Professional Documents
Culture Documents
Adaptive Control Strategy For Frequency Support From MTDC Connected Offshore Wind Power Plants
Adaptive Control Strategy For Frequency Support From MTDC Connected Offshore Wind Power Plants
Abstract—Grid integration of large-scale power electronic in- a major real-life example of remote OWFs integration into the
terfaced renewable energy sources leads to a low inertia system, mainland grids in Europe [1]. However, displacement of conven-
thus resulting in a high rate of change of frequency (RoCoF) tional generation due to large-scale wind integration results in
and frequency deviations in the power system following a credible
contingency. In this article, a realistic adaptive communication- diminishing system inertia. System operators/regulators, there-
independent control strategy for effective inertial and primary fore, mandate frequency support capability from wind farms
frequency support from multiterminal HVDC (MTDC) connected through grid code regulations (GCRs) for stable and secure
offshore wind farms (OWFs) has been proposed. The proposed power system operation. For example, GCRs require inertial
strategy can identify and distinguish the grid under disturbance and primary frequency support capability from OWFs during a
among the other healthy grids in the MTDC system by an adaptive
droop frequency support (ADFS) scheme at each receiving end con- frequency disturbance [2], [3], [4]. However, HVDC-connected
verter (REC). On the OWF side, the control system of wind turbine OWFs cannot inherently sense the onshore grid frequency de-
generators has been designed to coordinate with the ADFS scheme viations because of the HVDC link and wind turbine generator
to comply with the grid code regulations (GCRs) for inertial and (WTG) converters that interface WTGs in the offshore grid and
primary frequency support. The proposed ADFS control scheme the main grid. Therefore, due to such a nonsynchronous link
ensures that while providing frequency support to the grid under
disturbance, frequency deviation limits of the healthy neighboring (HVDC and WTG converters), WTGs in the OWF cannot inher-
grids are not breached. Moreover, the proposed strategy complies ently support the main grid in frequency recovery. To address
adequately with the maximum permissible limits of HVDC voltage this issue, several strategies have been proposed in the literature
deviation. Furthermore, the proposed strategy is dependent on that require frequency signals measured at the onshore site to be
only local measurements and can be easily customized to comply communicated to the offshore site through a physical medium of
with any applicable GCR. The reliability and effectiveness of the
proposed robust control strategy have been demonstrated on three communication. The main limitations of such communication-
power systems interconnected through the MTDC system to two dependent strategies are low reliability and communication la-
OWFs. tency. Therefore, to address the limitations of communication-
Index Terms—Adaptive droop frequency support (ADFS), grid
dependent strategies, several strategies that are communication-
code regulations (GCRS), multiterminal HVDC (MTDC), offshore independent have been reported in the literature [5], [6], [7], [8],
wind farms (OWFs). [9], [10], [11], [12], [13], [14], [15], [16], [17], [18].
In addition to the challenges in point-to-point HVDC
I. INTRODUCTION (PP-HVDC) connected OWFs, the additional issues in
FFSHORE wind farms (OWFs) are considered one of the multiterminal HVDC (MTDC) connected OWFs are to
O promising sources of wind energy, primarily due to high
wind speed in the offshore site and saturation of the available
identify and distinguish the grid with disturbance from the
other healthy interconnected ac areas and coordinate frequency
mainland. The planned offshore supergrid in the Nordic Seas is support from OWFs to the target grid through the MTDC system
interconnecting multiple ac areas. Zhu et al. [5] proposed an
inertial emulation control strategy to support the onshore grid
Manuscript received 9 May 2022; revised 20 August 2022; accepted 20
October 2022. Date of publication 27 October 2022; date of current version 26 frequency from the energy stored in the capacitor banks of
December 2022. This work was supported by the India-EU collaborative project the PP-HVDC system. Zhu et al. [6] extended the inertial
SUSTENANCE funded by the Department of Science and Technology (DST) on emulation control strategy for PP-HVDC topology in [5] to
the Indian side and the European Commission on the EU side. Recommended for
publication by Associate Editor Z. Chen. (Corresponding author: Muhammad the MTDC topology. However, the two main limitations of
M. Kabsha.) the control strategies reported in [5] and [6] are the need for
Muhammad M. Kabsha is with the Indian Institute of Technology Bombay, large capacitor banks connected at the receiving end converters
Mumbai 400076, India, and also with the Faculty of Engineering, Mansoura Uni-
versity, Mansoura 35516, Egypt (e-mail: muhammad_kabsha@mans.edu.eg). (RECs) and large voltage deviations in the MTDC system. The
Zakir Hussain Rather is with the Indian Institute of Technology Bombay, OWFs can, however, support onshore grid frequency through
Mumbai 400076, India (e-mail: zakir.rather@iitb.ac.in). emulated inertial and primary frequency response from WTGs.
