Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

Design and commission a zero-carbon

building for hot and humid climate


..............................................................................................................................................................

Trevor S.K. Ng, Raymond M.H. Yau, Tony N.T. Lam and Vincent S.Y. Cheng*
Building Sustainability Group, Arup, Level 3 Festival Walk 80 Tat Chee Avenue, Kowloon,
Hong Kong SAR, China
.............................................................................................................................................
Abstract
The Construction Industry Council (CIC) Zero-Carbon Building is a net zero-carbon building that was
designed for local hot and humid climate of sub-tropical Hong Kong. Over 80 sustainability features of
the architecture and building systems have considered the life-cycle carbon emissions, including the

Downloaded from https://academic.oup.com/ijlct/article/11/2/222/2198318 by guest on 14 May 2023


embodied carbon of construction materials, emissions associated with the construction process, the 50-
years of operation and decommission of the building. The total life-cycle carbon emission was off-set by
on-site renewable energy generated by photovoltaics (PV) and bio-diesel combined cooling heating and
power (CCHP) system. To optimise the design, a series of climate-responsive strategies on passive
architecture were applied to the construction of the building. These include the high-performance facade,
effective air tightness and optimised window design that allows the application of natural ventilation and
daylighting. Reduction of 20% energy demand was achieved by these passive designs. To further lower the
carbon emission on operation, energy-efficient air-conditioning (A/C) systems using desiccant
dehumidification, underfloor air supply and radiant cooling have also contributed on achieving an
ultralow energy use value. Amalgamated saving of these passive and active systems are over 45% when
compared with the design per existing local building energy codes.

Keywords: zero carbon; combined cooling heating and power; bio-diesel; photovoltaics; Hong Kong
*Corresponding author:
vincent.cheng@arup.com Received 20 March 2013; revised 30 July 2013; accepted 28 August 2013

................................................................................................................................................................................

1 INTRODUCTION In Asia, many challenges lie ahead for getting to net zero
energy/carbon for buildings. Blindly copying European or
The emerging imperative to reduce carbon footprint worldwide North American architecture and construction techniques leads
is to bring down its emission from building to zero level. to higher consumption rates than conventional design. Lacking
Buildings account for a big portion of energy use in a country/ the knowledge of local contexts, in terms of climatic conditions
region, over 40% in the case of the USA [1] and over 60% for and building performance, and appropriate technologies for
Hong Kong [2]. Zero-Energy Building (ZEB) and Zero-Carbon analysing and construction of ZCB/ZEB have created the barrier
Building (ZCB) are becoming a global design trend worldwide for standardising the practice of low carbon in this region [3].
as the strategy for de-carbonation, and therefore creating a More efforts are required from the government and the industry
climate neutral community as the ultimate target. In the UK, the to tackle the technical issues and build up the experiences.
legislation called for all zero-carbon emission from new housing In response to the quest of low carbon technologies applic-
by 2016. The European Parliament recently has also set the able to Hong Kong, the Construction Industry Council (CIC)
target for all new construction to be zero energy by 2019. In commissioned the design and construction of a ZCB in Hong
2007, California energy regulators set a goal for all new homes to Kong in 2011. The purpose of the buildings is to create a place
be built to net zero energy standards starting in 2020. Various for the industry to demonstrate the technologies of the con-
initiatives/policies are in place to accelerate this trend. Pilot struction and practices of building design and construction. The
ZEB/ZCB projects were built in recent years first in Europe as CIC ZCB has designed with various uses to engage the profes-
the key initiative of governments and now exist in many places sionals and practitioners for a common goal of creating a better,
in the world. safer and more sustainable environment to the industry. The

International Journal of Low-Carbon Technologies 2016, 11, 222–234


# The Author 2013. Published by Oxford University Press.
This is an Open Access article distributed under the terms of the Creative Commons Attribution License (http://creativecommons.org/licenses/by/3.0/), which
permits unrestricted reuse, distribution, and reproduction in any medium, provided the original work is properly cited.
doi:10.1093/ijlct/ctt067 Advance Access Publication 6 October 2013 222
Design and commission a zero-carbon building

ZCB features more than 80 sustainable installations. The sched- layout is designed with cross-ventilation and microclimate en-
ule of accommodation of the building is summarised in Table 1 hancement in mind. The large open space creates a wind corri-
and the architectural outlook design is shown in Figure 1. The dor for the prevailing south-easterly wind to flow across the
construction was completed in June 2012. urban native woodland, effectively reducing the ambient tem-
This paper addresses the design approach on arriving at the perature through evapo-transpiration. The building shape also
most appropriate strategy on building and system designs and enhances cross-ventilation. As the wind flows over the sloped
solution for tackling the difficulties on commissioning the core roof, and leaves the sharp-trailing edge, a low-pressure region is
system, i.e. the CCHP system of this ZCB. Lessons learnt on the created leeward of the building. This creates a suction effect that
implementing ZCB in Hong Kong will be discussed. inducts the pre-cooled air from the urban woodland into the
building for cross-ventilation.

