WorkstationST* Recorder
These instructions do not purport to cover all details or variations in equipment, nor
to provide for every possible contingency to be met during installation, operation,
and maintenance. The information is supplied for informational purposes only, and
GE makes no warranty as to the accuracy of the information included herein.
Changes, modifications, and/or improvements to equipment and specifications are
made periodically and these changes may or may not be reflected herein. It is
understood that GE may make changes, modifications, or improvements to the
equipment referenced herein or to the document itself at any time. This document is
intended for trained personnel familiar with the GE products referenced herein.
GE may have patents or pending patent applications covering subject matter in this
document. The furnishing of this document does not provide any license whatsoever
to any of these patents.
This document contains proprietary information of General Electric Company, USA
and is furnished to its customer solely to assist that customer in the installation,
testing, operation, and/or maintenance of the equipment described. This document
shall not be reproduced in whole or in part nor shall its contents be disclosed to any
third party without the written approval of GE Energy.
GE provides the following document and the information included therein as is and
without warranty of any kind, expressed or implied, including but not limited to any
implied statutory warranty of merchantability or fitness for particular purpose.
If further assistance or technical information is desired, contact the nearest GE Sales
or Service Office, or an authorized GE Sales Representative.
Section Page
Introduction .................................................................................................... 3
Capture Buffer Collection .............................................................................. 4
Live Data Collection....................................................................................... 4
Trip Log Collection ........................................................................................ 4
EPA Log Collection ....................................................................................... 5
Acronyms and Abbreviations ......................................................................... 5
Terms.............................................................................................................. 6
A Workstation download stops all current collections while it downloads the new
configuration. A component download restarts collections for the component based
on the new configuration.
• Capture Buffer
• Live Data
• Trip Log
• EPA Log
The .dcaST files are stored in a location defined in the Recorder tab of the
WorkstationST component. The file directory structure is:
Continuous collections sample the data at the specified scan rate and save it if the
change in value has exceeded the deadband. A new file is created every hour to keep
the file sizes manageable.
Triggered Edge collections sample data for up to 60 seconds before, and for up to 60
seconds after, the event. During this time, the data is sampled at the specified scan
rate and saved if the change in value has exceeded the deadband.
Triggered Level collections sample data for up to 60 seconds before the event, while
the event is true, and for up to 60 seconds after the event. During this time, the data
is sampled at the specified scan rate and saved if the change in value has exceeded
the deadband. A new file is created every hour to keep the file sizes manageable.
The Live Data collection samples the data once a second with no deadbands, and
then saves it as a .dcaST file. The variables for the live data are the variables being
collected in the Capture Buffer. The Recorder uploads the list of variables from the
Capture Buffer list when it starts the Trip Log collection. These variables must be on
EGD for valid data to be collected.
The Capture Buffer collection samples the status variables of the Capture Buffers.
When all status words have transitioned to a complete state, the buffers are uploaded.
The Recorder then reads the data from the live data files, and writes the data to the
Trip Log file using the following data re-sampling.
Time Sample Rate
19 hours 10 minutes
Four hours One minute
40 minutes 10 seconds
20 minutes or until time of first sample in Capture Buffer One second
The alarms, events, and SOEs that occurred between the first sample and the last
sample in the Trip Log are requested in the Alarm Server. These alarms, events, and
SOEs are saved to the Trip Log file with a limit of 200 of each, with a maximum of
50 post-trigger.
For Dual and TMR systems, the Capture Buffers from the non-designated controller
are uploaded and saved to separate files.
EGD - A mechanism that provides access to global data between nodes supporting
the EGD protocol.
Exchange - An EGD data message consisting of a header and a body of data. The
header contains the producer ID and the exchange ID that uniquely identifies the
message. The body of data is a block of bytes in a format agreed upon by the
producer and all consumers.
OPC (OLE for Process Control) - A standard for data exchange in the industrial
environment (OLE is Microsoft’s Object Language Embedding). The OPC
foundation provides specifications for various OPC standards such as OPC DA (Data
Access) and OPC AE (Alarm and Event).
Producer - The EGD node configured to send data messages. The source of the
data samples for an exchange.
Refresh - To bind the configuration for each consumed exchange for a particular
consumed component.
Unbound Variables - Variables required by a consumer that were not found in the
producer configuration during the bind.