Products
General Catalog
www.air-sys.com.cn www.air-sys.com
Company Profile
AIRSYS is a refrigeration temperature control solution provider GE, PHILIPS, SIEMENS, UNITED IMAGING, CANON, etc.
with all value chain services, providing consulting, design,
product, engineering, operation and transformation for data In the semiconductor manufacturing industry, we introduce
center, telecommunication, medical imaging diagnosis, technology and transform it to break through the technical
semiconductor manufacturing and power storage industries. threshold of the industry, and the innovative cooling technology
makes a very positive contribution to domestic chip industry.
In the data center industry, we provide efficient and energy saving
refrigeration solutions from the traditional CRAC to the cutting- In the power storage industry, with years of experience in
edge indirect evaporative cooling and server liquid cooling, chiller design and development, our power storage supporting
which secures critical data infrastructure for operators, Internet refrigeration scheme stands out, providing exclusive schemes for
companies, finance, energy, education and government units. big clients in the power storage industry at home and abroad
such as Fluence, BYD, etc.
In the telecommunications industry, we offer integrated, split,
indoor installation or outdoor installation schemes with a variety With a global vision, we have set up 6 wholly-owned overseas
of energy saving technologies suitable for different environmental subsidiaries in the US, the UK, Germany, Brazil, Singapore and
requirements, providing all-in-one solution for scheme and the Philippines and have two manufacturing centers in China
strategy consulting, product customization development, and the United States. We also provide all value chain services for
engineering construction and operation maintenance for China localized consulting, design, product, engineering, operation and
Mobile, China Telecom, BT, Verizon, Reliance, Vodafone and other maintenance and transformation.
world-renowned operators.
After years of development, we have truly become an
In the medical imaging industry, our high precision and reliable international company, originating in China and going to the
supporting refrigeration solution is the image quality assurance of world.
2
Global Footprint
3
Core Value
Reliability We are chasing of ultimate products and services only because of promise to our custoners
and partners.
We are chasing of best attitude and results only because of promise to our colleagues and
shareholders.
We are chasing of highest ideal and value only because of promise to the environment and
the world.
Efficiency Efficiency is the golden rule we respect in satisfying customers and partners.
Efficiency is also the golden rule we drive our products and service to meet operational
requirements.
We continue to dig and understand deeper of customer needs and create effective
solutions.
We respect the division and cooperation between colleagues and departments, which
make us more efficient.
We respect the needs and relationships between our customers and partners, which
make us more successful.
We respect the rules of the world, the institution, the processes and obedience, which
support us facing every challenge.
4
Social Responsibility
Making the world respect AIRSYS is our ideal
Making employees be proud of AIRSYS our
Energy Saving
expectation
Making the environment balance is our vision World is facing the challenge of energy shortage,
By continuous innovation of technology and quality especially in ICT industry,the revolution in information
service, AIRSYS can create more value for customers storage, processing and transmission result more
than expected, and let the world be symbiotic. and more energy consumption. Energy efficiency
has always been the core value and responsibility of
Airsys. We use various kind of technologies, such as
free cooling chiller, air-conditioner, independent free
cooling unit, EC fan, DC compressor, battery cooler,
scroll compressor and displacement air distribution
scheme, to help our customer to cut their energy bill.
We improve the manufaction process and operation,
and strictly examine suppliers, to achieve low
carbon and environmental protection in the whole
Vision environment of business activities.
High Reliability
ICT environment cooling requires high reliability.
Airsys has always taken reliability as the most
important value and build into every aspect of our
business process and every employee’s mind. We
assure every product produced is highly reliable by
Manufacturing Facility selection of component, design validation, IE and QC,
100% test, process control on installation and service.
As the largest ICT cooling product manufacturing
Our product meet various international standard such
facility in Asia, Airsys GuAn has a total area of 80,000
as CE, UL, RoHS, CCC.
sqm among which 30,000 sqm are covered plant.
Equipped with production line for heat exchanger,
sheet metal, powder painting, assembly line and
performance test chamber, this facility can produce
different type of ICT cooling product or more than
100,000 units a year.
5
Research and Development Service Network
Our R&D team is formed by experienced HVAC AND Airsys has a well established ser vice network
electric engineers. Apart from the standard products, throughout China and major international regions. Our
we have rich experience in developing custom made team, call center and CRM platform provide fast and
products for our customer. We can quickly deliver the professional service covering installation, emergency
technical proposal, prototype, laboratory performance intervention, maintenance, contract operation, online
test report and real site test according to customer’s failure analysis, IAQ analysis.
requirement.
6
Airsys and ICT Industry
Telecom Operator – China Mobile Telecom Operator – China Telecom
Major Cooling Supplier Major Cooling Supplier
Strategic Partner for “Green Action Plan” Long Term Partner, supply CRAC for its large Data Center.
Research and consulting service on shelter cooling
energy saving and related standard, developing the Telecom Operator - Reliance
software for energy saving calculation, product. One of the three major operators in India
Supply CRAC for its large Data Center
Strategic Cooling Supplier
Completed Design, Prototype and Pilot order within 3
Telecom Operator – Vodafone
months, delivered 25,000 units within 12 months period.