2 APPROACH OF ZCB DESIGN


2.2 Life-cycle considerations
2.1 Climate-responsive designs There is no worldwide standard on the definition for ‘Zero

Downloaded from https://academic.oup.com/ijlct/article/11/2/222/2198318 by guest on 14 May 2023


Climate is the most important factor that shapes the design of Carbon’ building. The generally accepted practice is to estimate
low-/zero-carbon building. Hong Kong’s climate is characterised the components of carbon emission of building and off-set
by two distinct seasons, winter and summer. As indicated in them by renewable energy, using stand-alone or grid-connect
Figure 2, summer months tend to be hot and humid; winter approach [5]. Here we have adopted the life-cycle concept
months are cooler and dry. People have a tendency to escape (Figure 3). A number of carbon-emission producing processes
from the hot summer into the buildings which are normally were identified to be associated with the life-cycle of the build-
conditioned mechanically. Typical cooling season is about 2000 ing, from material manufacturing, construction process, 50
degree-hour in Hong Kong, a huge difference compared with years of operation and finally decommission of the building. To
200 degree-hour of London and 1300 degree-hour of achieve carbon neutrality, renewable energy facilities within the
San Francisco. This cooling demand posts a huge challenge on site boundary were designed to produce sufficient energy to
the adoption of passive architectural designs prevailing in meet the demands of energy consumptions associated with the
Europe and North America. A study by Givoni et al. [4] has activities inside the building over an annual basis—such that the
shown that psychological responses to the sub-tropical climate net carbon will be zero and also that all the life-cycle emissions
can be significantly improved by blocking direct solar heat (re- can be ‘off-set’ by the on-site renewable energy at the end of 50
ducing resultant temperatures) and encouraging breeze (increas- years of service life. As ZCB is connected to the local grid which
ing skin evaporation) due to accramodisation effect; this extends allows energy to be exported and the production of on-site re-
the natural ventilation period throughout the year—a key newable energy off-sets the power consumed from grid over an
climate-responsive design strategy of the project. annual basis, the emission associated with this energy input
In the mid-seasons, there is a good potential for the buildings should also be considered. The concepts for carbon calculation
to be naturally ventilated. Massing buildings to allow the air to for neutrality on annual basis are shown as follows:
pass through freely can significantly reduce the time mechanical
ventilation and cooling systems operate. The ZCB project site

Emissions reduction
Emissions
from excessive Emissions
Carbon Neutral associated with
electricity produced associated with
ðon annual basisÞ ¼ þ þ biodiesel supplied to
from renewables electricity supplied
the site
‘displacing’ grid to the site
consumptions

2.3 Carbon neutrality and energy cascade demands in all instants on-site power generation by bio-diesel
To achieve carbon neutrality, renewable energy facilities within generator plays a crucial role for carbon neutrality. The decision
the boundary were designed. There are two major renewable to use bio-diesel as a renewable energy source was helped by the
systems within the site boundary, namely PV panels and a fact that the fuel was produced locally in Hong Kong with waste
small-scale bio-diesel CCHP plant. The area of PV panels, cooking oil as feedstock. The emission factor for the use of bio-
limited by the roof areas, has been optimised for cost- diesel from waste cooking oil is very low since it not only dis-
effectiveness. It can only provide 66% of required renewable places the combustion of fossil fuel, but also avoids the generation
energy for carbon off-set. Also, solar energy is not constant and of methane gas at landfills. Detailed analyses were performed on
therefore not reliable and cannot fully satisfy the building how and when energy is used in the building and devised an

International Journal of Low-Carbon Technologies 2016, 11, 222–234 223


T.S.K. Ng et al.

