Professional Documents
Culture Documents
1.10 PLCs - Installation
1.10 PLCs - Installation
Introduction… Introduction…
Metal enclosures are used since they provide shielding that helps PLCs are always mounted horizontally with the name of the
minimize the effects of electromagnetic radiation that may be manufacturer facing out and right side up
generated by surrounding equipment Proper spacing of components in a manner that provides adequate
The heat that accumulates in the enclosure must be dissipated into room within the enclosure may be sufficient for heat dissipation
the surrounding air Additional cooling provisions may be required where high internal
The temperature inside the enclosure must not exceed the or ambient temperatures are encountered
maximum operating temperature of the controller, 60℃ maximum
1
Wiring Wiring…
How do we connect the PLC to the system being controlled? Wiring a device to the PLC involves:
Wiring involves connection of such devices as: Proper provision of power to the devices
photoelectric detectors Ensuring that all connections are made properly and to the
lights etc.
Wiring… Wiring…
The following are some general guidelines for PLC wire routing: Low level signal conductors such as thermocouples and serial
Use the shortest possible wire runs for I/O signals communication should be run as shielded twisted pair and routed
When possible, conductors that are run from the PLC enclosure to separately
another location should be in a metal conduit as the metal can serve A fiber optic system, which is totally immune to all kinds of
as a shield against EMI electrical interference, can also be used for signal wiring
Never run signal wiring and power wiring in the same conduit
2
PLC Power Connection PLC Power Connection…
The power requirement for the PLC being used will vary Power connection to the ac units is not so critical
depending on the model selected Proper fuses must be inserted in the power line connections to
PLCs operate on a wide range of power, 24v, 110v, 120v, 240v etc. protect both the PLC and the power wiring from overcurrent either
Some manufacturers produce units that will operate on any voltage from accidental shorts or equipment failure causes
without any modifications to the unit The installation manual for the PLC being used will provide fusing
Connection of power to the dc type units require that careful information for that unit
attention be paid to ensuring that (+) and (-) power wire are
correctly connected. Failure to do so can result in serious damage
to the PLC
21-Jul-18 Structured Text 9 21-Jul-18 Structured Text 10
3
Output Wiring Commissioning
Output units are available with a common terminal and isolated Commissioning: preparing a control process for start-up
from each other Involves a series of tests to ensure that the PLC, ladder logic
The type of output unit selected will depend upon the outputs being program, the I/O devices, and all associated wiring operate
controlled and the power available for controlling those devices according to specifications
Typically, power for driving output devices must be separately Before commissioning any control system, you should have a good
provided since there can be a wide range of requirements understanding of how the control system operates and how various
depending upon the device components interact
Commissioning… Commissioning…
The following are general steps to be followed when c) Examine the PLC’s indicator lights. If power is properly applied,
commissioning a PLC system: the power indicator should be on and there should be no fault
a) Before applying power to the PLC or the input devices, indication. If the PLC does not power up properly, it may be
disconnect or otherwise isolate any output device that could faulty. PLCs rarely fail, but if they do fail, it usually happens
potentially cause damage or injury. Typically, this precaution will immediately upon powering up.
pertain to outputs that cause movement such as starting a motor or d) Verify that you have communication with the PLC via the
operating a valve programming device that is running the PLC programming
b) Apply power to the PLC and input devices. Measure the voltage siftware
4
Commissioning… Commissioning…
e) Place the PLC in a mode that prevents it from energizing its f) Manually activate each input device, one at a time, to verify that
output circuits. Depending on the mode of the PLC, this mode the PLC’s input status lights turn on and off as expected. Monitor
may be called disable, continuous test, or single-scan mode. This the associated condition instruction to verify that the input device
mode will allow you to monitor input devices, execute the corresponds to the correct program address and that the
program, and update the output image file while keeping the instruction turns true or false as expected
output circuits de-energized g) Manually test each output. One way of doing this is by applying
power to the terminal where the output device is wired. This test
will check the output field device and its associated wirirng
Commissioning…
h) After verifying all inputs, the outputs and program addresses,
verify all preset values for counters, timers etc.