Global Cooling Supplier
The units have shown the best of its kind in terms of
Jointly develop various cooling products with significant failure rate, energy consumption in the market of India.
energy saving features Won the Best Supplier Award in year 2007 and 2008
Help to improve both CAPEX and OPEX
Telecom Operator - Verizon
Telecom Operator – British Telecom One of the largest mobile operators in the US
One of the largest operators in Europe
Gone through 3 years of real site testing, highly
Global Cooling Supplier recognized by the customer for its reliability, energy
Develop customized cooling product efficiency and overall performance. Specified in the
Provide turnkey solution including site survey, new Verizon Wireless Shelter standard. Become its first
installation, and product supply. Chinese supplier.
7
AIRSYS Product & Solutions
Cabinet Telecom Shelter Data Center
CRITICOOL HYDROCOOL
Air volume:114~1493kW Air volume:597.7kW-7735kW
Ventilation & Heat Exchanger
FREECOOL
Air volume:1000~3450m3/h
FREECOOL-HD
Air volume:2400~21600m3/h
FREECOOL-AD
Air volume:18000m3/h
8
OPTIMA
OPTIMA-HD is one type of precision air conditioners with high density cooling
capacity by using chilled water, applicable to large and medium-sized data
center and electronic equipment room. It has a wide range cooling capacity, high
operating reliability and stability, the density of cooling capacity is up to 80kW/
m2 which can save a lot of space in equipment room. Equipped with EC fan,
OPTIMA-HD has a high operating efficiency, precise control of temperature +/-
1C, relative humidity +/-5% which can assure the reliable and stable environment
of the data room. Chilled water coil work with chiller plant or central free cooling
tower, system is simple, reliable, while the operating cost is lower.
OPTIMA-HD has two types: single circuit and dual circuits. Each circuit of dual
circuits can be redundancy each other or work simultaneously or rotation
between mechanical cooling and chilled water of free cooling.
OPTIMA DXA O/U A1~A5 CMEG, AMAE series air condenser, User spare chilled Water
DC CMEH series dry cooler or Cooling tower, PUG pump group, User spare
DXW
chilled Water
DXA Free Cooling air inlet box, CMEG, AMAE series air condenser
Free Cooling air inlet box, CMEH series dry cooler or Cooling tower, PUG
DXW
DFC pump group
CWD Free Cooling air inlet box, User spare chilled Water
DXA CMEG, AMAE series air condenser
None
DXW CMEH series dry cooler or Cooling tower, PUG pump group
DXA CMEG, AMAE series air condenser, User spare chilled Water
FC
DXW CMEH series dry cooler or Cooling tower, PUG pump group
DXA CMEG, AMAE series air condenser, User spare chilled Water source
OPTIMA-INV O/U A1~A5
DC CMEH series dry cooler or Cooling tower, PUG pump group, User spare
DXW
chilled Water source
DXA Fresh Air Inlet Box, CME, AMAE series air condenser
DFC Fresh Air Inlet Box, CMEH series dry cooler or Cooling tower, PUG pump
DXW
group
9
OPTIMA (-DFC/FC/DC) .DXA/DXW
(1) Return air dry bulb temperature 24°C, RH50%, condensing temperature 47°C;
(2) Return air dry bulb temperature 24°C, RH50%, chilled water inlet/outlet 7°C/12°C.
(3) Return air dry bulb temperature 24°C, RH50%, free cooling water inlet/outlet 7°C/12°C.
(4) The cooling capacity@indoor temperature and outdoor temperature difference (ΔT) is 5°C compressor not operating;
(5) The cooling capacity@indoor temperature and outdoor temperature difference (ΔT) is 10°C, compressor not operating;
10
OPTIMA-INV (-DFC/FC/DC) .DXA/DXW
Model 16V1A1 20V1A1 25V1A2 30V1A2 35V1A2 40V1A3 45V2A3
Air Supply O:Up flow; U:Down flow
Power Supply 380V/3Ph/50Hz
Cooling Capacity
DXA (1) kW 16.7 20.2 25.4 30.5 35.2 41.3 45.1
DXW (2) kW - - 26.7 31.1 36.1 44.1 46
FC/DC Coil cooling Capacity (3) kW 18.6 22.9 29.6 37.3 40.5 43.6 55.2
DFC unit free cooling Capacity
Free Cooling (4) kW 10.7 12 15 16.2 21.3 22 23
Free cooling (5) kW 21.3 24 30.1 32.4 42.5 44 45.9
Compressor (6) Hermetic inverter scroll compressor
Supply Fan
Type Caseless backward EC centrifugal fan
Qty. of Fan n. 1 1 1 1 1 2 2
Air Volume m3/h 5750 6350 7500 8900 9600 12600 13600
Electric Heater kW 6 6 9 9 9 13.5 13.5
