall be checked, which can be tested by
EK1 module has two relay outputs. Relay capacity:AC250V/5A,DC30V/5A.
modifying the exchange of abnormal and normal meter slave addresses, to exclude
The relay output has two work modes: remote control mode and alarm mode.
27 28
or confirm the host computer software issue, or by exchanging the mounting according to the actual field wiring, because the wrong setting can also lead to the
positions of abnormal and normal meters, to exclude or confirm the meter wrong display.
malfunction.
29 30
MODBUS‐RTU Communication information address list 0038‐0039 Float 4# power value kW R
31 32
0072‐0073 Float #11 import total active energy kWh R 00AC‐00AD Float #19 export total active energy kWh R
0074‐0075 Float #12 import total active energy kWh R 00AE‐00AF Float #20 export total active energy kWh R
0076‐0077 Float #13 import total active energy kWh R 00B0‐00B1 Float #21 export total active energy kWh R
0078‐0079 Float #14 import total active energy kWh R 00B2‐00B3 Float Import total active energy kWh R
007A‐007B Float #15 import total active energy kWh R 00B4‐00B5 Float Export total active energy kWh R
007C‐007D Float #16 import total active energy kWh R 00B6‐01FF Reserved
0080‐0081 Float #18 import total active energy kWh R Address Instructio
Format Data content R/W
0082‐0083 Float #19 import total active energy kWh R (HEX) n
0084‐0085 Float #20 import total active energy kWh R 0200‐0201 Float Max. historical voltage value V
0086‐0087 Float #21 import total active energy kWh R 0202‐0203 Float #1 max. historical current value A
0088‐0089 Float #1 export total active energy kWh R 0204‐0205 Float #2 max. historical current value A
008A‐008B Float #2 export total active energy kWh R 0206‐0207 Float #3 max. historical current value A
008C‐008D Float #3 export total active energy kWh R 0208‐0209 Float #4 max. historical current value A
008E‐008F Float #4 export total active energy kWh R 020A‐020B Float #5 max. historical current value A
0090‐0091 Float #5 export total active energy kWh R 020C‐020D Float #6 max. historical current value A
0092‐0093 Float #6 export total active energy kWh R 020E‐020F Float #7 max. historical current value A
0094‐0095 Float #7 export total active energy kWh R 0210‐0211 Float #8 max. historical current value A
0096‐0097 Float #8 export total active energy kWh R 0212‐0213 Float #9 max. historical current value A
0098‐0099 Float #9 export total active energy kWh R 0214‐0215 Float #10 max. historical current value A
009A‐009B Float #10 export total active energy kWh R 0216‐0217 Float #11 max. historical current value A
009C‐009D Float #11 export total active energy kWh R
0218‐0219 Float #12 max. historical current value A
009E‐009F Float #12 export total active energy kWh R
021A‐021B Float #13 max. historical current value A
00A0‐00A1 Float #13 export total active energy kWh R
021C‐021D Float #14 max. historical current value A
00A2‐00A3 Float #14 export total active energy kWh R
021E‐021F Float #15 max. historical current value A
00A4‐00A5 Float #15 export total active energy kWh R
0220‐0221 Float #16 max. historical current value A
00A6‐00A7 Float #16 export total active energy kWh R
0222‐0223 Float #17 max. historical current value A
00A8‐00A9 Float #17 export total active energy kWh R
0224‐0225 Float #18 max. historical current value A
00AA‐00AB Float #18 export total active energy kWh R
0226‐0227 Float #19 max. historical current value A
33 34
0228‐0229 Float #20 max. historical current value A 0262‐0263 Float #6 min. historical current value A
022A‐022B Float #21 max. historical current value A 0264‐0265 Float #7 min. historical current value A
022C‐022D Float #1 max. historical power value kW 0266‐0267 Float #8 min. historical current value A
022E‐022F Float #2 max. historical power value kW 0268‐0269 Float #9 min. historical current value A
0230‐0231 Float #3 max. historical power value kW 026A‐026B Float #10 min. historical current value A
0232‐0233 Float #4 max. historical power value kW 026C‐026D Float #11 min. historical current value A
0234‐0235 Float #5 max. historical power value kW 026E‐026F Float #12 min. historical current value A
0236‐0237 Float #6 max. historical power value kW 0270‐0271 Float #13 min. historical current value A
0238‐0239 Float #7 max. historical power value kW 0272‐0273 Float #14 min. historical current value A
023A‐023B Float #8 max. historical power value kW 0274‐0275 Float #15 min. historical current value A
023C‐023D Float #9 max. historical power value kW 0276‐0277 Float #16 min. historical current value A
023E‐023F Float #10 max. historical power value kW 0278‐0279 Float #17 min. historical current value A
0240‐0241 Float #11 max. historical power value kW 027A‐027B Float #18 min. historical current value A
