NFY-Fire Pump Controllers UL - Naffco - 101803

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

UL CERTIFIED ELECTRIC MOTOR

MICROPROCESSOR BASED CONTROLLER


MODEL NFY-SDM1 STAR DELTA
NAFFCO Electric Motor Controllers for fire pumps are
listed by Underwriters Laboratories (UL file number
EX15064), in accordance with UL218 (Standard for
Fire Pump Controller), UL508a (Standard for Industrial
Control Panel), NFPA20 (National Fire Protection
Association Pamphlet 20- Standard for Centrifugal Fire
Pumps), NFPA70 (National Electric Code) and NEMA.
Only high quality UL listed or UL recognized components
are used in these panels to guarantee the best possible
reliability. Also high quality UL listed enclosures are
used.
This controller is completely wired, assembled,
programmed and tested at the factory before shipment,
and ready for immediate installation.

MOTOR STARTING CHARACTERISTICS

RATING
Motor Power Rated Voltage Frequency Rated Current Short Circuit Rating
(HP) (V) (Hz) (A) (KA)
15 27
20 34
25 44
30 51
40 66
50 83
60 103
75 128
380 - 415 50 / 60 100
100 165
125 208
150 240
200 320
250 403
300 482
350 560
400 636

CAT.NO.NF/MPBFPC/06/15 Rev. 1 Referance No :-NAFF-H01-EXP-7328(0) www.naffco.com


Page 26 of 5
106
UL / FM CERTIFIED DIESEL ENGINE
MICROPROCESSOR BASED CONTROLLER
MODEL NFY-DM1

NAFFCO Fire Diesel Engine Controller are listed by Underwriters Power ratings suitable for 12/24 volts DC operating voltage, 110
Laboratories (UL number EX15064), in accordance with / 220 volts AC input voltage, 50/60 Hz. These controllers are
UL218 (Standard for Fire Pump Controller), UL508a (Standard
for Industrial Control Panel), NFPA20 (National Fire Protection
Only high quality UL listed or UL recognized components are
Association Pamphlet 20 – Standard for Centrifugal Fire Pumps),
used in these panels to guarantee the best possible reliability.
NFPA70 (National Electric Code) and NEMA.
Also high quality UL listed enclosures are used. This controller
Also approved by FM approvals (Factory Mutual), in accordance is completely wired, assembled and tested at the factory before
with FM standard 1321 / 1323 (Standard for Fire Pump Controller). shipment, and ready for immediate installation.

RATINGS

Line Voltage DC Voltage


(VAC) (VDC)

220/110 12/24

Referance No :-NAFF-H01-EXP-7328(0) Page 63 of 106


UL LISTED JOCKEY PUMP CONTROLLER
MODEL NFY-JSD1 REDUCED VOLTAGE/
STAR – DELTA (OPEN TRANSITION)
MODEL NFY-JDO1 DIRECT ON LINE

NAFFCO Jockey Pump Controllers for fire pumps are UL recognized components are used in these panels
listed by Underwriters Laboratories (UL file number to guarantee the best possible reliability. Also high
E309408), in accordance with UL508a (Standard for quality UL listed enclosures are used.
Industrial Control Panel), NFPA70 (National Electric
Code) and NEMA. The controller is completely wired, assembled and
tested at the factory before shipment, and ready for
Power ratings vary from 1.5 to 40 horsepower, 380 to immediate installation.
415 volts, 50 or 60 Hz. Only high quality UL listed or

STANDARD FEATURES
• Main disconnected switch with rotary handle, sized for
disconnecting motor horsepower and voltage.
• Motor Starter rated to motor’s horsepower, with
thermal and short circuit protection.
• Rated motor contactors.
• Circuit breaker for protection of control circuit.
• Selector switch for Hand—Off—Automatic operation.
• Star—Delta starting timer. ( in Model NFY-JSD1 )
• Power ON/Healthy indicator/free contact.
• Pump Run indicator/free contact.
• Pump Trip indicator/free contact.
• Adjustable pressure switch.
• UL listed enclosure.

SEQUENCE OF OPERATION
This controller is working under three modes automatic
off and manual mode.

OFF (RESET) MODE


In this mode, the controller is considered to be off and
can’t start the Jockey pump.

AUTOMATIC START
In this mode, controller will start the Jockey pump
automatically and directly at low pressure detection
by the pressure switch, and will stop the pump
automatically and directly when the pressure goes up
again.

MANUAL START
In this mode, controller will start the Jockey pump
directly, and will not stop until selector switch is
switched off or in Auto mode.

12 www.naffco.com Referance No :-NAFF-H01-EXP-7328(2) Page 17 of 23