Professional Documents
Culture Documents
Design and Commission A Zero-Carbon Building For Hot and Humid Climate
Design and Commission A Zero-Carbon Building For Hot and Humid Climate
Trevor S.K. Ng, Raymond M.H. Yau, Tony N.T. Lam and Vincent S.Y. Cheng*
Building Sustainability Group, Arup, Level 3 Festival Walk 80 Tat Chee Avenue, Kowloon,
Hong Kong SAR, China
.............................................................................................................................................
Abstract
The Construction Industry Council (CIC) Zero-Carbon Building is a net zero-carbon building that was
designed for local hot and humid climate of sub-tropical Hong Kong. Over 80 sustainability features of
the architecture and building systems have considered the life-cycle carbon emissions, including the
Keywords: zero carbon; combined cooling heating and power; bio-diesel; photovoltaics; Hong Kong
*Corresponding author:
vincent.cheng@arup.com Received 20 March 2013; revised 30 July 2013; accepted 28 August 2013
................................................................................................................................................................................
1 INTRODUCTION In Asia, many challenges lie ahead for getting to net zero
energy/carbon for buildings. Blindly copying European or
The emerging imperative to reduce carbon footprint worldwide North American architecture and construction techniques leads
is to bring down its emission from building to zero level. to higher consumption rates than conventional design. Lacking
Buildings account for a big portion of energy use in a country/ the knowledge of local contexts, in terms of climatic conditions
region, over 40% in the case of the USA [1] and over 60% for and building performance, and appropriate technologies for
Hong Kong [2]. Zero-Energy Building (ZEB) and Zero-Carbon analysing and construction of ZCB/ZEB have created the barrier
Building (ZCB) are becoming a global design trend worldwide for standardising the practice of low carbon in this region [3].
as the strategy for de-carbonation, and therefore creating a More efforts are required from the government and the industry
climate neutral community as the ultimate target. In the UK, the to tackle the technical issues and build up the experiences.
legislation called for all zero-carbon emission from new housing In response to the quest of low carbon technologies applic-
by 2016. The European Parliament recently has also set the able to Hong Kong, the Construction Industry Council (CIC)
target for all new construction to be zero energy by 2019. In commissioned the design and construction of a ZCB in Hong
2007, California energy regulators set a goal for all new homes to Kong in 2011. The purpose of the buildings is to create a place
be built to net zero energy standards starting in 2020. Various for the industry to demonstrate the technologies of the con-
initiatives/policies are in place to accelerate this trend. Pilot struction and practices of building design and construction. The
ZEB/ZCB projects were built in recent years first in Europe as CIC ZCB has designed with various uses to engage the profes-
the key initiative of governments and now exist in many places sionals and practitioners for a common goal of creating a better,
in the world. safer and more sustainable environment to the industry. The
ZCB features more than 80 sustainable installations. The sched- layout is designed with cross-ventilation and microclimate en-
ule of accommodation of the building is summarised in Table 1 hancement in mind. The large open space creates a wind corri-
and the architectural outlook design is shown in Figure 1. The dor for the prevailing south-easterly wind to flow across the
construction was completed in June 2012. urban native woodland, effectively reducing the ambient tem-
This paper addresses the design approach on arriving at the perature through evapo-transpiration. The building shape also
most appropriate strategy on building and system designs and enhances cross-ventilation. As the wind flows over the sloped
solution for tackling the difficulties on commissioning the core roof, and leaves the sharp-trailing edge, a low-pressure region is
system, i.e. the CCHP system of this ZCB. Lessons learnt on the created leeward of the building. This creates a suction effect that
implementing ZCB in Hong Kong will be discussed. inducts the pre-cooled air from the urban woodland into the
building for cross-ventilation.
Emissions reduction
Emissions
from excessive Emissions
Carbon Neutral associated with
electricity produced associated with
ðon annual basisÞ ¼ þ þ biodiesel supplied to
from renewables electricity supplied
the site
‘displacing’ grid to the site
consumptions
2.3 Carbon neutrality and energy cascade demands in all instants on-site power generation by bio-diesel
To achieve carbon neutrality, renewable energy facilities within generator plays a crucial role for carbon neutrality. The decision
the boundary were designed. There are two major renewable to use bio-diesel as a renewable energy source was helped by the
systems within the site boundary, namely PV panels and a fact that the fuel was produced locally in Hong Kong with waste
small-scale bio-diesel CCHP plant. The area of PV panels, cooking oil as feedstock. The emission factor for the use of bio-
limited by the roof areas, has been optimised for cost- diesel from waste cooking oil is very low since it not only dis-
effectiveness. It can only provide 66% of required renewable places the combustion of fossil fuel, but also avoids the generation
energy for carbon off-set. Also, solar energy is not constant and of methane gas at landfills. Detailed analyses were performed on
therefore not reliable and cannot fully satisfy the building how and when energy is used in the building and devised an
Table 1. Schedule of Accommodations of CIC ZCB. energy matching strategy that aligned the consumption pattern
of the building. The strategy was based on the first and second
Accommodation Net floor area
(m2) laws of thermodynamics—energy is not destroyed, just becomes
lower grade when used. Hence energy usages are lined up in
Entrance lobby and reception terms of the energy grade such that the lower-grade energy
Orientation / break-out / information 100
output from one piece of equipment is utilised as the input of
Temporary exhibition area
Temporary exhibition zone with renew showcases from 150 another in an energy cascade. Figure 4 illustrates the schematic
local industry / stakeholders diagram of the PV and CCHP systems operation. Electricity gen-
Permanent exhibition area erated will serve the building and the landscape area; any surplus
Permanent exhibition zone on low-/zero-carbon design 490 electricity will be fed into the grid. Waste heat from the generator
and technologies
will be recovered to drive the absorption chiller and desiccant de-
Multi-purpose room
Audio–visual presentation for organised visits / public 260 humidification system. The energy generated and feed-in to grid
lectures, CIC seminars, conferences were continuously monitored by intelligent metering and trans-
Eco-office 1 mitted to Building Management System (BMS).