Humidifier kg/h 3 3 5 5 5 8 8
Outdoor Unit (DXA) (7)
Model × Qty n. AMAE5×1 AMAE6×1 AMAE8×1 AMAE10×1 AMAE12×1 AMAE15×1 AMAE8×2
Model × Qty n. CMEG5×1 CMEG8×1 CMEG10×1 CMEG10×1 CMEG×15×1 CMEG×20×1 CMEG8×2
OPTIMA-INV-FC.DXA Dry Cooler CMEH20×1 CMEH20×1 CMEH30×1 CMEH40×1 CMEH50×1 CMEH60×1 CMEH70×1
OPTIMA-INV (-FC) .DXW Dry Cooler - - CMEH30×1 CMEH40×1 CMEH50×1 CMEH60×1 CMEH70×1
DFC Free coolingAir Inlet Box S1×1 S1×1 S2×1 S2×1 S1×2 S1×2 S1×2
Width*Depth*Height mm 875×890×1960 1480×890×1960 1750×890×1960
Weight
OPTIMA-INV (-DFC) .DXA kg 320 340 390 410 460 540 630
OPTIMA-INV-FC/DC.DXA kg 350 370 490 510 750 700 790
OPTIMA-INV (-DFC) .DXW kg - - 410 430 510 570 630
OPTIMA-INV-FC/DC.DXW kg - - 520 540 790 850 910
Model 50V2A3 60V2A4 70V2A4 80V2A4 90V2A5 100V2A5
Air Supply O:Up flow; U:Down flow
Power Supply 380V/3Ph/50Hz
Cooling Capacity
DXA (1) kW 50.6 60.9 71.3 81.5 90.3 102.3
DXW (2) kW 53.1 62.1 72.2 83.2 93.6 105.6
FC/DC Coil cooling Capacity (3) kW 55.2 63.1 77.5 84.1 102.5 116.2
DFC unit free cooling Capacity
Free Cooling (4) kW 24.7 30.1 32.4 35.5 41.5 47.1
Free cooling (5) kW 59.5 60.1 64.8 70.9 83.1 94.2
Compressor (6) Hermetic inverter scroll compressor
Supply Fan
Type Caseless backward EC centrifugal fan
Qty. of Fan n. 2 3 3 3 3 3
Air Volume m3/h 13600 17800 19200 21000 24600 27900
Electric Heater kW 13.5 18 18 18 18 18
Humidifier kg/h 8 8 8 8 8 8
Outdoor Unit (DXA) (7)
Model × Qty n. AMAE8×2 AMAE10×2 AMAE12×2 AMAE15×2 AMAE18×2 AMAE20×2
Model × Qty n. CMEG10×2 CMEG10×2 CMEG15×2 CMEG20×2 CMEG20×2 CMEG20×2
OPTIMA-INV-FC.DXA Dry Cooler CMEH70×1 CMEH80×1 CMEH50×2 CMEH50×2 CMEH60×2 CMEH70×2
OPTIMA-INV (-FC) .DXW Dry Cooler CMEH70×1 CMEH80×1 CMEH50×2 CMEH50×2 CMEH60×2 CMEH70×2
DFC Free coolingAir Inlet Box S1×2 S1+S2 S1+S2 S1+S2 S2×2 S2×2
Width*Depth*Height mm 1750×890×1960 2490×890×1960 3095×890×2050
Weight
OPTIMA-INV (-DFC) .DXA kg 690 760 830 910 1010 1080
OPTIMA-INV-FC/DC.DXA kg 830 1080 1130 1220 1420 1510
OPTIMA-INV (-DFC) .DXW kg 720 810 960 1050 1120 1210
OPTIMA-INV-FC/DC.DXW kg 1000 1120 1160 1280 1470 1590
(1) Return air dry bulb temperature 24°C, RH50%, condensing (5) The cooling capacity@indoor temperature and outdoor temperature
temperature 47°C; difference (ΔT) is 10°C, compressor not operating;
(2) Return air dry bulb temperature 24°C, RH50%°C, condensor water (6) For dual-system units, it has hermetic inverter scroll compressor also
inlet/outlet 30°C/35°C,inverter compressors are at economic speed included a hermetic fixed speed compressor;
(3) Return air dry bulb temperature 24°C, RH50%°C, free cooling water (7) AMAE series air-cooled condenser configuration EC fan, CMEG series
inlet/outlet 7°C/12°C. air-cooled condenser configuration AC fans, one of the series is selected
(4) The cooling capacity@indoor temperature and outdoor temperature according to your needs.
11
difference (ΔT) is 5°C compressor not operating;
OPTIMA (-DFC) .CW/CWD
Model S1 S2
G4 Panel Air filter
Size mm 825×545×10 717×545×10
Qty n. 1 2
F7 Bag Filter
Size mm 828×545×46 717×545×46
Qty n. 1 2
Air Inlet/Outlet Dimensions
Length mm 732 1320
Width mm 410 410
Dimensions & Weight
Width mm 870 1480
Depth mm 680 680
Height mm 1450 1450
Weight kg 90 143
12
OPTIMA-HD
OPTIMA-HD is one type of precision air conditioners with high density
cooling capacity by using chilled water, applicable to large and medium-
sized data center and electronic equipment room. It has a wide range
cooling capacity, high operating reliability and stability, the density
of cooling capacity is up to 80kW/m2 which can save a lot of space in
equipment room. Equipped with EC fan, OPTIMA-HD has a high operating
efficiency, precise control of temperature +/- 1C, relative humidity +/-5%
which can assure the reliable and stable environment of the data room.
Chilled water coil work with chiller plant or central free cooling tower,
system is simple, reliable, while the operating cost is lower.
OPTIMA-HD has two types: single circuit and dual circuits. Each circuit of
dual circuits can be redundancy each other or work simultaneously or
rotation between mechanical cooling and chilled water of free cooling.