Color versions of one or more figures in this article are available at
https://doi.org/10.1109/TPEL.2022.3217712. For example, the study in [7] proposed frequency droop control
Digital Object Identifier 10.1109/TPEL.2022.3217712 implemented at the RECs, sending end converters (SECs) and
0885-8993 © 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on August 13,2023 at 06:52:01 UTC from IEEE Xplore. Restrictions apply.
3982 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 38, NO. 3, MARCH 2023
the offshore WTGs to enable the OWF to sense the onshore TABLE I
COMPARATIVE ANALYSIS OF DIFFERENT STRATEGIES
disturbance events, and hence provide frequency support to the
main grid from the PP-HVDC connected OWF.
Silva et al. [8] extended the fixed droop frequency sup-
port (FDFS) control strategy in [7] for the MTDC-connected
OWFs. However, the FDFS strategy in [8] ignored the GCRs
requirements. In addition, the local frequency deviation limits
of the different ac areas interconnected through the MTDC
system were not considered, whereas the MTDC permissible
voltage deviation limits have been ignored. Moreover, under the
conventional FDFS strategy, the HVDC voltage deviations are
mapped to offshore grid frequency variations, which actually
result in a high rate of change of frequency (RoCoF) and large
frequency deviations in the offshore grid. Rafferty et al. [9]
proposed a frequency support strategy for MTDC-connected very high RoCoF values in the offshore grid would be required
OWFs using HVDC voltage variation. However, this approach to provide an adequate inertial response from WTGs.
has ignored the GCRs, and the local frequency deviation limits Kumar et al. [17] proposed a hybrid frequency droop scheme
were ignored, whereas the MTDC permissible voltage devi- implemented at the bipolar RECs to improve power sharing
ation limits were not considered. Moreover, the study in [9] and frequency stability at the onshore grids following ac and
has tested the proposed strategy on a simple MTDC grid with dc disturbance events. However, the main limitation of the
oversimplified models of onshore ac grids while ignoring power strategy in [17] is using the master–slave control philosophy
system dynamics. Sakamari et al. [10] proposed a frequency while modeling one of the onshore grids as a strong grid, thereby
support strategy similar to the strategies reported in [8] and ignoring the real grid dynamics.
[9] while considering the second frequency nadir in the main All the communication-independent frequency support strate-
grid. However, the strategy in [10] did not consider the GCRs gies for the MTDC-connected OWFs did not consider the HVDC
at the onshore grids and ignored the maximum dc permissible voltage deviation limits in the MTDC grid and the GCRs com-
voltage deviation limits at the MTDC grid. Adeuyi et al. [11] pliance in the main ac areas connected to the MTDC system
proposed a frequency support strategy by modifying the strategy [5], [6], [7], [8], [9], [10], [11], [12], [13], [14], [15], [16], [17].
in [8], where f–P supplementary droop control (instead of f–V In addition, all the above-reported communication-independent
droop) has been used at RECs to provide enhanced primary strategies translate the HVDC voltage deviations to offshore grid
frequency support while using V–f droop control at the SECs frequency variations, which actually result in a high RoCoF and
similar to that in [8]. However, the strategy reported in [11] large frequency deviations in the offshore grid. To provide iner-
has ignored the GCRs and the real power system dynamics tial and primary frequency support from PP-HVDC-connected
while modeling one of the onshore grids as an infinite bus OWF. Kabsha and Rather [18] proposed an offshore ac voltage
(strong grid). Jose et al. [12] modified the control strategy regulation based frequency support strategy. However, the focus
developed in [11] by using logic control based supplementary of the study was only on PP-HVDC-connected OWF. A com-
control schemes at RECs to enhance the frequency support from parison table of the above-discussed strategies is presented in
MTDC-connected OWFs. However, the main limitation of the Table I.