Table 1. Schedule of Accommodations of CIC ZCB. energy matching strategy that aligned the consumption pattern
of the building. The strategy was based on the first and second
Accommodation Net floor area
(m2) laws of thermodynamics—energy is not destroyed, just becomes
lower grade when used. Hence energy usages are lined up in
Entrance lobby and reception terms of the energy grade such that the lower-grade energy
Orientation / break-out / information 100
output from one piece of equipment is utilised as the input of
Temporary exhibition area
Temporary exhibition zone with renew showcases from 150 another in an energy cascade. Figure 4 illustrates the schematic
local industry / stakeholders diagram of the PV and CCHP systems operation. Electricity gen-
Permanent exhibition area erated will serve the building and the landscape area; any surplus
Permanent exhibition zone on low-/zero-carbon design 490 electricity will be fed into the grid. Waste heat from the generator
and technologies
will be recovered to drive the absorption chiller and desiccant de-
Multi-purpose room
Audio–visual presentation for organised visits / public 260 humidification system. The energy generated and feed-in to grid
lectures, CIC seminars, conferences were continuously monitored by intelligent metering and trans-
Eco-office 1 mitted to Building Management System (BMS).

Downloaded from https://academic.oup.com/ijlct/article/11/2/222/2198318 by guest on 14 May 2023


Live showcase and active eco-office for CIC 230
Eco-office 2
Live showcase and active eco-office 120
Eco-home þ display gallery
Demonstration of low-/zero-carbon home design, features 150
3 ENERGY SIMULATION
and engagement for low-carbon living
Souvenir shop Whole building energy simulations were conducted at the early
Souvenirs / eco-products retail 10 design stage to predict the energy consumption of the ZCB. The
Eco-café results were used to size the building energy systems as well as re-
Ancillary catering facilities of the ZCB, with an eco-theme 10 newable energy systems for neutralisation. At design stage, this
for sustainable food
Total net floor area 1520
process was also important to evaluate the effectiveness of different
design strategies to reduce the loads (cooling and electricity) and

Figure 1. Photo of CIC ZCB.

224 International Journal of Low-Carbon Technologies 2016, 11, 222–234


Design and commission a zero-carbon building

energy demand. This had helped the architects and engineers to 3.1 Base building
make the design decision using the standard cost–benefit analysis. New buildings in Hong Kong are becoming more efficient; this
Building energy simulation was conducted using the simulation is partially attributed to the mandatory Building Energy Codes
tool IES ver 6.4 [6]. Two major inputs were needed—hourly (BEC) in 2012 to new buildings [9]. The codes provide the best
weather databases and ZCB building designs (architectural ele- practice design guidelines for all new developments in Hong
ments and building systems). The Typical Meteorological Year Kong. Along with the regulations, BEC regulates the design of
(TMY) method, developed by the Sandia National Laboratories in Overall Thermal Transmittance Values (OTTV) [10] of building
the USA and the most widely adopted methods for determination fabric and minimum requirements of major building services
of typical weather years [7], were adopted in the study. ATMY con- systems including those for the air-conditioning (A/C), electric-
sists of 12 typical meteorological months (TMMs) selected from al, lighting and escalators etc. They therefore form the baseline
various calendar months in a 25-year period (1979–2003) mea- and design targets for practitioners. To achieve the objective of
sured weather database [8]. An 8760 hourly TMY weather file was ultra-low energy use, the ZCB was designed to substantially
used to represent the Hong Kong prevailing climatic characteristics. surpass such baseline performance.

Downloaded from https://academic.oup.com/ijlct/article/11/2/222/2198318 by guest on 14 May 2023


Figure 2. Challenging climatic conditions of Hong Kong on meeting thermal
environmental conditions for human occupancy. Figure 3. Concept of life-cycle approach for ZCB.

Figure 4. Schematic diagram of PV and CCHP systems operation.

International Journal of Low-Carbon Technologies 2016, 11, 222–234 225


T.S.K. Ng et al.

were built to BEC standards. It is observed that fabric loads


make up the majority proportion as the building has a high
envelope-to-floor area ratio.

Reduced window-to-wall ratio Approximately 10 times the solar


heat gains come through windows compared with opaque
facades. Minimising the extent of glazing has a dramatic effect
on the solar heat gain. The south-west facade is with no glazing
to avoid heat gains from afternoon low angle sun and the
ramped nature of the section naturally reduces window-to-wall
ratios on the south compared with the north. The overall
window-to-wall ratio of the ZCB is 0.4. The value was optimised
to meet the daylight requirement.