OPTIMA-HD.CW/CWD
(1) Return air dry bulb temperature 24°C, RH50%, chilled water inlet/outlet 7°C/12°C;
(2) The cooling capacity@indoor temperature and outdoor temperature difference (ΔT) is 5°C compressor not operating;
(3) The cooling capacity@indoor temperature and outdoor temperature difference (ΔT) is °C, compressor not operating.
13
DATACOOL
DATACOOL Precision air conditioning units are widely applied in small/medium data
center and computer rooms. DADATCOOL unit adoptsnew technologies, using efficient
compressor and fans and optimizingrefrigerating system configuration, to achieve its
high efficiency and reliability, realizing COP >2.9, temperature control accuracy <±1°C
while humidity control accuracy <±5%.
The compact structure and light weight makes easy installation. The unit canbe fully
maintained from the front, greatly reducing the maintenance cost.
DATACOOL unit is available in 4 different air flow scheme: front up flow, downflow,
displacement flow, top flow, offering more options for different customers.
380V/3Ph/50Hz
(1) Return air dry bulb temperature 24°C, RH50%, Outdoor dry bulb temperature 35°C.
220V/1Ph/50Hz
Model 5R1C0 7R1C0
Air Supply O: Up-front throw; U: Bottom Throw; DL: Replacement; TP: Top throw
Power Supply 220V/1Ph/50Hz
Cooling Capacity (1) kW 5.8 7.4
Compressor Hermetic Rotor
Supply Fan
Qty. of Fan n. 1 1
Air Volume m3/h 1650 1650
Electric Heater kW 2.3 2.3
Humidifier kg/h 3 3
Air Cooled Condenser CMDG3×1 CMDG4×1
Width*Depth*Height mm 650×580×1910
Weight kg 148 149
(1) Return air dry bulb temperature 24°C, RH50%, Outdoor dry bulb temperature 35°C.
14
CHILLROW
CHILLROW is applicable to large and medium-sized data center and
electronic equipment room. It is installed closely with the server cabinets
and refrigerating independently. The unit takes away the high density heat
load through horizontal air supply scheme. The unit adopts adjustable
support legs and wheels which is convenient to remove.
CHILLROW has two cooling types, air-cooled direct expansion (DXA) and
chilled water (CW) .
CHILLROW.DXA
(1) Return air dry bulb temperature 37°C,RH24%, Outdoor dry bulb temperature 35°C;
CHILLROW.CW
(1) Return air dry bulb temperature 37°C, RH24%, water inlet/outlet temperature 10°C/15°C;
15
CYBERCOOL-MOD
CYBERCOOL-MOD range is a versatile product which combines the
advantages of traditional precision air conditioning with modular design
technology, simplifying system expansion. New units are able to be
integrated into an existing CYBERCOOL -MOD arrangement simply through a
standard network cable connection.
The single coil chilled water system can directly use existing chilled water
source as cold source, without outdoor air-cooled condensing unit. The unit
has lower initial investment, more energy efficient and higher reliability.
CYBERCOOL-MOD.DXA
Model 25E1X0 30E1X0 35E1X0 40E1X1 40E2X1 50E2X1 60E2X3 70E2X3 80E2X3 90E2X3 100E2X3
Air Supply O:Up flow; U:Down flow
Power Supply 380V/3Ph/50Hz
Cooling Capacity (1) kW 27.7 32.7 38.1 42.6 43.6 52.7 65.5 74.5 86.1 94.6 105.1
Compressor Hermetic scroll
Supply Fan
Type Caseless backward EC centrifugal fan
Qty. of Fan n. 1 1 1 1 1 1 2 2 2 2 2
Air Volume m3/h 7300 9000 9350 11500 11500 12500 18000 21000 24000 26500 28000
Electric Heater kW 6 6 6 6 6 6 12 12 12 12 12
Humidifier kg/h 5 5 5 8 8 8 8 8 8 8 8
Air Cooled Condenser CMEG10*1 CMEG10*1 CMEG15*1 CMEG20*1 CMEG8*2 CMEG10*2 CMEG10*2 CMEG15*2 CMEG20*2 CMEG20*2 CMEG20*2
Refrigerant Pump RPU12*1 RPU12*1 RPU12*1 RPU12*1 RPU22*1 RPU22*1 RPU22*1 RPU22*1 RPU22*1 RPU22*1 RPU22*1
Width*Depth*Height mm 1090×965×1975 1455×965×1975 2370×965×1975
Weight kg 310 330 360 400 450 480 650 700 735 790 800
(1) Return air dry bulb temperature 24°C, RH50%, Outdoor dry bulb temperature35°C
CYBERCOOL-MOD.CW
Model 40X1 60X1 80X2 90X2 100X2 120X2 140X2 160X3 180X3 210X3
Air Supply O:Up flow; U:Down flow
Power Supply 380V/3Ph/50Hz
Cooling Capacity (1) kW 47 61.8 81 95 107 122.3 140.9 160.5 185.1 210.1
Supply Fan
Type Caseless backward EC centrifugal fan
Qty. of Fan n. 1 1 2 2 2 2 2 3 3 3
Air Volume m3/h 11700 15500 20000 22500 25000 31000 33000 37500 40000 46000
Electric Heater kW 4.5 4.5 9 9 9 9 9 13.5 13.5 13.5
Humidifier kg/h 3 3 8 8 8 8 8 8 8 8
Width*Depth*Height mm 965×990×1975 1880×990×1975 2795×990×1975
Weight kg 330 350 525 540 560 740 780 900 910 1150
(1) Return air dry bulb temperature 24°C, RH50%°C, water inlet/outlet 7°C/12°C.