strategy reported in [12] is that the authors modeled one of Therefore, in this backdrop, a new realistic communication-
the onshore grids as an infinite bus (strong grid), thus ignoring independent strategy is proposed in this article for effective
the system dynamics and its influence on the proposed control frequency support provision from MTDC-connected OWFs. The
strategy. Wang et al. [13], [14] proposed control strategies for proposed strategy consists of two control stages, the first one is
frequency support to the disturbed onshore grid from the other at the WTGs, where all the OWFs can comply with GCRs for
onshore grids connected through the MTDC grid, however, the frequency support based on offshore voltage regulation. The
GCRs have been ignored, and the frequency support provision second stage at the RECs considers the GCRs at the onshore
from the OWFs was not considered in these strategies. Yang grids and the permissible limits of voltage at the MTDC grid
et al. [15] proposed a control scheme for the MTDC RECs to by using only one adaptive coefficient at the droop control
provide frequency support without using a phase-locked loop of each REC. Moreover, the proposed strategy can be easily
(PLL). However, for the strategy reported in [15], the frequency customized to fit any applicable GCRs by providing the flex-
support provision from the healthy grids to the disturbed grid ibility of parameters setting to the different grid operators at
is not adequate. The strategy in [15] has the primary advantage the different onshore ac areas. So, every grid operator can set
of the PLL-free feature. Zhong et al. [16] proposed a virtual the parameters setting which is not feasible with conventional
capacitor control scheme implemented at SECs to enhance the communication-independent strategies.
inertial frequency support from the MTDC-connected OWFs, This article is structured as follows: In Section II, frequency
where the inertial control function shifted from the offshore support regulations imposed on OWFs are summarized. In Sec-
WTGs to SECs. However, for the strategy reported in [16], the tion III, offshore wind power plant modeling including the test
inertial frequency support to the disturbed grid is not effective as system and modeling of OWFs and associated control system is
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on August 13,2023 at 06:52:01 UTC from IEEE Xplore. Restrictions apply.
KABSHA AND RATHER: ADAPTIVE CONTROL STRATEGY FOR FREQUENCY SUPPORT FROM MTDC 3983
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on August 13,2023 at 06:52:01 UTC from IEEE Xplore. Restrictions apply.
KABSHA AND RATHER: ADAPTIVE CONTROL STRATEGY FOR FREQUENCY SUPPORT FROM MTDC 3985
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on August 13,2023 at 06:52:01 UTC from IEEE Xplore. Restrictions apply.
3986 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 38, NO. 3, MARCH 2023
∗
where Voff,i and Voff0,i are, respectively, the reference and the
nominal ac voltage for offshore grid connected to the ith SEC,
Kv,i is ac voltage droop coefficient at the ith SEC, and Vdcoff,i
and Vdc0,i are, respectively, the measured and the nominal dc
voltage at the ith SEC.
The WTGs in each OWF can provide an inertial response
based on the rate of change of voltage (RoCoV) of offshore grid
as given by
dVmeas
ΔPin = Kin (9)
dt
where Kin is the voltage inertial gain, and Vmeas is the measured
WTG terminal voltage.
It is important to mention that by using a voltage regulation-
based approach in the offshore ac grid, high RoCoF and fre-
quency nadir in the offshore grid are avoided, as WTGs provide
an inertial response based on RoCoV instead of RoCoF used in
the conventional strategies as shown in Fig. 6.
In the proposed strategy, the WTGs follow the primary fre-
quency support requirements imposed by ENTSO-E GCR as
defined in the following equation:
ΔPprim = (Vref − Vmeas ) ∗ Kprim ∗ PMPPT (10) Fig. 7. Dominate eigenvalues locus with variation in adaptive frequency droop
coefficient from 0 to 7.5.
where ΔPprim is the scheduled active power for primary fre-
quency support, Vref and Vmeas are, respectively, the reference A. Modal Analysis
and the measured ac voltage at the WTG terminal, Kprim is the The modal/eigenvalue analysis has been performed to com-
voltage droop gain, and PMPPT is the maximum WTG active pute the eigenvalues for small signal stability analysis of the test
power at the available wind speed. system, with eigenvalues plotted in Fig 7.
The active power command fed to each WTG GSC control The adaptive frequency droop coefficient Kf∗ v,i is the critical
system is given by parameter in the proposed control strategy. Therefore, the modal
Pref = ΔPin + ΔPprim + PMPPT ∗ del (11) analysis has been conducted to evaluate the impact of Kf∗ v,i on
the system stability. The value of Kf∗ v,i is changed from 0 to 7.5,
where ΔPin and ΔPprim are, respectively, the inertial and pri- and the dominant eigenvalues movements with the variations of
mary active power of the proposed strategy, and del is the active Kf∗ v,i are shown in Fig. 7.
