LOAD FREQUENCY CONTROL OF SINGLE AREA AND TWO AREA SYSTEMS-TIE LINE
BIAS CONTROL-AUTOMATIC VOLTAGE REGULATOR AND ITS DYNAMICS
Q.1) Two generating units rated 300 MW and 400 MW have governor speed regulation of 6%
and 4% respectively from no load to full load. Both the generating units are operating in parallel
to share a load of 600 MW. Assuming free governor action, the load shared by the larger unit
is _______ MW.
Sol.1)
Assume No – load speed regulations are equal
f1 =50− P1
3
and f2 =50− P2
200
3
50− P2 = 50− P1
200
2P1−3P2=0 ......(ii)
P1=180MW
P2=120MW
Machine (i) which has better speed regulation will be loaded first to its full load rating, so it will
operate on maximum load of 200 MW
2×200−3P2=0
P2=400/3=133.33MW
Q.3) A 250-MW, 60-Hz turbine generator set has a speed regulation of 5 percent based on its
own rating. The generator frequency decreases from 60 Hz to a steady state value of 59.7Hz.
Determine the increase in the turbine power output.
Sol) The change in the angular frequency is
.
Δω= =-0.005pu