Downloaded from https://academic.oup.com/ijlct/article/11/2/222/2198318 by guest on 14 May 2023


Envelope absorptivity and facade insulation Minimising the flow
of heat through the opaque walls is also important. Two steps
reduce this impact: (1) lowering the absorptivity of the facade
reflects more heat away from the building, reducing the surface
temperature—absorptivity below 0.3 and (2) adding insulation to
the wall stops the flow of heat through the walls—u-value below
Figure 5. Results of energy simulation on energy use of various building
systems.
0.6 W/m2K for the walls and below 0.2 W/m2K for the roof.
To achieve an absorptivity of below 0.3, white walls or glazed
Figure 5 shows the energy use distribution predicted for the finishes can be used. Photovoltaic panels will sit above the
baseline model. The energy use intensity (EUI) of typical exist- roof, these have high absorptivity but the ventilated air gap
ing office buildings ranges 250– 350 kWh/m2 [11], while our beneath them will reduce heat transfer to the building. To
base building design per BEC is around 157 kWh/m2. In other achieve 0.6 W/m2K, the building was designed to incorporate
words, adoption of BEC requirements can effectively reduce 4– 5 cm of high-quality polyurethane board or 8 –9 cm of
energy use in building. glass fiber insulation. To achieve 0.2 W/m2K, the building
incorporated 12– 15 cm of high-quality polyurethane board or
18 – 20 cm of glass fiber insulation.
3.2 Energy performance of ZCB
Table 2 summarises the design values of the key parameters of
the ZCB. Energy model was performed with these values as the 3.3.2 Daylighting
design case; the predicted EUI of ZCB is 86 kWh/m2, i.e. 45% The profile of the building tilting to the north had provided the
lower than that of the BEC-compliant baseline building. Due to maximum opportunity of daylight while reducing the solar pene-
its nature of mixed-uses (for office, conference and exhibition) tration of the building. Effectively, the north light design has inte-
and intensive application, the CIC ZCB is relatively more grated into the building design and provides daylighting
energy-intensive than other ZCB buildings of cities with similar requirement for most of the spaces. To increase the amount of
climate. For example, the EUI of the ZCB of Singapore is only natural light which reaches the middle of the floor plate, the
46 kWh/m2 according to the published data [12]. The nature building incorporates an active skylight and light pipes. The sky-
and operation schedule of building may cause the large differ- light illuminates both the upper and lower exhibition spaces, and
ence in the annual energy use. the two light pipes sit above the lower exhibition space. The active
skylight, shown in Figure 7, consists of a standard skylight with
moveable fins located above. The fins are rotated to adjust the
3.3 Effectiveness of design strategies amount of daylight that passes through the skylight. The building
The effectiveness of energy saving strategies operated in the con- is designed to rotate the fins manually from the exhibition space
texts of Hong Kong, i.e. those passive and active systems were below. This will allow occupants to experience control over the
predicted by energy simulation. Figure 6 summarises their rela- building around them—the idea being they will adjust fins to
tive effectiveness. The design considerations and performances allow more light on an overcast day and less on a sunny day. The
of these strategies are summarised in the following paragraphs. light pipes are reflective light transmitting tubes to lead in add-
itional natural daylight into the inner part of the building.
3.3.1 Facade thermal performance
It is essential to minimise the envelope loads to reduce the heat 3.3.3 Envelope air-tightness
build-up. The peak cooling load of the ZCB is calculated to be This is particularly important for low energy design in Hong
163 W/m2 while most of the time cooling load is 80 W/m2. Kong climate because dehumidification of high humidity of in-
Table 3 shows the cooling load breakdown of this building if it filtration has a disproportional impact on the size of mechanical

226 International Journal of Low-Carbon Technologies 2016, 11, 222–234


Design and commission a zero-carbon building

Table 2. Design assumptions for system design and energy simulation.


Feature Design

Thermal characteristics
Window-to-wall ratio north-east facade 10%
Window-to-wall ratio south-east facade 80%
Window-to-wall ratio south-west facade 0%
Window-to-wall ratio north-west facade 56%
Shading coefficient 0.33, double low-E window panes
Visual light transmission 0.54
Horizontal overhangs on the south facade 458 angle
Vertical louvers on the north-west facade 238 angle
Skylights Shaded by variable louvers
Wall U-value and absorptivity ,0.6W/m2K and ,0.3
Roof U-value and absorptivity ,0.2W/m2K and ,0.3
Room Design condition

Downloaded from https://academic.oup.com/ijlct/article/11/2/222/2198318 by guest on 14 May 2023