power deloading factor. The blue color arrows point to the dominant eigenvalue trace
In this study, the de-loaded operation of WTGs has been as Kf∗ v,i varies from 0 to 7.5. When Kf∗ v,i increases, some
adapted to maintain active power reserve for primary frequency eigenvalues (λ5 , λ6 , λ11 λ12 , λ48 , λ49 , λ59 , λ60 ) move to the left
support from OWFs. In accordance with ENTSO-E GCR, the half of the s-plane and the damping ratio increases. However,
reserve active power in each WTG is controlled such that 10% there are two modes (λ68, λ69) that moved toward the left and
active power reserve is released for 0.5 Hz frequency deviation reached an inflection point at Kf∗ v,i equal to 0.95, following
at the disturbed onshore grid [2]. which the two oscillating modes move toward the right half
of the s-plane. There are some oscillations modes (λ3, λ4), and
V. RESULTS AND DISCUSSIONS (λ108, λ109) that have complex movements as shown in Fig. 7(e)
To evaluate the superiority of the proposed ADFS strategy, and (g). For higher values of Kf∗ v,i > 0.55, the eigenvalues (λ3,
both the conventional FDFS and the proposed ADFS strategies λ4) start moving to the right half of the s-plane before reaching
have been implemented on the MTDC system interconnecting the first inflection point and start moving to the left and reach
two OWFs and three main ac grids as shown in Fig. 4, with more again to the second inflection point at Kf∗ v,i value of 1.6 for (λ3,
details provided in Section III. The proposed ADFS and the λ4). On the other hand, the oscillating modes (λ106, λ107) are
conventional FDFS strategies have been tested under different the most critical and move to the right half of the s-plane, and
scenarios, such as overfrequency and underfrequency events, an the damping ratio decreases, however, the two modes’ values
SEC outage, a REC outage, and multiple frequency events at the saturated at high values of Kf∗ v,i as shown in Fig. 7(d). In this
onshore ac areas to evaluate their frequency support performance study, the values of Kf∗ v,i are limited at 7.5 to ensure system
while considering permissible limits of the MTDC voltage and stability, however, the actual value of Kf∗ v,i did not exceed 0.5
compliance with the GCRs in all the MTDC interconnected in all the test cases considered for this study. It can be concluded
ac areas. While case studies with underfrequency events are that, the test system under the proposed strategy has enough
discussed in Section V-B and Section V-C, the other case studies, stability margin. This conclusion is verified by the simulation
such as overfrequency, SEC, or REC station outage, have shown results in Section V-B and Section V-C with the proposed control
a similar trend as that of the presented case studies. strategy under different disturbances events.
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on August 13,2023 at 06:52:01 UTC from IEEE Xplore. Restrictions apply.
KABSHA AND RATHER: ADAPTIVE CONTROL STRATEGY FOR FREQUENCY SUPPORT FROM MTDC 3987
Fig. 8. Case study A. (a) Onshore grid 1 frequency. (b) Onshore grid 2 Fig. 9. Case study A. (a) REC-1 active power. (b) REC-2 active power.
frequency. (c) Onshore grid 3 frequency. (d) RoCoF of onshore grid 1. (e) RoCoF (c) REC-3 active power. (d) Variation of the adaptive droop coefficient at REC-1.
of onshore grid 2. (f) RoCoF of onshore grid 3. (e) OWF-1 active power. (f) OWF-2 active power.
B. Case Study A
OWFs contribute both the inertial and the primary frequency
In this case study, a load step change of 17% at all the response.
load buses of the IEEE 39 bus system is applied to simulate The active power import by three ac areas at their respective
an underfrequency event. Onshore ac grids performance under RECs, and the OWFs active power output at SECs side in all the
the proposed ADFS strategy in all four studied cases (case I: four cases are shown in Fig. 9. It can be observed that the OWFs
no frequency support from OWFs; case II: primary frequency follow the ENTSO-E GCR for primary frequency support, as
assistance from OWFs; case III: inertial response from OWFs; the entire WTGs active power reserve of 10% is exhausted
and case IV: both primary and inertial frequency response from for onshore frequency deviation of −0.5 Hz. The OWFs active
OWFs) is shown in Fig. 8. power output increased from 1284 MW to 1427 MW under case
The onshore grid frequencies of the IEEE 39 bus system II (primary frequency support) as shown in Fig. 9(e) and (f).
(grid 1), 118 bus system (grid 2), and 9 bus system (grid 3) The active power exported to grid 2 and grid 3 under all the
without OWFs frequency provision are shown as a solid red four cases decreased to provide frequency support to grid 1 as
line in Fig. 8(a)–(c), respectively. It can be observed that the shown in Fig. 9(a)–(c). It is important to note that in this study,
corresponding frequency nadirs of the three ac areas under case it is assumed that the other neighboring ac areas (grid 2 and
I are 48.88 Hz, 49.05 Hz, and 49.03 Hz, whereas their respective grid 3) are expected to provide frequency support to the grid
values of maximum RoCoF are −0.544 Hz/s, −0.582 Hz/s, and experiencing frequency disturbance (grid 1), either through prior
−0.673 Hz/s as shown Fig. 8(d)–(f). In case II (with only OWFs agreed contract or through ancillary service market. However,
primary frequency provision), the respective frequency of the the frequency support from neighboring ac areas (grid 2 and
three onshore ac areas are shown as the dashed green line in grid 3) is limited by their local limits of frequency deviation.
