Transformers

 Problem  Set  
For  doubts/clarifications:  knrao.ee@gmail.com      facebook.com/knrao.ee    
1)  
a) Estimate  active  cross  sectional  area  of  the  core  of  a  10  turn  single  phase  
inductor  for  a  terminal  voltage  of  100V  at  50Hz.  The  flux  density  is  to  be  
about  0.9  Wb/m2  .  Give  suitable  dimensions  for  core.    
b) Take  stacking  factor  =  0.9  and  estimate  Gross  cross  sectional  area.  
2) Estimate  reduction  of  volume,  expressed  as  a  percentage  of  the  original  
volume  of  a)  Core  Iron  b)  Copper  in  a  transformer  when  original  steel  plates  
worked  at  a  flux  density  of  0.8  Tesla  are  replaced  by  others  of  Silicon  steel  
worked  at  flux  density  of  1.2  Tesla  assuming  the  total  flux  to  remain  same.  
Assume  square  core.  
3) The  required  no  load  ratio  in  a  single  phase,  50  Hz,  core  type  transformer  is  
6000/250V.  Find  the  number  of  turns  in  each  winding  if  maximum  flux  to  be  
55mWb.  
4) A  voltage  v=155.5  sin  377t  +  15.5  sin  1131t  V  is  applied  to  the  primary  of  the  
transformer.  Neglecting  leakage,  determine  the  instantaneous  and  rms  values  
of  core  flux.  Let  N1  =  200T  with  200V,  60Hz  source  
***  
5) Consider  a  simple  power  system  consisting  of  an  ideal  voltage  source,  an  
ideal  step  up  transformer,  a  transmission  line,  an  ideal  step  down  
transformer  and  a  load.  The  voltage  of  source  is  480  |0  V,  the  impedance  of  
transmission  line  is  (3+j4)  Ω,  impedance  of  load  is  (30+j40)  Ω.  What  turns  
ratio  would  be  required  to  reduce  transmission  line  loss  to  1%  of  total  power  
produced  by  generator.  
***  
6)  
a) Find  the  operating  flux  for  given  magnetic  circuit  with  No.  of  turns=100,  
length  of  core=2000Cm,  Area  of  cross  section  of  core=25Cm2,  Current  
injected=1A.  relative  permeability=2500  
b) Repeat  problem  4)  and  calculate  current  to  be  injected  for  operating  flux  
of  47.12  μWb  if  magnetic  core  has  now  2  mm  airgap.    
c) Determine  also  the  magnetic  energy  stored  in  the  iron  and  in  the  air  gap  
of  magnetic  circuit.  
***  
7) The  flux  in  a  magnetic  core  is  sinuisoidally  varying  at  200Hz.  The  maximum  
flux  density  is  2Tesla  and  eddy  current  loss  is  15W.  If  the  frequeny  is  raised  
to  400Hz,  maximum  flux  density  is  reduced  to  1Tesla,  then  eddy  current  
losses  will  be   a)  reduced  to  half   b)get  doubled  c)reduce  to  one-­‐forth
  d)remain  same  
8) A  single-­‐phase  10kva,  50Hz  transformer  with  1kv  primary  winding  draws  
0.5A  and  55W  at  rated  voltage  and  frequency  on  no  load.  A  second  
transformer  has  a  core  with  all  its  linear  dimensions  √2times  the  
corresponding  dimensions  of  the  first  transformer.  The  core  material  and  
lamination  thickness  are  the  same  in  both  transformers.  The  primary  
windings  of  both  the  transformers  have  the  same  number  of  turns.  If  a  rated  
voltage  of  2kv  at  50Hz  is  applied  to  the  primary  of  the  second  transformer,  
the  the  noload  current  and  power  respectively  are        a)0.7A,  77.8w  
  b)0.7A,  155.6w     c)1A,  110w     d)1A,220w  
9) A  transformer  has  hysteresis  loss  of  30W  at  240V,60Hz  supply.  The  
hysteresis  loss  at  200V,  50Hz  supply  is?  
10)A  transformer  has  Iron  loss  of  90W  at  60Hz  supply  and  52W  a  40Hz  supply.  
Both  losses  being  measured  at  same  peak  flux  density.  The  total  iron  losses  in  
the  transformer  at  50Hz  supply  will  be  ?  