16
MOBILECOOL-OUTDOOR
MOBILECOOL-OUTDOOR is a packaged type telecommunication base station
special air conditioner and designed for telecommunication base station,
small electronic equipment room. The unit features including good structure,
easy maintenance, high sensible ratio, high efficiency, and high reliability.
The air supplied from the front lower portion of the unit, which conforms
with the air flow rules well, making the heat exchange more efficient.
Model 3R1C1 5R1C1 7E1C2 9E1C2 13E1C3 18E1C4 25E1C5 32E1C5 32E2C5
Air Supply DL: Replacement
Power Supply
230V-1PH-60Hz ● ● ● ● ● ● ●
230V-3PH-60Hz ● ● ● ● ● ●
380V-3PH-60Hz ● ● ● ● ●
460V-3PH-60Hz ● ● ●
220V-1PH-50Hz ● ● ● ● ● ● ●
380V-3PH-50Hz ● ● ● ● ● ●
Cooling Capacity (1) kW 3.8 5.7 8.1 9.8 13.8 17.7 25.8 32.8 32.5
Free Cooling Capacity (2) kW 3.4 4.6 7.2 8.6 10.3 15.7 23.7 30.2 30.2
Compressor Rotor Scroll
Supply Fan
Type EC centrifugal fans
Air Volume m³/h 840 1140 1780 2130 2550 3900 5900 7500 7500
Condenser Fan
Type Axial Fan
Air Volume m³/h 3500 3400 3740 6290 6500 7800 15600 15600 15600
Width mm 700 700 1009 1009 1159 1359 1460 1460 1460
Depth mm 620 620 698 698 698 698 1075 1075 1075
Height mm 1930 1930 2148 2148 2148 2110 2445 2445 2445
(1) Return air dry bulb temperature 26.7°C, RH50%, Outdoor dry bulb temperature35°C, the compressor is operating;
(2) Indoor temperature and outdoor temperature difference (ΔT) is 10°C, the compressor is not operating.
17
MOBILECOOL-INDOOR
MOBILECOOL-INDOOR is a package type telecommunication base station
special air conditioner and designed for telecommunication base station, small
electronic equipment room. The unit features including good structure, easy
maintenance, high sensible ratio, high efficiency, and high reliability. The air
supplied from the front lower portion of the unit, which conforms with the air
flow rules well, making the heat exchange more efficiency.
(1) Return air dry bulb temperature 26.7°C, RH50%, Outdoor dry bulb temperature35°C, the compressor is operating;
(2) Indoor temperature and outdoor temperature difference (ΔT) is 10°C, the compressor is not operating.
18
UNICOOL
UNICOOL - second generation Wall Package Unit is a variable speed air
conditioner with integrated free cooling (economizer) , Which is a high
efficiency cooling product of AIRSYS solutions, designed primarily to for
electronic and mechanical equipment shelters, container data center,
E-Houses.
UNICOOL has been serving worldwide sites with over 15 years experiences
in being a reliable friend of IT facilities. It is designed to safely work across a
range of operating conditions, with high efficiency, green refrigerant, various
power supply and installation arrangements.
In this era of huge data generating and flowing to every corner, UNICOOL
units are going to wherever bits and bytes are blazing with the enhanced
design combining yesterday’s experience and today’s innovation.
230V/3PH/60Hz ● ●
460V/3PH/60Hz ● ●
380V/3PH/50Hz ●
Cooling Capacity (1) kW 7.2 10.2 10.3 14.8 15.1 28.1 28.1 28.1
Free Cooling Capacity (2) kW 9.8 12.1 10.8 19 16.9 32.4 32.4 40.2
Compressor Rotor Scroll
Supply Fan
Type EC centrifugal fans
Air Volume m³/h 1900 2800 2500 4400 3900 7500 7500 9300
Condenser Fan
Type Axial Fan
Air Volume m³/h 3740 7000 6500 8300 7800 17000 17000 17000
Refrigerant
type R410A
control Electronic expansion valve
Width mm 1010 1141 1159 1355 1359 1460 1460 1460
Depth mm 698 680 698 912 794 1075 1075 1075
Height mm 2148 2360 2148 2360 2110 2448 2448 2448
Weight kg 229 293 287 390 380 632 590 590
(1) Return air dry bulb temperature 26.7°C, RH50%, Outdoor dry bulb temperature35°C, the compressor is operating;
(2) Indoor temperature and outdoor temperature difference (ΔT) is 10°C, the compressor is not operating.
19
DATACOOL-PACKAGE
DATACOOL-PACKAGE air conditioner with built-in fresh air free cooling system is
specially designed for small/medium data center and electronic equipment room.
Due to its proper working logic and standard EC supply fan, DATACOOL-PACKAGE can
maximumly works in free cooling mode with the lowest power consumption, saving
huge energy and lowering the operation cost.