Internal design conditions
In general 25.5 + 18C DB; 55 + 10% RH
Office 25.5 + 18C DB; 55 + 10% RH
Exhibition area 25.5 + 18C DB; 55 + 10% RH
Multi-function room (normal operation) 25.5 + 18C DB; 55 + 10% RH
Server room 22 + 18C DB; 55 + 10% RH
E&M plantroom , 408C DB
Lighting load (office) 6 W/m2 (200lux þ task lighting)
Lighting load (exhibition area) 6 W/m2 (200lux þ task lighting)
Lighting load (multi-purpose room) 6 W/m2 (300lux)
Equipment load (office) 20 W/m2
Equipment load (exhibition area) 10 kW
Equipment load (multi-purpose room) 5 W/m2
People load (office) 130 W/person
People load (exhibition area) 130 W/person
People load (multi-purpose room) 95 W/person
Room Occupancy (m2/person) Occupancy (person) Fresh air (l/s/person) Fresh air (l/s/m2)

Occupancy and fresh air


Exhibition 4.7 — 4.3 0.3
Display 4.7 — 4.3 0.3
Multi-purpose room — 300 4.3 0.3
Eco-office 8 — 2.5 0.3

plant and its energy use. Good air tightness also reduces the risk minimum air exchange rate of six air changes per hour under
of condensation. Infiltration occurs primarily at window and typical conditions.
door joins, these features was designed to reduce infiltration to
below 5 l/s per m2 of door area and to below 2 l/s per m2 of 3.3.5 Radiant cooling
window area. Radiant cooling systems rely primarily on radiation heat transfer.
Typically, chilled water is circulated through ceiling panels or
beams to maintain comfort in the building. The circulated water
3.3.4 Optimising microclimate and natural ventilation collects and removes heat from the space. Radiant systems are
Enhanced natural ventilation can reduce building energy loads more energy-efficient than air-based systems. They require less
as air is moved through the building naturally for, in this case, parasitic energy ( pump and fan energy) to deliver cooling. The
30 – 40% of the year (when used in conjunction with ceiling higher operating temperatures mean that chillers can operate
fans). As shown in Figure 8, with the computational fluid more efficiently if they are not required to serve other cooler
dynamic (CFD) modeling technique, the building is oriented to areas. Because the floors are radiantly cooled, the air tempera-
receive the site prevailing south-easterly wind, in order to opti- ture can be higher to achieve the same level of comfort. Higher
mising the natural air flow availability. A thermal dynamic study air temperatures also result in lower heat losses to the outdoors.
has shown that under natural ventilation operation, cool Also, radiant cooling systems are silent in operation and this
fresh-air is brought in through orifices, warmed by the internal enhances occupant comfort.
loads and exhausted. An internal temperature at 25.58C is to be A limiting factor for the panel temperature and the cooling
maintained. For this level of internal gains, natural ventilation capacity is the dew-point temperature in the space. Standards
can function below external temperatures of 208C, accounting recommend a limit for the relative humidity in a space to 60 or
for increased air movement due to ceiling fans. This delivers a 70% relative humidity, which at an air temperature of 268C

International Journal of Low-Carbon Technologies 2016, 11, 222–234 227


T.S.K. Ng et al.

Downloaded from https://academic.oup.com/ijlct/article/11/2/222/2198318 by guest on 14 May 2023


Figure 6. Summary of energy simulation results for different design strategies.

(798F) corresponds to a dew point between 17 and 208C (63 and Table 3. Estimated cooling load and the breakdown for the zero-carbon
688F), i.e. lower than the floor temperature (218C typical). building.
In the design, the radiant system is sized to deliver 50 W/m2 Components Cooling load (kW)
accounting for about 30 – 50% of the total heat load. Energy
savings occurs through the reduction in fan-power (by 30 – 50%) Fabric load 64.4
Equipment load 18.4
but is slightly off-set by an increase in pump power—additional Lighting load 6.0
energy for chilled water circuit. People load 20.2
Given the risk for condensation, radiant panels is applied to Fresh air load 53.4
areas away from the perimeter zone with appropriate control Total peak cooling load 163
methodology discussed in later sections. The radiant panels are
provided with higher water temperature (compared with conven-
tional fan coils), leading to higher Coefficient of Performances temperature difference ¼ 108C for both systems and hence both
(COPs) at the chillers. Expected cooling energy savings is 6– systems will have similar volume flow rate.
12%. Corresponding overall energy reduction is 1–3%. Energy savings arises in two key areas: (1) the plenum under-
floor design and low-velocity outlets minimises pressure drop and
3.3.6 Underfloor air-supply hence fan power (15% reduction in fan power) and (2) the higher
Underfloor systems mainly use the same A/C equipment, e.g. chil- supply air temperature allows greater extent of free-cooling
lers, pumps, and AHUs as in conventional A/C systems. The main number of days suitable for free cooling increases from 200 h each
difference between the two is the manner that air is being distrib- year to 600 h each year. Overall energy reduction expected from
uted. To avoid drafts, the temperature of the supply air is higher the use of underfloor systems was predicted to be 0.5–3%.
in an underfloor system (15–208C compared with 10–158C of
conventional A/C). While jet-throw systems are considered semi- 3.4 On-site renewable energy generation
stratified, the fully stratified displacement systems will have a After applying the passive and active design measures for energy
higher return air temperature even though the exhaust inlets are efficiency, the building and landscape energy consumption is
located at similar height at the ceiling. The final temperature dif- greatly reduced to the following:
ference between inlet and exhaust will depend on the detailed
air-flow and will be the subject of further studies. As a reasonable - 116 MWh/year electricity consumption by the building
starting point, the effect of increased stratification is assumed to - 15 MWh/year electricity consumption by surrounding
be exactly off-set by the effect of increased supply temperature, i.e. landscape