Fig. 8(a)–(c). Therefore, the proposed adaptive control strategy is designed
It is realized that with primary frequency support from OWFs such that while supporting the grid with frequency disturbance
(case II), frequency nadir and maximum RoCoF in all three (grid 1), local frequency limits in the neighboring ac areas (grid
ac areas have enhanced with their respective values of 49.29 2 and grid 3) are not breached. It can be observed from Fig. 8(b)
Hz, 49.33 Hz, 49.31 Hz, and −0.512 Hz/s, −0.453 Hz/s, and (c), frequency of grid 2 and grid 3 do not breach the lower
−0.524 Hz/s. Results for case III (with only inertia support) frequency limit (49 Hz). The proposed controller can be easily
shown in Fig. 8(a)–(c) suggest that while frequency nadir of the customized to block any frequency support from neighboring
three ac areas (49.022 Hz, 49.071 Hz, 49.04 Hz) are better than grids if required so, and the results in such cases will show
those under case I, case II shows better performance than that similar trend in terms of frequency response in the disturbed
of case III in terms of frequency nadir. This can be attributed to grid, however, without affecting frequency of the neighboring
the absence of primary frequency response from OWFs in case grids. It has been observed from Fig. 9(d) that under ADFS
III. However, the maximum RoCoF in the three grids under case strategy, the maximum value of the adaptive droop coefficient
III (−0.477 Hz/s, −0.355 Hz/s, −0.42 Hz/s) have been further REC
KU,i at the RECs did not exceed 0.35. Therefore, the system is
improved compared to case II, which is due to inertial response stable with the proposed strategy under the different frequency
provided by OWFs in case III. support from the OWFs.
Results for case IV (OWFs provide both primary and inertial Fig. 10(a) and (b) shows that under the proposed strategy, the
frequency response), which include frequency nadir (49.414 Hz MTDC voltage deviation is translated to ac voltage deviations
in grid 1, 49.446 Hz in grid 2, 49.43 Hz in grid 3) and respective in OWF-1 offshore grid for all four cases. At the onset of
maximum RoCoF (−0.472 Hz/s, −0.306 Hz/s, −0.352 Hz/s) the frequency event, offshore ac voltage increases suddenly to
observed in all the three ac areas are the best among all the four activate inertial frequency support from WTGs, however, during
cases, as shown in Fig. 8. This is primarily because in case IV, the inertial support, offshore ac voltage does not breach the set
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on August 13,2023 at 06:52:01 UTC from IEEE Xplore. Restrictions apply.
3988 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 38, NO. 3, MARCH 2023
Fig. 10. Case study A. (a) REC-1 DC voltage. (b) Offshore grid 1 AC voltage. Fig. 11. Comparative study 1. (a) Onshore grid 1 frequency. (b) Onshore
(c) OWF-1 WTGs rotational speed. (d) REC-2 DC voltage. (e) Offshore grid 2 grid 2 frequency. (c) Onshore grid 3 frequency. (d) RoCoF of onshore grid 1.
AC voltage. (f) OWF-2 WTGs rotational speed. (e) RoCoF of onshore grid 2. (f) RoCoF of onshore grid 3.
Fig. 12. Comparative study 1. (a) REC-1 active power. (b) REC-2 active power.
C. Comparative Analysis of the Proposed Strategy and (c) REC-3 active power. (d) Variation of the adaptive droop coefficients at RECs.
Conventional Strategies (e) OWF-1 active power. (f) OWF-2 active power.
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on August 13,2023 at 06:52:01 UTC from IEEE Xplore. Restrictions apply.
KABSHA AND RATHER: ADAPTIVE CONTROL STRATEGY FOR FREQUENCY SUPPORT FROM MTDC 3989
Fig. 14. Comparative study 2. (a) Onshore grid 1 frequency. (b) Onshore grid
Fig. 13. Comparative study 1. (a) REC-1 HVDC voltage. (b) Offshore grid
2 frequency. (c) Onshore grid 3 frequency. (d) REC-1 active power. (e) REC-2
1 AC voltage. (c) OWF-1 WTGs rotational speed. (d) REC-2 HVDC voltage.
active power. (f) REC-3 active power.