energy demand. This had helped the architects and engineers to 3.1 Base building
make the design decision using the standard cost–benefit analysis. New buildings in Hong Kong are becoming more efficient; this
Building energy simulation was conducted using the simulation is partially attributed to the mandatory Building Energy Codes
tool IES ver 6.4 [6]. Two major inputs were needed—hourly (BEC) in 2012 to new buildings [9]. The codes provide the best
weather databases and ZCB building designs (architectural ele- practice design guidelines for all new developments in Hong
ments and building systems). The Typical Meteorological Year Kong. Along with the regulations, BEC regulates the design of
(TMY) method, developed by the Sandia National Laboratories in Overall Thermal Transmittance Values (OTTV) [10] of building
the USA and the most widely adopted methods for determination fabric and minimum requirements of major building services
of typical weather years [7], were adopted in the study. ATMY con- systems including those for the air-conditioning (A/C), electric-
sists of 12 typical meteorological months (TMMs) selected from al, lighting and escalators etc. They therefore form the baseline
various calendar months in a 25-year period (1979–2003) mea- and design targets for practitioners. To achieve the objective of
sured weather database [8]. An 8760 hourly TMY weather file was ultra-low energy use, the ZCB was designed to substantially
used to represent the Hong Kong prevailing climatic characteristics. surpass such baseline performance.
Thermal characteristics
Window-to-wall ratio north-east facade 10%
Window-to-wall ratio south-east facade 80%
Window-to-wall ratio south-west facade 0%
Window-to-wall ratio north-west facade 56%
Shading coefficient 0.33, double low-E window panes
Visual light transmission 0.54
Horizontal overhangs on the south facade 458 angle
Vertical louvers on the north-west facade 238 angle
Skylights Shaded by variable louvers
Wall U-value and absorptivity ,0.6W/m2K and ,0.3
Roof U-value and absorptivity ,0.2W/m2K and ,0.3
Room Design condition
plant and its energy use. Good air tightness also reduces the risk minimum air exchange rate of six air changes per hour under
of condensation. Infiltration occurs primarily at window and typical conditions.
door joins, these features was designed to reduce infiltration to
below 5 l/s per m2 of door area and to below 2 l/s per m2 of 3.3.5 Radiant cooling
window area. Radiant cooling systems rely primarily on radiation heat transfer.
Typically, chilled water is circulated through ceiling panels or
beams to maintain comfort in the building. The circulated water
3.3.4 Optimising microclimate and natural ventilation collects and removes heat from the space. Radiant systems are
Enhanced natural ventilation can reduce building energy loads more energy-efficient than air-based systems. They require less
as air is moved through the building naturally for, in this case, parasitic energy ( pump and fan energy) to deliver cooling. The
30 – 40% of the year (when used in conjunction with ceiling higher operating temperatures mean that chillers can operate
fans). As shown in Figure 8, with the computational fluid more efficiently if they are not required to serve other cooler
dynamic (CFD) modeling technique, the building is oriented to areas. Because the floors are radiantly cooled, the air tempera-
receive the site prevailing south-easterly wind, in order to opti- ture can be higher to achieve the same level of comfort. Higher
mising the natural air flow availability. A thermal dynamic study air temperatures also result in lower heat losses to the outdoors.
has shown that under natural ventilation operation, cool Also, radiant cooling systems are silent in operation and this
fresh-air is brought in through orifices, warmed by the internal enhances occupant comfort.
loads and exhausted. An internal temperature at 25.58C is to be A limiting factor for the panel temperature and the cooling
maintained. For this level of internal gains, natural ventilation capacity is the dew-point temperature in the space. Standards
can function below external temperatures of 208C, accounting recommend a limit for the relative humidity in a space to 60 or
for increased air movement due to ceiling fans. This delivers a 70% relative humidity, which at an air temperature of 268C
(798F) corresponds to a dew point between 17 and 208C (63 and Table 3. Estimated cooling load and the breakdown for the zero-carbon
688F), i.e. lower than the floor temperature (218C typical). building.
