RELACION TEKNIK
OBJEKTI:
Digitally signed by
Ing.Zenun Katana
Dr.Elton Hasani
1
Digitally signed by
PËRMBAJTJA
1. KODET DHE REFERENCAT
2. MATERIALET
BETONI
ARMATURA HEKURIT
STRUKTURA METALIKE
4 KRITERET E PROJEKTIMIT
KOMBINIMI I NGARKESAVE
EFEKTI I PËRDREDHJES AKSIDENTALE
FAKTORI I RËNDËSISË SIPAS KATEGORIZIMIT
SPOSTIM I NDËRKATIT(DRIFTI)
SPEKTRI I SJELLJES ELASTIKE
SPEKTRI LLOGARITËS
3
Digitally signed by
Analiza strukturale për këtë objekt është bërë në përputhje me EUROKODET si vijon.
Gjithashtu llogaritjet dhe konstruimet i janë referuar edhe kushteve shqiptare të projektimit.
2. MATERIALI
2.1 Betoni
Betoni- Klasa C30/37 për themelet.
Pesha vetjake
= kg/m3
Moduli i elasticitetit
Ec = 340770 daN/cm2
fctm = 32 daN/cm2
Ku
4
Digitally signed by
= 0.1
Rezistenca në tërheqje
Moduli i elasticitetit
Ec = 2100000 daN/cm2
A5 = 12%
S = 1.15
Rezistenca e lejuar
fyd = 3700 daN/cm2
Profilet e celikut janë te plota HEA dhe IPE tubolare CHSdhe RHS. Celiku i përdorur është S-275 për
profilet e realizuar në të nxehtë dhe S-235 për profilet e realizuar në të ftohtë tubolar.
Kollonat janë realizuar Croos me profile HEA të inkastruara në themelat tip pllake . Trarët kryesor janë IPE
të lidhura me nyje tip inkastrim me kollonat dhe trarët sekondarë janë IPE të lidhura me nyje tip sharnierë
me trarët kryesorë . Distanca midis trareve sekondare eshte pranuar 1.5 ml ne menyre qe te shmanget perdre-
dhja e trareve kryesore.Llamarina e perdorur per shkelje eshte e kodrinuar me spensor 6mm . Lartësia e stru-
kturës është 9.2ml , kurse lartësia e katit 0 është 4.2 ml dhe e katit i është 5 ml.Themelet janë tip plintash të
lidhur me trarë lidhës . Mbulesa dhe ndërkati është soletë kompozite me lartësi h = 130 mm . Struktura është
me simetri të njëanëshme dhe me nyje të paspostueshme, sepse ndërkati është i ngurtë. Përmasat plane të stru-
kturës janë 17ml x 6 ml .
5
Digitally signed by
Sandwich t-40 mm
Në përputhje me Ec1 dhe aneksin kombetar Shqiptar KTP89 ngarkesat e përkohshme të përdorura në
këtë projekt kanë vlerat e mëposhtme
Për analizën e kësaj strukture është marrë në konsideratë edhe efekti nga veprimi sizmik i zonës . Ky
efekt është konsideruar në përputhje me karakteristikat e strukturave Mbitokësore . Efekti ndikues i
ngarkesave sizmike është i papërfillshëm në këtë strukturë celiku, kjo për shkak të lartësisë të vogël të
strukturës dhe peshës të vogël të ndërkatit. Gjithësesi një kontroll i përgjithshëm është kryer në këtë ra-
st .
7
Digitally signed by
q0 x Kd x Kr u/=5.2
3. KRITERET E PROJEKTIMIT
Ngarkesat janë kombinuar siç janë treguar dhe më poshtë, ku IE është veprimi sizmik për gjendjen
e lejuar nën egzaminim, Gt është vlera karakteristikë e veprimit të përkohshëm, Q1k vlera
karakteristikë e veprimit variabël të situatës së krijuar prej ngarkesave , Qik është vlera
karakteristikë e situatës variable i: ; γg , γp and γq janë faktorë të sigurisë pjesore , ψ0i është koefiçent
kombinimi i cili jep 95% të vlerës së aksionit variabël i, ψ2i është koefiçenti i kombinimit i cili jep
vlerën e përafërt të veprimit të përkohshëm variable i.
8
Digitally signed by
SLD
Sizmik IE + Gk + Σi(Ψ0i Qik)
Veprimi sizmik është marë në konsideratë me dy komponentët e saj ortogonale , të cilësuar Iex
dhe Iey ; ku të dy veprimet respektive të komponenteve përfaqësojnë të njëjtën spëktër reagimi
dhe plotesojnë kombinimin kuadratik (CQC), metodë e cila është përdorur si kombinim i të dyjave
përbërësve.
