YFR-1 Addressable Fire Alarm Control Panel Manual Book
YFR-1 Addressable Fire Alarm Control Panel Manual Book
YFR-1
Addressable Fire Alarm Control Panel
Operation Manual
2017.06.15 REV.1
71114-R01-E
Table of Contents
External Dimensions Drawing …………………………………….2
Dimensions
Addresses Type H mm*W mm*D mm
/ Loops
150 / 1CH Mounting 450 * 480 * 160
256 / 1CH Mounting 450 * 480 * 160
512 / 2CH Mounting 450 * 480 * 160
768 / 3CH Mounting 500 * 480 * 160
1024 / 4CH Mounting 500 * 480 * 160
1280 / 5CH Mounting 840 * 480 * 180
1536 / 6CH Mounting 840 * 480 * 180
1792 / 7CH Mounting 1020 * 480 * 180
2048 / 8CH Mounting 1020 * 480 * 180
Select casing dimensions based on on-site condition. Please confirm with us your needs.
10. Status Indicator Section: main indicator section of main panel status.
1. AC Power:
The light is lit when the main system is using external AC power as
the main power source;
and the light is off when AC power is removed.
(Allowable voltage range is plus and minus 10% of nominal.)
2. Standby Power:
This light is lit when AC power is removed and the standby power is
used.
3. Off-line Indicator:
This light flashes when any external locator (repeater) loop in the
system is off-line. (L,C disconnection)
4. Switch Caution:
This light flashes when the control switch on the operating panel is
not positioned normally.
5. Communication Isolation:
This light flashes when the isolation switch is not positioned in the
ON position or when isolation is not set via the operating panel in the
system communication module.
6. Abnormal Connection:
This light flashes when abnormality is detected in the main signal
transmission line between the main panel and the locator (repeater),
address detector, or address transmitter; or in the transmission line
between the main panel and system communication modules.
7. Accumulation Indicator:
This light flashes when the address detector or the locator (repeater)
loop is accumulating.
9. Fuse Malfunction:
This light flashes when a fuse is burnt out in the main system power
panel or system communication modules. (A red LED is located next to
each fuse. Lit LED indicates a burnt fuse.)
2. Damper Switch:
When this switch is pressed during exhaust loop activation, damper
relay output is paused and the dislocation indicator light above the
switch flashes.
3. Sounder Switch:
When this switch is pressed during sprinkler/foam loop activation and
sounder sounding, sounder sounding is paused and the dislocation
indicator light above the switch flashes.
Exterior Dimensions
Casing
Mounting
type
Addresses
150/1CH 256/1CH 512/2CH 768/3CH 1024/4CH 1280/5CH 1536/6CH 1792/7CH 2048/8CH
/ Loops
H (mm) 450 500 840 1020
W (mm) 480 480 480 480
D (mm) 160 160 180 180
Specifications Table
Item Specification
Main Power Supply AC110V 50/60Hz、AC220V 50/60Hz
No. of Addresses
150/1CH 256/1CH 512/2CH 768/3CH 1024/4CH 1280/5CH 1536/6CH 1792/7CH 2048/8CH
/ No. of Units
Standby Battery DC24V
Transmission
Distance Dual-line type (branched wiring possible) 1.5KM
Main/Sub-panel RS-485 transmission distance 800M, Maximum 3KM with network signal adaptor
Communication and 40KM with fiber optics
Load power/ Indicator light/ Zone telephone: DC24V
Loop Voltage
SLC power source: AC32V
Power Main control panel monitoring (max): 500mA
Consumption Communication module (each system) monitoring (max): 280mA
Transmission
Selective/Sequential
Method
Broadcast Output Relay output: interlock relay board x 13 sets for a maximum of 2000 contacts
Method (relay board = 40 contacts (standard), 160 contacts (expansion))
Main Audio Synthesized sound, vocal, or alarm sound (over 90 dB)
Temperature
Range 0~40℃
Cabinet Material Powder coating steel
10
G. Maintenance Essentials
11
abnormalities.
○
6 Test exterior relay devices.
12
H. Easy Troubleshooting
13
I. Installation Cautions
1. Please make sure that the exterior wires correspond to the labeled
contents prior to installation. Ground resistance must be greater than
2MΩ.
3. Please turn off the battery power when loading or unloading the battery.
Confirm the polarity and install the battery correctly into the battery
terminal.
5. During test, after the AC power switch is turned off (OFF), please also
turn off the standby power to prevent excessive power discharge of the
standby battery which may result in lack of power during the next test
(need to await recharge).
14
15
16
17
18