DATACOOL-PACKAG is available in 2 different air flow schemes: up flow and down flow,
offering more options for different customers to increase its application flexibility.
(1) Return air dry bulb temperature 24°C, RH50%, Outdoor dry bulb temperature35°C, the compressor is operating;
(2) Indoor temperature and outdoor temperature difference (ΔT) is 10°C.
20
METROCOOL
METROCOOL unit is specially designed for industry environment, standing up
to high temperature, heavy pollution and continuous working demand and
offering high efficiency, strict fire proofing, various power supplies and widely
working condition with high reliability.
Electrical heaters with different capacity are available for this unit as options
to satisfy different application requirement.
(1) Indoor return air dry ball temperature of 27 °C, wet bulb 19 °C, outdoor environment dry bulb temperature of 35 °C, wet bulb 24 °C.
21
TELECOOL
TELECOOL cabinet cooling unit is cooling with compressor or heat pipe, and it
will remove the heat inside the cabinet to outside. It can also keep the dust and
heat outside the cabinet, avoiding problems from using fan. The inside cabinet
can be maintained at an ideal temperature for electrical components which
effectively guarantees the stability of the electronic equipment and improves
the reliability of the whole system. TELECOOL cabinet cooling unit includes
AIRSYS Cabinet Air Conditioner (ACA) , AIRSYS Cabinet Heat Exchanger (ACE) .
It can be widely used for outdoor communication cabinets, battery cabinets,
electric cabinets, industry control cabinets etc.
22
DC series Cabinet Air Conditioner
Heat Exchanger
23
FREECOOL-AD
FREECOOL-AD, an adiabatic evaporation cooling unit, is designed for small/medium data center
or electronic equipment room. Direct free cooling will be used when outdoor temperature is low;
if ambient temperature rises, adiabatic mode will be used. Ambient air will blow through the
built-in pad saturated with water, evaporating water by air flow. The unit can save energy around
30%~90% by reducing running hours of other air conditioning units.
The unit adopts EC centrifugal fan that can adjust its air volume according to customer's
demand.
FREECOOL-AD is modular designed and convenient for transportation.
Model 20F2A2
Air Supply (1) DN
Power Supply 400V/3Ph/50Hz
cooling Capacity (2) kW 34.0
Free Cooling Capacity (3) kW 32.2
Supply Fan
Type EC centrifugal fans
Qty n. 2
Air Volume m³/h 18000
Water consumption kg/h 90.9
Pump AC centrifugal pump
Width*Depth*Height (4) mm 1900×1180×2460
Weight kg 558
FREECOOL-HD
FREECOOL-HD intelligent ventilation unit is applied in small/medium data center and electronic
equipment room. The unit introduces outdoor fresh air with lower temperature to cool
equipment room.
By using the FREECOOL-HD unit, the running hours of other air conditioning units can be highly
reduced, achieving power energy saving around 30~90%.
The FREECOOL-HD unit using EC fans can adjust the air volume automatically according to the
temperature difference with the lowest power consumption.
FREECOOL-HD without refrigeration system realizes easy installation and convenient
maintenance. The unit is available in 2 different air flow schemes: up flow and down flow, and 2
installation positions: outdoor and indoor, offering more options for different customers.
24
FREECOOL
FREECOOL is one of the intelligent ventilation family which provides perfect
energy-saving solutions for retrofit of shelters and small data centers. While
working with existing AC units, FREECOOL introduces outdoor fresh air with
lower temperature to cool equipment room, which can highly reduce the
running hours of original air conditioners to achieve power energy saving
around 30~90%.
25
Outdoor Condenser and Dry
Cooler
The covers of CMEG air-cooled condenser are produced by aluminum sheet,
which has characteristics of light weight, Anti-corrosion, anti-rust, etc. The
condenser is equipped with adjustable speed axial fan and high efficiency
heater exchanger. Vertical or horizontal installation of the condenser is
available.
CMDG air-cooled condenser is used for small precision air conditioner or base station air conditioner. The covers of
CMD condenser are produced by coating sheet metal, which has characteristics of anti-corrosion, anti-rust, etc. The
condenser is equipped with adjustable speed axial fan and high efficiency heater exchanger. Only vertical installation of
the condenser is available.
The covers of CMEH dry cooler are produced by aluminum sheet, which has characteristics of light weight, Anti-
corrosion, anti-rust, etc. The condenser is equipped with adjustable speed axial fan and high efficiency heater exchanger.
Vertical or horizontal installation of the condenser is available, free cooling type unit can choose PUG pump group box.
VMEG series condenser, the shell is made of galvanized steel sheet, surface spraying, anti-corrosion and anti-embroidery.
The unit is equipped with an external rotor, Axial Fan, and the fan speed is adjustable, which is energy-saving and
reliable. Equipped with high efficiency heat exchanger, electrical box.