Dy kombinimet e mundeshme janë si vijon
Efektet inerciale të ngarkesave sizmike të hedhura do të vlerësohen duke marë parasysh dhe masat
e lidhura dhe me të gjitha ngarkesat e gravitetit që shfaqen në kombinimin që vijon .
Gk + Σi(ψEi Qik)
9
Digitally signed by
10
Digitally signed by
Nëse shtangësia laterale dhe masa janë të shperndara në plan mjaftueshmerisht simetrike, efekti
aksidental i përdredhjes mund të llogaritet ose të kihet parasysh duke shumëfishuar efektin e
veprimit të çdo ngarkese individuale në çdo element me një faktor δ të dhënë nga:
Ku:
x është distanca nga elementi i marrë në konsideratë (nga qendra e masës së ndërtesës në plan të
matur perpendikular me drejtimin e aksionit sizmik të marrë në konsideratë) .
Le është distanca ndërmjet dy elementëve më të largët të ngarkuar, e matur perpendikular me
drejtimin e veprimit sizmik të marre në konsideratë.
Ndërtesat janë kategorizuar në klasa të ndryshme sipas rëndësisë, duke u nisur nga konseguencat
e një kolapsi për jetën njerëzore dhe për rëndësinë e tyre në sigurinë publike dhe civile, mbrojtja e
menjëhershme përgjatë një lëkundje sizmike, si dhe pasojat sociale dhe ekonomike të një kolapsi
.
Klasat e rëndësisë të një objekti janë të karakterizuar nga një sërë faktorësh të ndryshëm i të cilat
janë të lidhura me pasojat dhe dështimet e një strukture.
Faktori i rëndësisë i = 1,0 është marrë në konsideratë për llogaritjen e objektit .
“Kërkesat mbi dëmin e limituar” është quajtur e pranueshme nëse gjatë një veprimi sizmik me nje
probalitet më të madh se veprimi sizmik respektiv që i korrespondon kërkesës së jokolapsit,
spostimi i katit të jetë i limituar.
Për strukturat që kanë elemente jostruktural me elemente të dobët të bashkangjitur me strukturën:
dr < 0,005 h
ku: dr spostimi i ndërkatit referuar kjo limitit të mundshëm të gjendjes së dëmtimit
h lartësi ndërkati.
Për rastin tonë driftet janë të pa konsiderueshme
Spostimet e strukturës janë marrë konform Eurocod-3 duke u pranuar
dv = L / 300 per trarët kryesorë , kurse për sekondarët dv = L /200 .Spostimet horizontale janë
pranuar dr = H / 250
11
Digitally signed by
PAMJE GJATESORE
12
RELACION TEKNIK
Digitally signed by
KOLLONAT
STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------- -----------
CODE: EN 1993-1:2005/A1:2014, Eurocode 3: Design of steel structures.
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------- -----------
CODE GROUP:
MEMBER: 3 kolona 2_3 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------- -----------
LOADS:
Governing Load Case: 11 ULS /56/ 1*1.35 + 2*1.05 + 3*1.05 + 9*1.50
----------------------------------------------------------------------------------------------------------------------------- -----------
MATERIAL:
S 275 ( S 275 ) fy = 275.00 MPa
----------------------------------------------------------------------------------------------------------------------------- -----------
STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------- -----------
CODE: EN 1993-1:2005/A1:2014, Eurocode 3: Design of steel structures.
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------- -----------
CODE GROUP:
MEMBER: 29 kryesor_29 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------- -----------
LOADS:
Governing Load Case: 11 ULS /7/ 1*1.35 + 2*1.50 + 3*1.50 + 9*0.90
----------------------------------------------------------------------------------------------------------------------------- -----------
MATERIAL:
S 275 ( S 275 ) fy = 275.00 MPa
----------------------------------------------------------------------------------------------------------------------------- -----------
14
RELACION TEKNIK
Digitally signed by
STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------- -----------
CODE: EN 1993-1:2005/A1:2014, Eurocode 3: Design of steel structures.
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------- -----------
15
RELACION TEKNIK
Digitally signed by
----------------------------------------------------------------------------------------------------------------------------- -----------
VERIFICATION FORMULAS:
Section strength check:
N,Ed/Nc,Rd = 0.00 < 1.00 (6.2.4.(1))
(My,Ed/MN,y,Rd)^ 2.00 + (Mz,Ed/MN,z,Rd)^1.00 = 0.09 < 1.00 (6.2.9.1.(6))
Vy,Ed/Vy,T,Rd = 0.00 < 1.00 (6.2.6-7)
Vz,Ed/Vz,T,Rd = 0.00 < 1.00 (6.2.6-7)
Tau,ty,Ed/(fy/(sqrt(3)*gM0)) = 0.00 < 1.00 (6.2.6)
Tau,tz,Ed/(fy/(sqrt(3)*gM0)) = 0.00 < 1.00 (6.2.6)
----------------------------------------------------------------------------------------------------------------------------- -----------
LIMIT DISPLACEMENTS
STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------- -----------
CODE: EN 1993-1:2005/A1:2014, Eurocode 3: Design of steel structures.
