Professional Documents
Culture Documents
ESP Commissioning Procedure
ESP Commissioning Procedure
CONTENT
1. PURPOSE
2. SCOPE
3. REFERENCE DOCUMENT
5. SAFETY PRECAUTION
6. PREE COMMISSIONING
7. COMMISSIONING TEST
8. INTERLOCK
9. DOSING PHILOSHOPHY
10. ATTACHMENT
PURPOSE
1.2 To check and ensure that electric and I&C interlock, protection and signal devices
can operate correctly.
1.3 Inspect equipment operation and check out system performance. Find and repair
defects that might exist.
1.4 This procedure should be applied for test and commissioning of ESP Boiler unit 1
and 2 PLTU Sebalang Lampung.
1. SCOPE
[Type text]
Commissioning of Electro Static precipitator and its system after the individual test of
all ESP equipment completed. This Commissioning includes mechanical and electrical
equipment test.
2. REFERENCE DOCUMENT
Inlet nozzle are installed between inlet flue gas duct and ESP inlet casing, there are 2
layer of gas distribution screen installed inside inlet nozzle to make flue gas passing
enter the ESP Field as uniform as possible.
Out let nozzle installed at out let line of ESP casing to let the clean flue gas go into
the exhaust flue gas duct
Structural in ESP divided into two portions, electric portion and mechanical portion.
Their main componens and functions are described below :
4.1 Electrical portion
The electrical porttion consist of high voltage DC power source (including its
control system) and low control system.
4.1.1 conventionally we use Model GGAJ02 high voltage power source. Design
of the model is follow :
Such a set of device usually includes high voltage transformer rectifier, auto
control cabinet and reactor of high voltage transformer rectifier and auto
control cabinet. The power source can automatically adjust the voltage applied
to the electric field according to change of gas conditions there in and can
adjust spark ratio in the field to optimum level to the high result of dust
collection can be achieved. This power source is equiped with perfect
interlocking protective system.
4.2.1 Internals
[Type text]
Consist of :
a. Collecting system
b. Emiting System
c. Correcting Rapping System
d. Emiting Rapping System
4.2.2 Casing
Consist of :
a. Inlet Nozzle
b. Outlet Nozzle
c. Roofs
d. Casing
e. Hopper and hopper Ridge beam.
4.2.3 Auxiliaries
Consist of :
a. Stairs and platforms
b. Support Bearings
c. Thermal insulation
d. Earthing
4. SAFETY PRECAUTION
All the commissioning personnel must have the general knowledge of savety and a
special requirement must abide by standard JB6407.
Necessary safety measures before commissioning test :
1. Commissioning condition is qualified, Engineering installation meets requirements of
design and pass acceptance.
2. Relevan test site field is leveling, without sundry, road is clear, normal/accident
lighting is equipped completely
3. There is reliable and rapid communication method
4. Make sure that all personnel leave ESP interior and other HV dangerous area
5. Relevan charged rooms door shall be locked, electrical equipment shall have
obstruction and relevant warning boards shall be hung
6. Fire fighting device shall be arranged according to relevant provision
[Type text]
6. PREE COMMISSIONING
Installation, Check and adjustment of equipment
6.1. The installation of equipment should met the requirements ESP Isntallation manual.
6.2. Check and adjustment of equipment
Respective check and adjustment should made to the electric and mechanical portion
After equipment erected prior to it being to put into operations.
7. COMMISSIONING TEST
7.1 Tested items and specific operation
7.1.1 Dummy Load test
7.1.2 Protection punction test
- Safety interlock protection
- Short circuit protection test
- Open – circuit protection test
- Oil temperatureprotection test
- Gas protection test
Make sure that motor running direction is accurate when rapper motor is energized
and test running. Make sure that it is in good waiting operation condition after
operating for 2 hours.
- Test conditions
1. Throught inspection and commissioning of above item ands reach
requirement of commissioning.
2. Its not rainy, foggy or strongly windy
3. Make sure that all person have left field andother HV areas
4. All the manhole door are locked and safety measures area implemented.
- Test Procedure
1. Organize relevan personnel about test andsafety supervisory personnel. There
shall be special assigned person to supervision at the position ofmanhole door
and HV inducting insulated switch.