228 International Journal of Low-Carbon Technologies 2016, 11, 222–234


Design and commission a zero-carbon building

Downloaded from https://academic.oup.com/ijlct/article/11/2/222/2198318 by guest on 14 May 2023


Figure 7. Active skylight of the ZCB.

Figure 8. Building massing and orientation optimising natural ventilation.

To achieve net zero carbon, these energy demands were met users. This also gives the opportunity for carbon trading for
through renewable means. An additional 99 MWh/year will be such additional energy output in the future.
exported to the grid to off-set the embodied energy in major The site is surrounded by buildings with one high-rise office
building materials and if possible the embodied energy in other tower, located at the southern location, completely overshadow-
building components, water use and transportation energy of ing during winter solstice. The expected power output per

International Journal of Low-Carbon Technologies 2016, 11, 222–234 229


T.S.K. Ng et al.

square meter of panels is 85 kWh/m2. The panels will also 1015 m2 PV panels can produce only 87 MWh/year of electricity,
require 50% of mounting and servicing space in between. The i.e. insufficient for our needs.
installed PV cells are monocrystalline and polycrystalline PV A bio-diesel CCHP system was designed as a suitable add-
systems. Complete coverage of the building footprint with itional renewable system [13]. A CCHP system is suitable as the
thermal energy produced can be used to drive an absorption
chiller system to provide cooling to the building which reduces
the electrical energy use for chillers by 85%. Table 4 summarises
the energy and carbon balance with the application of bio-diesel
Table 4. Life-cycle calculation on energy and carbon balance in 50 years. CCHP and PV systems.

Energy Carbon

Energy use 4 COMBINE COOLING, HEATING AND


Embodied energy due to construction 14 MWh —
materials
POWER SYSTEM

Downloaded from https://academic.oup.com/ijlct/article/11/2/222/2198318 by guest on 14 May 2023


Energy use due to construction process 4 MWh —
Energy use of ZCB 116 MWh/year — The core element of the central system is the CCHP powered by
Energy use of the landscape area and 15 MWh/year — bio-diesel for carbon off-set. The commissioning of the gener-
others ator and absorption chiller is complicated. It requires the cali-
Generation bration of the condensing water temperature to provide the
Output from bio-diesel tri-generation 143 MWh/year —
system (100 kWe)
cooling design capacity and the supply temperature of the
Output of PV panels 87 MWh/year — chilled water for the A/C systems.
(1015 m2)
Offset
Surplus energy export 99 MWh/year — 4.1 System selection
Carbon emission reduction by on-site — 7100 Four options of CCHP system were investigated; the relative merits
renewable energy (over 50 years) tonnes and drawbacks are discussed in Table 5. Key considerations for
selection are:

Table 5. System selection for overall optimised energy efficiency.