In the design, the radiant system is sized to deliver 50 W/m2 Components Cooling load (kW)
accounting for about 30 – 50% of the total heat load. Energy
savings occurs through the reduction in fan-power (by 30 – 50%) Fabric load 64.4
Equipment load 18.4
but is slightly off-set by an increase in pump power—additional Lighting load 6.0
energy for chilled water circuit. People load 20.2
Given the risk for condensation, radiant panels is applied to Fresh air load 53.4
areas away from the perimeter zone with appropriate control Total peak cooling load 163
methodology discussed in later sections. The radiant panels are
provided with higher water temperature (compared with conven-
tional fan coils), leading to higher Coefficient of Performances temperature difference ¼ 108C for both systems and hence both
(COPs) at the chillers. Expected cooling energy savings is 6– systems will have similar volume flow rate.
12%. Corresponding overall energy reduction is 1–3%. Energy savings arises in two key areas: (1) the plenum under-
floor design and low-velocity outlets minimises pressure drop and
3.3.6 Underfloor air-supply hence fan power (15% reduction in fan power) and (2) the higher
Underfloor systems mainly use the same A/C equipment, e.g. chil- supply air temperature allows greater extent of free-cooling
lers, pumps, and AHUs as in conventional A/C systems. The main number of days suitable for free cooling increases from 200 h each
difference between the two is the manner that air is being distrib- year to 600 h each year. Overall energy reduction expected from
uted. To avoid drafts, the temperature of the supply air is higher the use of underfloor systems was predicted to be 0.5–3%.
in an underfloor system (15–208C compared with 10–158C of
conventional A/C). While jet-throw systems are considered semi- 3.4 On-site renewable energy generation
stratified, the fully stratified displacement systems will have a After applying the passive and active design measures for energy
higher return air temperature even though the exhaust inlets are efficiency, the building and landscape energy consumption is
located at similar height at the ceiling. The final temperature dif- greatly reduced to the following:
ference between inlet and exhaust will depend on the detailed
air-flow and will be the subject of further studies. As a reasonable - 116 MWh/year electricity consumption by the building
starting point, the effect of increased stratification is assumed to - 15 MWh/year electricity consumption by surrounding
be exactly off-set by the effect of increased supply temperature, i.e. landscape
To achieve net zero carbon, these energy demands were met users. This also gives the opportunity for carbon trading for
through renewable means. An additional 99 MWh/year will be such additional energy output in the future.
exported to the grid to off-set the embodied energy in major The site is surrounded by buildings with one high-rise office
building materials and if possible the embodied energy in other tower, located at the southern location, completely overshadow-
building components, water use and transportation energy of ing during winter solstice. The expected power output per
square meter of panels is 85 kWh/m2. The panels will also 1015 m2 PV panels can produce only 87 MWh/year of electricity,
require 50% of mounting and servicing space in between. The i.e. insufficient for our needs.
installed PV cells are monocrystalline and polycrystalline PV A bio-diesel CCHP system was designed as a suitable add-
systems. Complete coverage of the building footprint with itional renewable system [13]. A CCHP system is suitable as the
thermal energy produced can be used to drive an absorption
chiller system to provide cooling to the building which reduces
the electrical energy use for chillers by 85%. Table 4 summarises
the energy and carbon balance with the application of bio-diesel
Table 4. Life-cycle calculation on energy and carbon balance in 50 years. CCHP and PV systems.
Energy Carbon
Figure 10. Annual energy balance of energy consumption and renewable generation.
REFERENCES [8] Chan ALS, Chow TT, Fong SKF, et al. Generation of a typical meteorological
year for Hong Kong. Energy Convers Manage 2006;47:87– 96.
[9] Electrical & Mechanical Services Department. Code of practices for energy
[1] Energy Information Administration. Annual energy review 2011, efficiency of building services installation 2012, Hong Kong, 2012.
Washington, USA, 2012. [10] Buildings Department. Code of practice for overall thermal transfer value in
[2] Electrical & Mechanical Services Department. Hong Kong energy end-use buildings, Hong Kong, 2011.
data 2012, Hong Kong, 2012. [11] Electrical & Mechanical Services Department. Energy consumption indica-
[3] Hui SCM. Zero energy and zero carbon buildings: myths and facts. In: tors and benchmarks for residential, commercial and transport sectors by
Proceedings of the International conference on Intelligent Systems, Structures Dec 2012. http://ecib.emsd.gov.hk/en/indicator_cmc.htm
and Facilities (ISSF2010): Intelligent Infrastructure and Buildings, Hong [12] Building and Construction Authority. The island’s first retrofitted zero
Kong, January 2010, 15 – 25. energy building, Singapore. www.bca.gov.sg/zeb/default/html
[4] Givoni B, Noguchi M, Saaroni H, et al. Outdoor comfort research issues. [13] Liu H, Qiu G, Shao Y, et al. Preliminary experimental investigations
Energ Buildings 2003;35:77– 86. of a biomass-fired micro-scale CHP with organic Rankine cycle. Int J
[5] United Kingdom Green Building Council (UKGBC). Report on carbon Low-carbon Technol 2010;5:81– 7.
reductions in new non-domestic buildings. London, UK, 2007. [14] Environmental Protection Department and Electrical & Mechanical