VMEG
Model VMEG25 VMEG30 VMEG40 VMEG50 VMEG55 VMEG65 VMEG80
Power Input ~220V/50Hz 3-380V/50Hz
Capacity kW 25 30 40 50 55 65 80
Max Air Volume m3/h 8500 14000 14000 21000 21000 21000 28000
Qty. of Fan n. 1 1 1 1 1 1 2
Maximum Power Input kW 0.63 1.13 1.13 1.85 1.85 1.85 2.26
Max Current A 3.0 2.35 2.35 4.0 4.0 4.0 4.7
Air Intake Pipe Φ mm 22 22 22 22 22 22 22
Liquid Pipe Φ mm 16 16 16 16 16 16 16
Width*Depth*Height mm 1380×1000×1295 1380×1000×1550 1380×1000×1570 2000×1200×1550
(1) Heat Capacity calibration conditions: inlet air temperature 35°C, condensation temperature 50°C.
26
CMDG/CMEG
Model CMEG5 CMEG8 CMEG10 CMEG15 CMEG20 CMEG25
Power supply 220V/1Ph/50Hz
Capacity kW 20.5 29.6 35.4 47.6 67.4 73.1
Fan
Qty n. 1 1 1 2 2 2
3
Air Volume m /h 5600 10100 9700 11600 20100 19100
Input Power kW 0.37 0.63 0.63 0.74 1.26 1.26
Input Current A 1.7 3 3 3.4 6 6
Gas pipe ODF 19 22 22 22 28 35
Liquid pipe ODF 12 16 16 19 19 22
Width*Depth*Height mm 1140×475×770 1340×620×1070 1540×620×1070 2400×630×1135
Weight kg 47 95 110 130 155 185
(1) The capacity is rated at entering air temperature 35°C and condensing temperature 50°C condition.
AMAE
Model AMAE5 AMAE6 AMAE8 AMAE10 AMAE12 AMAE15 AMAE18 AMAE20
Power Supply 220V/1Ph/50Hz
Capacity kW 24.2 29.7 36.2 41.3 50.7 57.2 62.4 74.3
Fan
Qty n. 1 1 1 1 2 2 2 2
Air Volume m3/h 12500 11600 11800 11500 23500 22000 23400 22600
Input Power kW 0.63 0.63 0.63 0.63 1.26 1.26 1.26 1.26
InputCurrent A 2.8 2.8 2.8 2.8 5.6 5.6 5.6 5.6
Gas pipe ODF 19 19 19 22 22 22 22 28
Liquid pipe ODF 16 16 16 16 16 16 19 19
27
CMEH
Model CMEH50 CMEH60 CMEH70 CMEH80
Power Supply
Capacity kW 56.7 61.5 75.2 83.1
Heat Exchanger
Water Flow m3/h 9.3 10.2 10.6 11.8
Pressure Drop kPa 57.6 69.1 72.3 78.5
Fan
Qty n. 2 2 3 3
Air Volume m3/h 23200 21800 33600 32400
Input Power kW 1.5 1.5 2.3 2.3
Input Current A 6.6 6.6 10.1 10.1
Width*Depth*Height mm 2590×620×1325 2690×620×1325 3500×620×1335 3570×620×1335
Weight kg 175 195 235 255
(1) Heat capacity calibration conditions: inlet air temperature 35 °C, inlet water temperature 45 °C.
PUG
(1) The standard pump box with two pumps, one for use, the performance parameters in the table is for a single pump parameter.
28
CRITICOOL-FC
The CRITICOOL series are AIRSYS air-cooled screw chillers. The products are
designed and produced in accordance with the ISO9000 quality system, strict
pressure vessel specifications and refrigeration equipment safety standards.
After continuous innovation and improvement, the full load coefficient of
performance (COP) of the equipment is as high as 5.6 or higher, which
greatly reduces the user's operating costs.
Perfect design, powerful control and protection system and world class
accessory configuration can ensure the safe and effective operation of the equipment under various loads. AIRSYS
chillers are widely used in hotels, hospitals, theaters, office buildings, shopping centers, schools and other places with
their high
efficiency, low noise, low failure rate, safety and reliability. They can also be used as cooling sources for central air
conditioning
systems. Textile, chemical, nuclear power, food processing and other places provide chilled water for process cooling
systems. At the same time, the unit can also make full use of the residual heat after condensation during the refrigeration
operation to provide customers with sanitary hot water.
Since CRITICOOL-FC series (free-cooling) units were put on the market in 2005, this product has been widely used in the
field of
data center equipment process cooling and has received wide acclaim from users.
CRITICOOL-FC
Model 115 140 175 205 240 275 330 395
Cooling Capacity (1) kW 397 493 618.1 723.8 844.5 965.0 1162.0 1393.0
Cooling Capacity (2) kW 467.1 580.1 727.3 851.6 992.8 1136.0 1364.0 1640.0
Free cooling Capacity (3) kW 467.1 580.1 727.3 851.6 992.8 1136.0 1364.0 1640.0
Refrigerant R134a
Compressor Qty n. 1 1 1 1 1 1 2 2
Length mm 5240 5240 6245 7250 8255 9260 10265 11270
Width mm 2300 2300 2300 2300 2300 2300 2300 2300
Height mm 2460 2460 2460 2460 2460 2460 2460 2460
Weight kg 5400 6030 6580 7350 8500 8930 11380 12350
(1) Norminal paremeter refers to the following conditions: outdoor temperature=35°C, chilled water inlet/outlet=12°C/7 °C, fouling factor=0.018
(m2*°C) /kW.