11)A  230V,  50Hz  single  phase  transformer  has  eddy  current  loss  of  30W.  If  this  
transformer  is  excited  with  DC  source  of  same  magnitude  eddy  current  losses  
will  be  _______     a)30W     b)25W     c)0W     d)None  of  
the  above  
12)A  voltage  of  (200  wt-­‐50  sin  3wt)  is  applied  to  a  250  turn  transformer  winding  
having  negligible  resistance  and  leakage.  By  what  percentage  will  the  eddy  
current  loss  in  the  iron  be  reduced  if  the  applied  voltage  is  altered  to  200  sin  
wt?  Given  w=100π  
13)The  flux  in  a  magnetic  core  is  sinuisoidally  varying  at  200Hz.  The  maximum  
flux  density  is  2Tesla  and  eddy  current  loss  is  15W.  If  the  frequeny  is  raised  
to  400Hz,  maximum  flux  density  is  reduced  to  1Tesla,  then  eddy  current  
losses  will  be   a)  reduced  to  half   b)get  doubled  c)reduce  to  one-­‐forth
  d)remain  same  
***  
14)A  5kV,  25Hz  single  phase  transformer  has  copper  loss  of  1.4%,  hysteresis  loss  
of  0.6%  and  eddy  current  loss  of  0.5%  of  full  load  output.  If  this  transformer  
is  operated  on  10kV,  50Hz  supply  system,  what  will  be  these  losses  if  the  
current  in  the  windings  remain  same  
***  
15)A  1000VA,  230/115V,  transformer  has  been  tested  to  determine  its  
equivalent  circuit.  The  results  are  given  as   O.C:  115V,0.11A,3.9W  and  
S.C.:17.1V,8.7A,38.1W  
a) Find  equivalent  circuit  of  this  transformer  referred  to  LV  side.  
b) Find  efficiency  at  rated  conditions  and  0.8pf    
16)A  50Hz,  single  phase  transformer  draws  short  circuit  current  of  30A  at  0.25pf  
when  connected  to  16V,50Hz  source.  What  will  be  the  power  factor  if  it  is  
energized  from  16V,75Hz  source.  
17)Two  windings  of  transformer  are  indicated  by  terminal  AB  and  CD  as  shown.  
When  a  voltage  of  100V  is  applied  across  AB  with  BD  short  circuited,  a  
voltage  of  200V  appears  across  AC.  The  turns  ratio  from  CD  to  AB  is  
  a)  3   b)1   c)3  or  1   d)  2  or  1  
18)A  single  phase  transformer  has  core  loss  of  30W  at  rated  voltage  and  its  full  
load  copper  loss  is  40W.  The  percentage  of  rated  load,  at  which  a  short  circuit  
test  can  be  regarded  as  an  economic  heat  run  test  is       a)132   b)135
  c)138   d)can’t  be  determined  
***  
19)The  ratio  of  number  of  turns  per  phase  in  the  primary,  secondary  and  tertiary  
windings  of  transformer  is  10:2:1.  With  the  lag  currents  of  45A  at  0.8pf  lag  in  
secondary  and  50A  at  0.71  pf  lag  in  tertiary  winding,  find  the  primary  current  
and  power  factor.  
***  
20)A  20kva  2000/200V  single  phase  transformer  has  (0.02+j0.06)  pu  
impedance.  To  maintain  load  side  voltage  at  200V  at  full  load  0.8pf  lag,  the  
voltage  required  to  be  applied  on  primary  side  of  transformer  is  ____  
21)A  transformer  has  400/200V  rating  and  it  has  a  pf  of  0.8  lag  on  secondary  
side  when  it  is  loaded.  About  40V  is  required  to  circulate  rated  current  on  
short  circuit,  at  pf  of  0.2.  The  voltage  regulation  of  transformer  at  full  load  0.8  
pf  lag  is  ____  
22)10kva,  400V/200V  single  phase  transformer  with  (3+j6)%    impedance  
delivers  25A  to  a  resistive  load.  The  load  side  voltage  of  transformer  is  ___  
23)A  400V/200V  transformer  has  full  load  voltage  regulation  of  Xpu  at  0.8pf  lag.  
If  this  transformer  is  used  as  an  auto  transformer  with  voltage  ratings  of  
400V/600V  or  200V/600V,  then  its  voltage  regulation  would  be       a)  
x/3,  x/3   b)2x/3,  x/3   c)2x/3,2x/3   d)x/3,2x/3  
24)A  3phase  transformer  is  supplied  at  6000V  on  delta  connected  side.  The  
terminal  voltage  on  the  star  connected  side  when  loaded  at  0.8pf  lag  is  415V.  
the  equivalent  resistance  and  reactance  drops  are  1%  and  5%.  Find  turns  
ratio??  
***  
25)20kVA  single  phase  transformer  has  efficiency  of  98%  at  full  load  and  also  at  
half  full  load.  The  power  factor  is  unity  in  both  the  cases.  The  efficiency  of  
transformer  at  3/4th  full  load  at  upf  is  ___?  