(e) Offshore grid 2 AC voltage. (f) OWF-2 WTGs rotational speed.
from the healthy grids (grid 2 and grid 3) is limited by their local
limits of frequency deviation (1 Hz). It can also be concluded
from Fig. 12(d) that the maximum value of the adaptive droop
REC
coefficient KU,i at the different RECs did not exceed 0.35.
At the onset of frequency deviation detected by RECs, the
MTDC voltage is suddenly reduced, thus translating onshore
frequency deviation to MTDC voltage deviation, which in turn is
translated by SEC-1 to ac voltage deviation in the offshore grid,
as shown in Fig. 13(a) and (b) for OWF-1. It can be realized
from Fig. 13(a), that under the conventional FDFS strategy,
MTDC voltage deviation exceeds the maximum permissible
limit (±0.15 p.u.) considered in this study. On the other hand,
under the proposed ADFS strategy, the adaptive controller does Fig. 15. Comparative study 2. (a) SEC-1 HVDC voltage. (b) Offshore grid 1
not allow MTDC voltage to breach the voltage deviation limit, AC voltage. (c) OWF-1 WTGs rotational speed. (d) Variations of the adaptive
hence limiting it to 0.85 p.u., as shown in Fig. 13(a). It has been droop coefficients at RECs. (e) OWF-1 active power. (f) OWF-2 active power.
observed that under the ADFS strategy, the HVDC voltage drop
and the offshore ac voltage rise rates are slightly higher than It can be observed from Fig. 14(a)–(c) that under the conven-
that in the FDFS strategy, hence the WTGs inertial response tional strategy (Conv-2), the frequency deviation in the disturbed
is also slightly fast in ADFS, as can be observed from the grid (grid 1) breached the lower limit of 1 Hz. On the other
WTGs rotational speed shown in Fig. 13(c). The performance hand, the neighboring (healthy) ac areas (grid 2 and grid 3)
of OWF-2, which is similar to that of OWF-1 is shown in cannot provide sufficient frequency support to the disturbed
Fig. 13(d)–(f). grid, even though the frequency deviation at grid 2 and grid
2) Comparative Study 2: In the comparative study 2, the 3 has a sufficient margin from the frequency deviation limit
proposed ADFS strategy is compared with the PLL-free control- of 1 Hz in the respective grids. On the other hand, under the
based conventional strategy (Conv-2). Under the PLL-free con- proposed ADFS strategy, the frequency nadir in the grid with
trol strategy, a new control scheme is implemented at the RECs, disturbance (grid 1) is effectively improved, which is attributed
which is similar to the control scheme implemented at SECs to the relatively higher frequency support from the healthy ac
shown in Fig. 3. However, the control scheme at the RECs is areas (grid 2 and grid 3) under the proposed strategy, however,
working in the P-Q mode. The main advantage of this strategy without breaching the local frequency limits in their respective
is that the RECs can provide frequency support to the disturbed grids (grid 2 and grid 3). It is important to note that in the
onshore grid without using PLL at RECs. However, in this proposed strategy, the local frequency deviation limit setpoint
strategy, the frequency support provision from the healthy grids can be easily customized. Therefore, the primary frequency
to the disturbed grid is not adequate. Moreover, the strategy support from the healthy grids is under full control, which is
(Conv-2) considered only the inertial response from OWFs, not feasible in the conventional strategy (Conv-2).
whereas the primary frequency support from OWFs was ignored. Under the proposed strategy (ADFS), the HVDC voltage
An underfrequency event is realized by a load step increase deviation at the MTDC grid during the onshore frequency devi-
of 15% at all the load buses of grid 1. For a fair comparison with ation is induced by the RECs to emulate the onshore frequency
the conventional strategy (Conv-2), only the inertial frequency deviation. This results in a fast inertial response at the offshore
support is considered at OWFs under the proposed strategy. WTGs as shown in Fig. 15(e) and (f). On the other hand,
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on August 13,2023 at 06:52:01 UTC from IEEE Xplore. Restrictions apply.
3990 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 38, NO. 3, MARCH 2023
Fig. 16. Comparative study 3. (a) Onshore grid 1 frequency. (b) Onshore grid
2 frequency. (c) Onshore grid 3 frequency. (d) REC-1 active power. (e) REC-2
active power. (f) REC-3 active power.
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on August 13,2023 at 06:52:01 UTC from IEEE Xplore. Restrictions apply.