(1) IDC cooling paremeter refers to the following conditions: outdoor temperature=12°C/18°C, outdoor temperature=35 °C, fouling factor=0.018 (m2*°C)
/kW.
(3) Free cooling parameter refers to the following conditions: outdoor temperature= ambient temperature of free cooling condition only; chilled water
inlet/outlet= 18°C/12°C, fouling factor= 0.018 (m2*°C) /kW
29
ADIACOOL
ADIACOOL is a air cooled dry cooler with extra adiabatic cooling feature.
It is designed to provide free cooling, the primary chilled water cooling, to
the Datacenters in conjunction with the supplimentary chiller providing
mechanical cooling. The cooling capacity ranges 100~1400kW. Thanks to the
adiabatic cooling capacity and high temperature of the chilled water plant,
ADIACOOL could deliver no less than 80% of the cooling needed, regardless
where the DC is located
The above data is based on: 30% ethylene glycol solution, inlet and outlet water temperature: 35/19°C, ambient temperature 15°C, altitude below
500m.
The above data is based on: 30% ethylene glycol solution, inlet and outlet water temperature: 35/19°C, ambient temperature 15°C, altitude below
500m.
30
HYDROCOOL-F
HYDROCOOL-F series water-cooled variable frequency centrifugal chillers are
suitable for large data centers and various industrial process applications,
with a wide range of cooling capacity and high reliability. All series of units
meet the national first-class energy efficiency standards, saving users a lot of
operating costs, integrating single-shaft direct drive, aerospace pneumatic
technology, aerodynamic design, optimizing the overall flow field efficiency.
The isentropic efficiency of the compressor is improved, the back-to-back
two-stage compression structure balances the thrust, prolongs the service
life and improves the efficiency, and the closed impeller design reduces
leakage and improves the efficiency.
31
HYDROCOOL-E
HYDROCOOL-E series high-efficiency/ultra-high-efficiency centrifugal chillers are
suitable for large data centers and various industrial process applications, with a
wide range of cooling capacity and high reliability. In order to obtain more efficient
and energy-saving heat exchange efficiency, the evaporator adopts full falling film
evaporation technology, which adopts spraying technology, and the refrigerant
realizes film evaporation on the surface of efficient heat exchange tubes, thus
improving heat exchange efficiency and liquid distribution uniformity.The optimized
structure of the condenser enhances the heat transfer performance. The bottom is
provided with a pure countercurrent subcooling section with multiple turbulent flows, so that the subcooling degree is
improved, and the performance is improved.
32
Model 1900H10 2000H10 2100H10 2200H10
Cooling Capacity (1) kW 6680 7032 7384 7735
Evaporate Water flow (2,3) m3/h 1149 1210 1270 1330
3
Condenser Water Flow (2,3) m /h 1436 1512 1587 1663
Length mm 5290 5290 5290 5290
Width mm 3150 3150 3150 3150
Height mm 3180 3180 3180 3180
Weight kg 27490 27840 28076 28310
33
HYDROCOOL-G
HYDROCOOL-G series water-cooled magnetic levitation centrifugal chillers
are suitable for large data centers and various industrial process applications,
with a wide range of cooling capacity and high reliability. Aerodynamic
design for more efficient full-load operation; magnetic bearings avoid friction
for more efficient part-load operation and offer a large IPLV of 12.29. Magnetic
bearing centrifugal chiller has magnetic bearing technology, aerodynamic
technology, permanent magnet synchronous motor and full falling film
evaporation technology.
34
Control system
All AIRSYS products are equipped with AIRSYS advanced microcomputer control system. Hardware meets industrial / ICT environment
requirements, high reliability, anti-jamming. Control program embodies AIRSYS many years’ experience in ICT environment-air
conditioner produce, fully consider reliable, energy saving, convenient needs, are the core values embodied AIRSYS products.
By micro-controller, a large number of parameters can be set flexibly, including automatic / manual, operating logic selection,
parameter calibration, the ON / OFF the designated member.
By running status and time records, you can keep abreast of the operational status of the unit, part of the on / off status, running time
and other information.
Alarm and security alarm information and provide numerous security protection, including restart, current and voltage, phase
sequence protection, pressure protection, thermal protection, and so on.
There are several ways to achieve remote monitoring, remote setting parameters, upload programs, remote on / off, remote alarm, etc.
Remote Control And Monitoring Network
The unit can be remote controlled or monitored by many kinds of methods as follows:
N2
Ethernet network cable RS485 Bus
Wireless connection 2
Wireless router
N1
Monitoring Computer
GSM communication network
N16
Direct connection 1
34%BUBDBCMF
Units direct connection type
RS485-RS232 Converter N1
Direct connection 2
34%BUBDBCMF
RS485-RS232 Converter
RS485 Bus N2
RS232 cable
34%BUBMJOF
Direct connection 3
35
阿尔西制冷工程技术(北京)有限公司 阿尔西新加坡有限公司 AIRSYS SINGAPORE PTE. LTD
地址:北京市石景山区苹果园西小街 19 号宏坤盛通大厦 10 层 Add: 50, Tagore Lane Entrepreneur Centre, #03-04 (F),
Tel: +86(0)10 68656161 Singapore 787494
全国免费咨询电话:400-820-5515 Tel: +65 62787188 Fax: +65 68416301