0242‐0243 Float #12 max. historical power value kW 027C‐027D Float #19 min. historical current value A
0244‐0245 Float #13 max. historical power value kW 027E‐027F Float #20 min. historical current value A
0246‐0247 Float #14 max. historical power value kW 0280‐0281 Float #21 min. historical current value A
0248‐0249 Float #15 max. historical power value kW 0282‐0283 Float #1 min. historical power value kW
024A‐024B Float #16 max. historical power value kW 0284‐0285 Float #2 min. historical power value kW
024C‐024D Float #17 max. historical power value kW 0286‐0287 Float #3 min. historical power value kW
024E‐024F Float #18 max. historical power value kW 0288‐0289 Float #4 min. historical power value kW
0250‐0251 Float #19 max. historical power value kW 028A‐028B Float #5 min. historical power value kW
0252‐0253 Float #20 max. historical power value kW 028C‐028D Float #6 min. historical power value kW
0254‐0255 Float #21 max. historical power value kW 028E‐028F Float #7 min. historical power value kW
0256‐0257 Float Min. historical voltage value V 0290‐0291 Float #8 min. historical power value kW
0258‐0259 Float #1 min. historical current value A 0292‐0293 Float #9 min. historical power value kW
025A‐025B Float #2 min. historical current value A 0294‐0295 Float #10 min. historical power value kW
025C‐025D Float #3 min. historical current value A 0296‐0297 Float #11 min. historical power value kW
025E‐025F Float #4 min. historical current value A 0298‐0299 Float #12 min. historical power value kW
0260‐0261 Float #5 min. historical current value A 029A‐029B Float #13 min. historical power value kW
35 36
029C‐029D Float #14 min. historical power value kW 04D4‐04D5 Float #19 present demand of current A
029E‐029F Float #15 min. historical power value kW 04D6‐04D7 Float #20 present demand of current A
02A0‐02A1 Float #16 min. historical power value kW 04D8‐04D9 Float #21 present demand of current A
02A2‐02A3 Float #17 min. historical power value kW 04DA‐04DB Float #1 present demand of power kW
02A4‐02A5 Float #18 min. historical power value kW 04DC‐04DD Float #2 present demand of power kW
02A6‐02A7 Float #19 min. historical power value kW 04DE‐04DF Float #3 present demand of power kW
02A8‐02A9 Float #20 min. historical power value kW 04E0‐04E1 Float #4 present demand of power kW
02AA‐02AB Float #21 min. historical power value kW 04E2‐04E3 Float #5 present demand of power kW
02AC‐0357 Float #1‐21 extreme values in present month 04E4‐04E5 Float #6 present demand of power kW
0358‐0403 Float #1‐21 extreme values in last month 04E6‐04E7 Float #7 present demand of power kW
04B0‐04B1 Float #1 present demand of current A 04EA‐04EB Float #9 present demand of power kW
04B2‐04B3 Float #2 present demand of current A 04EC‐04ED Float #10 present demand of power kW
04B4‐04B5 Float #3 present demand of current A 04EE‐04EF Float #11 present demand of power kW
04B6‐04B7 Float #4 present demand of current A 04F0‐04F1 Float #12 present demand of power kW
04B8‐04B9 Float #5 present demand of current A 04F2‐04F3 Float #13 present demand of power kW
04BA‐04BB Float #6 present demand of current A 04F4‐04F5 Float #14 present demand of power kW
04BC‐04BD Float #7 present demand of current A 04F6‐04F7 Float #15 present demand of power kW
04BE‐04BF Float #8 present demand of current A 04F8‐04F9 Float #16 present demand of power kW
04C0‐04C1 Float #9 present demand of current A 04FA‐04FB Float #17 present demand of power kW
04C2‐04C3 Float #10 present demand of current A 04FC‐04FD Float #18 present demand of power kW
04C4‐04C5 Float #11 present demand of current A 04FE‐04FF Float #19 present demand of power kW
04C6‐04C7 Float #12 present demand of current A 0500‐0501 Float #20 present demand of power kW
04C8‐04C9 Float #13 present demand of current A 0502‐0503 Float #21 present demand of power kW
04CA‐04CB Float #14 present demand of current A 0504‐0557 Float #1‐21 max. demand in last period
04CC‐04CD Float #15 present demand of current A 0558‐05AB Float #1‐21 max. demand value
04CE‐04CF Float #16 present demand of current A 05AC‐05FF Float #1‐21 max. demand in present month
04D0‐04D1 Float #17 present demand of current A 600‐0653 Float #1‐21 max. demand in last month
04D2‐04D3 Float #18 present demand of current A 654‐06A7 Float #1‐21 max. demand in the month
37 38
before last
06A8‐06FF Reserved
Address Instructio
Format Data content R/W
(HEX) n
The information in this document is subject to changes without any further notice.
JIANGSU SFERE ELECTRIC CO., LTD.
Add: No.1 Dongding Road, Jiangyin, Jiangsu, China.
P.C: 214437
Tel: +86‐510‐86199063 +86‐510‐86199069 +86‐510‐86199073
Email: export@sfere‐elec.com
Website: www.sfere‐elecnova.com
39 40