2. Make sure that its commanded unitedly by commander in chief, assign duty
for each person and its implemented term by term.
3. Put insulator heating system into action (8 hours in advance)
4. Start firstly and then close fan after nature air passing throught field, so as to
remove ozone, moisture and etc.
5. Do static no loac field voltage rising test firstly and then go on dynamic no
load field voltage rising commissioning.
- Test contents
[Type text]
At the static and dynamic condition, measure voltage value of each field atdifferent
secondary current separately and draw V – I characteristic curve.
Heteropole distance
[Type text]
8. INTERLOCK
a. Flow, Temperature and Pressure
a) Inlet Flow meter – the inlet flow meter can detect that the flow is in the correct
range. Should the flow fall out of the correct range the rectifier should shut
down immediately followed by the rest of the system.
b) Flow Switch on outlet of electrolyser – should the inlet flow meter be
indicating the correct inlet flow but the flow switch on the outlet detecting no /
low flow, the rectifier should shut down immediately followed by the rest of
the system. This could indicate a burst pipeline somewhere downstream of the
main flow meter and/or a faulty inlet flow signal.
c) High Outlet Temperature – a high outlet temperature may mean the flow has
dropped below a certain level and/or stopped completely. With the rectifier
running in a low flow situation heat will very quickly develop in the
electrolyser cells. The rectifier should shut down immediately followed by the
rest of the system.
d) High Differential Temperature – a high differential temperature (inlet to outlet)
may mean the flow has dropped below a certain level and/or stopped
completely. With the rectifier running in a low flow situation heat will very
quickly develop in the electrolyser cells. The rectifier should shut down
immediately followed by the rest of the system.
e) High Inlet Temperature – this is not normally a problem on seawater systems,
however, the inlet temperature should be below a certain point to prevent
deformation of the PVC pipework. If over a certain level the rectifier should
shut down immediately followed by the rest of the system.
Point List
b. Rectifier Alarm
- Rectifier Key Switch Change (if the system already running)
Action :
[Type text]
“Rectifier shut down, Seawater Booster Pumps and run flush 20 seconds
then stop, Alarm on HMI Rectifier Key Switch Change Position & EC Plant
Failed”
- Rectifier Thyristor Over temperature, Rectifier Phase Failure, Rectifier Fan
Failure, Rectifier Door Open, Rectifier over voltage, Rectifier Transformer
Over temperature, Rectifier Over Current trip.
Action :
“If rectifier not running – Appropriate Alarm on HMI”
“If rectifier is running ‐ Rectifier shut down, Seawater Booster Pumps run and
flush 20 seconds then stop, Alarm on HMI Rectifier Key Switch Change
Position & EC Plant Failed and appropriate Alarm on HMI”
d. Chlorine Analyzer
The chlorine analyzer will be transmitted to the PLC and system will try and
maintain set point of CI2 residual at concentrate 0,2% (2000 mg/l) of NaOCL by
varying the current output from the rectifier for electrolyser and manipulated dosing
rate of the dosing pump (Variable Speed Drive)
[Type text]
9. DOSING PHILOSOPHY
a. Normal Dosing
The required normal dosing rate is 1.2 ppm, one dosing pump will be running on the
variable speed drive at pumping capacity of 27.029 m³/hr to maintain 1.2ppm.
b. Shock Dosing
The shock dosing philosophy will be 3 times per day for 15 minutes to a level
4ppm,and time between for shock dosing is 8 hours.
The shock dosing will be drawn from the storage tank by running 2 of the dosing
pumps in parallel, to reach 90.096 m³/hr in 15 minutes of CI2.
Variable speed drive at dosing pump will take each pump to pumping output
capacity of 90.096 m³/hr / 2 = 45.048 m³/hr each dosing pumps.
b. RECTIFIER
Serial no : 10227
Manufactured : AET ELECTRIC Pte LTD.
Rated Power : 308 Kw
AC Input Voltage : 380 V
AC Input Current : 400 A
DC Output Voltage : 81 V
DC Output Current : 3800 A
Pump
Manufacture : Corro Pump SA.
Type : Centrifugal
Head : 40 m
Capacity : 43 m³/hr
Pump
Manufacture : Corro Pump SA
Type : Centrifugal
Head : 21 m
Capacity : 50 m³/hr
11. ATTACHMENT