System option descriptiona Option 1 Option 2 Option 3 Option 4

Chiller for underfloor A/C


Quantity 1 no.  100 kW 1 no.  100 kW 2 nos.  70 kW 1 no.  55 kW (absorption chiller)
(absorption chiller)
1 no.  40 kW 1 no.  40 kW 2 no.  55 kW (electric chiller)
Chilled water supply / Return temperature 9 / 138C 9 / 138C 9 / 138C 9 / 138C
COP (electric chiller) 5 5 N/A 5
Chiller efficiency (absorption chiller) N/A N/A 0.7 0.7
Chiller for chilled ceiling
Quantity 1 no.  40 kW 1 no.  40 kW 1 no.  40 kW 1 no.  55 kW (electric chiller)
(absorption chiller)
Chilled water supply / return temperature 15 / 198C 15 / 198C 15 / 198C 15 / 198C
COP (electric chiller) 5 5 N/A 5
Chiller efficiency (absorption chiller) N/A N/A 0.7 N/A
Peak power rating by chiller (kWp) 36 36 N/A 16
Overall cooling system efficiency 5 5 N/A 10.2
(cooling capacity / power rating)
Annual electricity consumption by chillers (kWh) 21 300 21 300 N/A 2000
Annual building energy consumption (exclude chillers) 95 000 95 000 95 000 95 000
(kWh)
PV area required (m2) 3000 N/A 1000 1000
CCHP power generation requirement (kWp) N/A 45 45 80
Heat rejection (high grade) from CCHP (kW) N/A 0 0 80
Heat rejection (low grade) from CCHP (kW) N/A 102 102 80
Waste heat recovery capacity (kW) N/A 0 102 55 (absorption chiller);
125 (desiccant dehumidifier)
CCHP operating hour N/A 24 h/day (summer only) 24 h/day (summer only) When absorption chiller is on
a
Option 1: electricity generated by PV; cooling by electric chiller. Option 2: electricity generated by CCHP; cooling by electric chiller. Option 3: electricity
generated by CCHP and PV; cooling by absorption chiller. Option 4: electricity generated by CCHP and PV; cooling by absorption chiller and electric chiller.

230 International Journal of Low-Carbon Technologies 2016, 11, 222–234


Design and commission a zero-carbon building

† System sized to instantaneous cooling demand


† Smaller central plant size
† PV panels contained within building footprint and covered
walkway
† Electric chiller increases resilience
† Excess electricity exported during peak hours (high value)
† Potential for waste heat for desiccant dehumidification
† Optimised running cost

Option 3 which provides the opportunity of energy cascade


was concluded to be the most energy efficient option. The
central cooling plant consists of absorption chiller operating
alongside with water-cooled electric chiller. Absorption chiller

Downloaded from https://academic.oup.com/ijlct/article/11/2/222/2198318 by guest on 14 May 2023


‘absorbs’ the waste heat from the bio-diesel generator and pro-
duces chilled water. Minimal electricity demand is required in
this process. The absorption chiller will deal with the cooling
load provided by underfloor A/C and ceiling air supply, while
the electric chiller will cater the remaining cooling load and will
also serve as back-up chiller to ensure system reliability. Figure 9
illustrates the CCHP bio-diesel generator and absorption chiller.

4.2 Design capacity


The CCHP system uses bio-diesel to generate both electrical and
thermal energy to run the chiller system and meet the building
cooling and electrical loads. The system is renewable as the fuel
is bio-diesel. The size of the system is 100 kWe and will operate
when a cooling demand is present.
In this design, a new approach towards chilled water produc-
Figure 9. Main equipment of CCHP-bio-diesel generator and absorption tion was adopted in the building. The idea of energy grading
chiller. was applied to match renewable energies to the remaining

Figure 10. Annual energy balance of energy consumption and renewable generation.

International Journal of Low-Carbon Technologies 2016, 11, 222–234 231


T.S.K. Ng et al.

Downloaded from https://academic.oup.com/ijlct/article/11/2/222/2198318 by guest on 14 May 2023


Figure 11. Annual carbon trade-off of the ZCB.