KABSHA AND RATHER: ADAPTIVE CONTROL STRATEGY FOR FREQUENCY SUPPORT FROM MTDC 3991
ADFS strategy, OWFs can provide inertial and primary fre- [19] E. Ela, V. Gevorgian, A. Tuohy, B. Kirby, M. Milligan, and M. O’Malley,
quency support based on offshore ac voltage regulation without “Market designs for the primary frequency response ancillary service—
Part I: Motivation and design,” IEEE Trans. Power Syst., vol. 29, no. 1,
experiencing any frequency deviations and high RoCoF in the pp. 421–431, Jan. 2014.
offshore grids. The results of the various case studies show that [20] E. Ela, V. Gevorgian, A. Tuohy, B. Kirby, M. Milligan, and M. O’Malley,
the proposed ADFS strategy is a realistic strategy for frequency “Market designs for the primary frequency response ancillary service—
Part II: Case studies,” IEEE Trans. Power Syst., vol. 29, no. 1, pp. 432–440,
support from MTDC-connected OWFs, which can be imple- Jan. 2014.
mented on offshore wind power plants connected to MTDC [21] A. B. Attya, J. L. Dominguez-Garcia, and O. Anaya-Lara, “A review on
systems without stressing the onshore grids, the MTDC grid, frequency support provision by wind power plants: Current and future
challenges,” Renewable Sustain. Energy Rev., vol. 81, pp. 2071–2087,
and the offshore grids. Jan. 2018.
[22] P. Fernández-Bustamante, O. Barambones, I. Calvo, C. Napole, and M.
Derbeli, “Provision of frequency response from wind farms: A review,”
REFERENCES Energies, vol. 14, no. 20, Oct. 2021, Art. no. 6689.
[1] J. G. Dedecca and R. A. Hakvoort, “A review of the North Seas offshore [23] C. H. Lin and Y. K. Wu, “Overview of frequency-control technolo-
grid modeling: Current and future research,” Renewable Sustain. Energy gies for a VSC-HVDC-integrated wind farm,” IEEE Access, vol. 9,
Rev., vol. 60, pp. 129–143, Jul. 2016. pp. 112893–112921, 2021.
[2] European Commission Regulation, “Establishing a network code on re- [24] F. Teng and G. Strbac, “Assessment of the role and value of frequency
quirements for grid connection of high voltage direct current systems and response support from wind plants,” IEEE Trans. Sustain. Energy, vol. 7,
direct current connected power park modules,” Official J. Eur. Union, no. 2, pp. 586–595, Apr. 2016.
vol. 59, no. 241, pp. 1–65, Aug. 2016. [25] M. Rajabdorri, L. Sigrist, E. Lobato, M. del Carmen Prats, and F. M.
[3] TenneT TSO GmbH, “Requirements for offshore grid connections in the Echavarren, “Viability of providing spinning reserves by RES in Span-
grid of TenneT TSO GmbH,” TenneT TSO GmbH, Bayreuth, Germany, ish island power systems,” IET Renew. Power Gener., vol. 15, no. 13,
2012. pp. 2878–2890, 2021.
[4] National Grid Electricity Transmission, “The grid code,” Nat. Grid Electr. [26] A. Aziz et al., “Frequency regulation capabilities in wind power plant,”
Transmiss., London, U.K., Issue 5, Revision 46, Nov. 2020. Sustain. Energy Technol. Assessments, vol. 26, pp. 47–76, 2018.
[5] J. Zhu, C. D. Booth, G. P. Adam, A. J. Roscoe, and C. G. Bright, “Inertia [27] K. Clark, N. W. Miller, and J. J. Sanchez-Gasca, “Modeling of GE wind
emulation control strategy for VSC-HVDC transmission systems,” IEEE turbine-generators for grid studies,” General Electric Int., Inc., Schenec-
Trans. Power Syst., vol. 28, no. 2, pp. 1277–1287, May 2013. tady, NY, USA, Rep. no. 4.5, 2010.
[6] J. Zhu et al., “Generic inertia emulation controller for multi-terminal [28] M. Pöller and S. Achilles, “Aggregated wind park models for analyzing
voltage-source-converter high voltage direct current systems,” IET Re- power system dynamics,” in Proc. 4th Int. Workshop Large-Scale Integr.
newable Power Gener., vol. 8, no. 7, pp. 740–748, 2014. Wind Power Transmiss. Netw. Offshore Wind Farms, 2003, pp. 1–10.