26)A  transformer  has  maximum  efficiency  of  90%  at  full  load  upf.  The  efficiency  
of  transformer  at  half  full  load  upf  is  ____  
27)The  percentage  resistance  and  reactance  of  10kVA,  400/200V  single  phase  
transformer  are  2%  and  6%  respectively.  If  the  constant  losses  of  
transformer  are  1%,  the  maximum  possible  efficiency  of  transformer  is  ____  
28)A  transformer  has  max  efficiency  of  95%  at  15kva  upf.  The  all  day  efficiency  
of  transformer  when  full  load  of  20kva  at  upf  for  12  hours  and  no  load  rest  of  
the  day  on  transformer  is  ____  
29)The  maximum  efficiency  of  a  100kva    single  phase  transformer  is  98%  at  
80%  of  full  load  upf.  If  the  leakage  impedance  of  transformer  is  5%,  the  
voltage  regulation  of  the  transformer  at  half  full  load  0.8pf  lead  is  ___  
30)The  efficiency  at  upf,  if  a  6600/384V,  200kva  single  phase  transformer  is  
91%  at  full  load  and  half  full  load.  The  pf  on  no  load  is  0.2  and  full  load  
regulation  at  0.8pf  lag  is  4%.  Find  equivalent  circuit  parameters  referred  to  
LV  side.  
***  
31)A  10kva  2500/250  V,  two  winding  transformer  is  to  be  used  as  an  auto  
transformer  with  source  voltage  of  2500V.  Calculate  power  output,  power  
transformed,  power  conducted.  If  the  efficiency  of  the  two  winding  
transformer  at  0.6pf,  full  load  is  96%,  find  the  autotransformer  efficiency  at  
full  load  same  pf.  
32)A  single  phase  ideal  transformer  has  1000turns  and  400  turns  for  its  primary  
and  secondary  windings  respectively.  The  secondary  winding  delivers  a  
resistive  load  of  600kw  between  A  &  C  and  a  load  of  (60+j60)  Ω  between  A  &  
B.  Between  A  &  B  there  are  300turns  and  between  B  &  C  there  are  100  turns.  
For  primary  voltage  of  30kv,  find  primary  current  and  primary  input.  
33)A  three  phase  load  of  1500kw  pf  0.8  lagging  is  supplied  from  a  tap  changer  
transformer,  11/33kv,  delta  on  LV  and  star  on  HV  side.  R  per  phase  =  0.5  Ω  on  
LV  and  1.5  Ω  on  HV.  X  per  phase=6.5  Ω  on  LV  and  20  Ω  on  HV  respectively.  
Each  line  conductor  has  R=10  Ω  and  X=6  Ω.  If  the  low  voltage  side  is  supplied  
at  11kv,  find  the  setting  of  tap  changer  to  give  33kv  at  full  load.  
***  
34)Two  100kva  single  phase  transformers  are  connected  in  parallel  on  both  
primary  and  secondary  sides.  One  transformer  has  impedance  drop  of  
(0.5+j8)%  and  the  other  has  (0.75+j4)%.  Consider  equal  turns  raitos  for  both  
transformers.    
a) How  will  they  share  load  of  180kva  at  0.9  pf  lag  
35)The  short  circuit  tests  of  two  single  phase  3300/200V  transformers  with  
equal  voltage  ratios  are  as  follows.  A:  100v,230A,600W;  B:80v,230A,1100W.  
transformers  are  running  in  parallel  on  the  same  primary  and  secondary  bus  
bars.  What  is  the  maximum  kva  that  can  be  extracted  from  the  combination  
without  over  loading  any  of  transformer.  
36)A  500kva,  500V  single  phase  transformer  with  (1+j4)%  Ω  is  connected  in  
parallel  with  250kva,  500V  single  phase  transformer  with  (1.5+j6)%  Ω  
respectively.  The  secondary  terminal  voltages  on  open  circuit  are  510V  in  
first  transformer  and  500V  in  the  second  with  the  secondary  windings  
connected  in  parallel.  Calculate  
a) The  cross  current  in  the  secondaries  on  no  load  
b) The  secondary  current  in  each  transformer  when  load  of  700kw  at  upf  is  
connected  
c) The  terminal  voltage  at  this  load  
***  
37)If  a  positive  sequence  current  passes  through  transformer  and  its  phase  shift  
is  30  degrees,  the  negative  sequence  current  flowing  through  the  transformer  
will  have  a  phase  shift  of     a)  30  degrees  b)-­‐30  degrees  
  c)120degrees  d)-­‐120degrees  
***  
38)Three  single  phase  transformers  are  connected  in  delta  supply  100A  per  line  
to  a  3phase  3  wire  system.  
a) What  is  the  current  in  each  transformer  if  one  unit  develops  fault  and  is  
removed  
b) By  how  much  is  the  capacity  of  the  set  reduced  for  the  same  temperature  
rise.  
c) Find  the  current  in  each  of  the  remaining  transformers  if  the  line  current  
corresponds  to  rating  in  b)  
39)Two  furnaces  1&2  are  supplied  at  80V  by  means  of  a  scott  connected  
transformer  combination  from  a  3phase  6600V  system.  The  voltage  of  
furnace  1  is  leading.  Calculate  the  line  currents  on  the  three  phase  side  when  
the  furnaces  take  500kW  and  800kW  repectively.  
a) At  upf  
b) Furnace  2  at  upf  and  furnace  2  at  0.7pf  lag  