energy demands. The technique is ‘energy grading’: ranking the 5 CONCLUSIONS


full range of possible renewable sources against end-use energy
needs, to generate a checklist of building design priorities. The The design of ZCB needs to consider the particular local con-
key issue is to match the lowest possible grade of source against texts. In Hong Kong, the CIC ZCB was designed for local hot
the grade of the end demand. and humid climate of sub-tropical Hong Kong. A new concept
Energy grading highlights interesting issues, like the inherent of defining ZCB adopting life-cycle concept was proposed.
inefficiency of many conventional systems that consume high- Designing of the ZCB has incorporated a series of sustainable
grade energy and deliver only low-grade energy to building designs on passive architecture and energy-efficient active
users. It is understood that the high-energy penalties of chilled systems were applied to the construction of the building. These
water production can be supplied by waste heat rather than the include the high-performance facade with low OTTV, effective
conventional grid electricity. Figure 10 illustrates the annual air tightness and optimised window design which allows the op-
energy balance of energy consumption and renewable gener- eration natural ventilation and daylighting. Energy-efficient AC
ation. By applying the general carbon conversion factor of systems using desiccant dehumidification, underfloor supply and
0.7 kgCO2-e/kWh in Hong Kong [14], the carbon emission radiant cooling have also contributed on achieving ultra-low EUI
values were calculated. Figure 11 shows the carbon trade-off for values. Over 45% energy saving is achieved when compared with
the whole year. It is observed that carbon emissions in cool the local standard. The concept of energy-cascade was introduced
season (November– March) can be fully off-set in summer time to maximise the overall thermal efficiency of the bio-diesel CCHP
(June –September). system. The overall thermal efficiency is 80%, a significant per-
formance that helps to lower the carbon footprint of the building.
4.3 Commissioning The total life-cycle carbon emission was off-set by on-site renew-
The CCHP was installed and commissioned to test the system able energy generated by PV and bio-diesel CCHP systems.
performance. The instantaneous testing results of the generator The commissioning was performed to test the performance
and absorption cooling systems are plotted in Figure 12. At the of the CCHP system. The instantaneous data including gener-
design power generation (100 kWe), the absorption chiller is ator output power, absorption chiller cooling capacity, supply
able to deliver a cooling capacity of 70 kW. The COP is at 1.1 and return chilled water temperatures were logged and investi-
with overall thermal efficiency of 80%. As shown in Figure 12, gated. With several rounds of condensing water temperature
the chilled water temperature can achieve the design conditions, calibrations, it is observed that the system is able to deliver
i.e. supply temperature at 98C and return temperature at 128C. design cooling capacity and design chilled water temperatures. A
More testing results are expected in the future after a longer comprehensive analysis of commissioning is expected in the
period of occupancy of the building. future when more testing data are available.

232 International Journal of Low-Carbon Technologies 2016, 11, 222–234


Design and commission a zero-carbon building

Downloaded from https://academic.oup.com/ijlct/article/11/2/222/2198318 by guest on 14 May 2023

Figure 12. Output of bio-diesel CCHP.

International Journal of Low-Carbon Technologies 2016, 11, 222–234 233


T.S.K. Ng et al.

REFERENCES [8] Chan ALS, Chow TT, Fong SKF, et al. Generation of a typical meteorological
year for Hong Kong. Energy Convers Manage 2006;47:87– 96.
[9] Electrical & Mechanical Services Department. Code of practices for energy
[1] Energy Information Administration. Annual energy review 2011, efficiency of building services installation 2012, Hong Kong, 2012.
Washington, USA, 2012. [10] Buildings Department. Code of practice for overall thermal transfer value in
[2] Electrical & Mechanical Services Department. Hong Kong energy end-use buildings, Hong Kong, 2011.
data 2012, Hong Kong, 2012. [11] Electrical & Mechanical Services Department. Energy consumption indica-
[3] Hui SCM. Zero energy and zero carbon buildings: myths and facts. In: tors and benchmarks for residential, commercial and transport sectors by
Proceedings of the International conference on Intelligent Systems, Structures Dec 2012. http://ecib.emsd.gov.hk/en/indicator_cmc.htm
and Facilities (ISSF2010): Intelligent Infrastructure and Buildings, Hong [12] Building and Construction Authority. The island’s first retrofitted zero
Kong, January 2010, 15 – 25. energy building, Singapore. www.bca.gov.sg/zeb/default/html
[4] Givoni B, Noguchi M, Saaroni H, et al. Outdoor comfort research issues. [13] Liu H, Qiu G, Shao Y, et al. Preliminary experimental investigations
Energ Buildings 2003;35:77– 86. of a biomass-fired micro-scale CHP with organic Rankine cycle. Int J
[5] United Kingdom Green Building Council (UKGBC). Report on carbon Low-carbon Technol 2010;5:81– 7.
reductions in new non-domestic buildings. London, UK, 2007. [14] Environmental Protection Department and Electrical & Mechanical

Downloaded from https://academic.oup.com/ijlct/article/11/2/222/2198318 by guest on 14 May 2023


[6] Integrated Environment Solutions (IES). www.iesve.com Services Department. Guidelines to account for and report on greenhouse
[7] Hall IJ, Prairie RR, Anderson HE, et al.. Generation of a typical meteoro- gas emissions and removals for buildings (commercial, residential or insti-
logical year. In: Proceedings of the 1978 Annual Meeting of the American tutional purposes) in Hong Kong 2010 edition, Hong Kong, 2010.
Section of the International Solar Energy Society, , 1978, 669 – 71.

234 International Journal of Low-Carbon Technologies 2016, 11, 222–234

You might also like