[7] Y. Phulpin, “Communication-free inertia and frequency control for wind [29] S. Dennetière et al., “The CIGRE B4 DC grid test system,” CIGRE Electra
generators connected by an HVDC-link,” IEEE Trans. Power Syst., vol. 27, Mag., 2013.
no. 2, pp. 1136–1137, May 2012. [30] P. Demetriou, M. Asprou, J. Quiros-Tortos, and E. Kyriakides, “Dynamic
[8] B. Silva, C. L. Moreira, L. Seca, Y. Phulpin, and J. A. Pecas Lopes, “Pro- IEEE test systems for transient analysis,” IEEE Syst. J., vol. 11, no. 4,
vision of inertial and primary frequency control services using offshore pp. 2108–2117, Dec. 2017.
multiterminal HVDC networks,” IEEE Trans. Sustain. Energy, vol. 3, no. 4, [31] M. Dreidy, H. Mokhlis, and S. Mekhilef, “Inertia response and frequency
pp. 800–808, Oct. 2012. control techniques for renewable energy sources: A review,” Renew. Sus-
[9] J. Rafferty et al., “Frequency support using multi-terminal HVDC systems tain. Energy Rev., vol. 69, pp. 144–155, 2017.
based on DC voltage manipulation,” IET Renewable Power Gener., vol. 10,
no. 9, pp. 1393–1401, 2016.
[10] J. N. Sakamuri et al., “Coordinated frequency control from offshore
wind power plants connected to multi terminal DC system considering
wind speed variation,” IET Renewable Power Gener., vol. 11, no. 8,
pp. 1226–1236, 2017.
[11] O. D. Adeuyi, M. Cheah-Mane, J. Liang, and N. Jenkins, “Fast frequency Muhammad M. Kabsha (Senior Member, IEEE) received the B.E. (Hons.) and
response from offshore multiterminal VSC-HVDC schemes,” IEEE Trans. M.Sc. degrees in electrical engineering from Mansoura University, Mansoura,
Power Del., vol. 32, no. 6, pp. 2442–2452, Dec. 2017. Egypt, and the Ph.D. degree from the Department of Energy Science and
[12] K. Jose et al., “Auxiliary dead-band controller for the coordination of fast Engineering, Indian Institute of Technology (IIT) Bombay, Mumbai, India.
frequency support from multi-terminal HVDC grids and offshore wind He is currently an Assistant Professor with the Department of Electrical Engi-
farms,” IET Renewable Power Gener., vol. 12, no. 13, pp. 1444–1452, neering, Mansoura University, Mansoura, Egypt. His research interests include
2018. grid integration of renewable energy sources, HVdc, power system stability,
[13] Y. Wang et al., “DC voltage deviation-dependent voltage droop control power system control, hybrid ac/dc microgrids, power electronic converters,
method for VSCMTDC systems under large disturbances,” IET Renew. and protection systems.
Power Gener., vol. 14, no. 5, pp. 891–896, 2020.
[14] Y. Wang, W. Wen, C. Wang, H. Liu, X. Zhan, and X. Xiao, “Adaptive
voltage droop method of multiterminal VSC-HVDC systems for DC
voltage deviation and power sharing,” IEEE Trans. Power Del., vol. 34,
no. 1, pp. 169–176, Feb. 2019.
[15] R. Yang, G. Shi, X. Cai, C. Zhang, G. Li, and J. Liang, “Autonomous syn-
chronizing and frequency response control of multi-terminal DC systems
with wind farm integration,” IEEE Trans. Sustain. Energy, vol. 11, no. 4, Zakir Hussain Rather (Senior Member, IEEE) received the bachelor’s degree
pp. 2504–2514, Oct. 2020.
in electrical engineering from Jammu University, Jammu, India, the M.Tech.
[16] C. Zhong, J. Zhang, and Y. Zhou, “Adaptive virtual capacitor control for
degree in power systems from the Indian Institute of Technology (IIT) Delhi,
MTDC system with De-loaded wind power plants,” IEEE Access, vol. 8,
New Delhi, India, and the Industrial Ph.D. degree in power systems from Aalborg
pp. 190582–190595, 2020. University, Aalborg, Denmark.
[17] A. S. Kumar and B. P. Padhy, “Hybrid control strategy for effec-
He has experience of more than five years in power industry including KK
tive frequency regulation and power sharing in multi-terminal HVDC
wind Solutions, Denmark. He was a Senior Power System Researcher with
grids,” IET Gener. Transmiss. Distrib., vol. 14, no. 23, pp. 5536–5546,
Electricity Research Centre, University College Dublin, Dublin, Ireland. He is
2020. currently an Associate Professor with IIT Bombay, Mumbai, India. His research
[18] M. M. Kabsha and Z. H. Rather, “A new control scheme for fast frequency
interests include grid and system integration of renewable energy, power system
support from HVDC connected offshore wind farm in low-inertia system,”
security and stability, microgrids, and wide-area measurement and control.
IEEE Trans. Sustain. Energy, vol. 11, no. 3, pp. 1829–1837, Jul. 2020.
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on August 13,2023 at 06:52:01 UTC from IEEE Xplore. Restrictions apply.