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------- -----------
CODE GROUP:
MEMBER: 127 SHKELJE_127 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------- -----------
16
RELACION TEKNIK
Digitally signed by
----------------------------------------------------------------------------------------------------------------------------- -----------
VERIFICATION FORMULAS:
Section strength check:
sqrt(Sig,x,Ed*^2 + 3*Tau,z,Ed^2)/(fy/gM0) = 0.85 < 1.00 (6.2.1.(5))
Vy,Ed/Vy,c,Rd = 0.03 < 1.00 (6.2.6.(1))
Vz,Ed/Vz,c,Rd = 0.00 < 1.00 (6.2.6.(1))
Global stability check of member:
My,Ed/(XLT*My,Rk/gM1) + Mz,Ed/(Mz,Rk/gM1) = 0.87 < 1.00 (6.3.3.(4))
----------------------------------------------------------------------------------------------------------------------------- -----------
LIMIT DISPLACEMENTS
6.3.5 NYJET
17
RELACION TEKNIK
Digitally signed by
General
Connection no.: 1
Connection name: Fixed column base
Structure node: 121
Structure bars: 108
Geometry
Column
Section: TCAR 80x4
Bar no.: 108
Lc = 1.00 [m] Column length
= 0.0 [Deg] Inclination angle
hc = 80 [mm] Height of column section
bfc = 80 [mm] Width of column section
twc = 4 [mm] Thickness of the web of column section
tfc = 4 [mm] Thickness of the flange of column section
rc = 4 [mm] Radius of column section fillet
Ac = 12.08 [cm2] Cross-sectional area of a column
Iyc = 115.80 [cm4] Moment of inertia of the column section
Material: S 235
fyc = 235.00 [MPa] Resistance
fuc = 360.00 [MPa] Yield strength of a material
Column base
lpd = 250 [mm] Length
bpd = 250 [mm] Width
tpd = 20 [mm] Thickness
Material: S 235
fypd = 235.00 [MPa] Resistance
fupd = 360.00 [MPa] Yield strength of a material
18
RELACION TEKNIK
Digitally signed by
Wedge
Section: IPE 100
lw = 100 [mm] Length
Material: S 235
fyw = 235.00 [MPa] Resistance
Stiffener
ls = 250 [mm] Length
hs = 100 [mm] Height
ts = 10 [mm] Thickness
d1 = 20 [mm] Cut
d2 = 20 [mm] Cut
Material factors
M0 = 1.00 Partial safety factor
M2 = 1.25 Partial safety factor
C = 1.50 Partial safety factor
Spread footing
L= 300 [mm] Spread footing length
B= 300 [mm] Spread footing width
H= 900 [mm] Spread footing height
Concrete
Class C20/25
fck = 20.00 [MPa] Characteristic resistance for compression
Grout layer
tg = 30 [mm] Thickness of leveling layer (grout)
fck,g = 12.00 [MPa] Characteristic resistance for compression
Cf,d = 0.30 Coeff. of friction between the base plate and concrete
Welds
ap = 1 [mm] Footing plate of the column base
aw = 4 [mm] Wedge
as = 4 [mm] Stiffeners
Loads
19
RELACION TEKNIK
Digitally signed by
Results
Compression zone
COMPRESSION OF CONCRETE
fcd = 13.33 [MPa] Design compressive resistance EN 1992-1:[3.1.6.(1)]
fj = 10.67 [MPa] Design bearing resistance under the base plate [6.2.5.(7)]
c = tp (fyp/(3*fj*M0))
c= 54 [mm] Additional width of the bearing pressure zone [6.2.5.(4)]
beff = 112 [mm] Effective width of the bearing pressure zone under the flange [6.2.5.(3)]
leff = 188 [mm] Effective length of the bearing pressure zone under the flange [6.2.5.(3)]
Ac0 = 211.75 [cm2] Area of the joint between the base plate and the foundation EN 1992-1:[6.7.(3)]
Ac1 = 672.00 [cm2] Maximum design area of load distribution EN 1992-1:[6.7.(3)]
Frdu = Ac0*fcd*(Ac1/Ac0) ≤ 3*Ac0*fcd
Frdu = 502.97 [kN] Bearing resistance of concrete EN 1992-1:[6.7.(3)]
j = 0.67 Reduction factor for compression [6.2.5.(7)]
fjd = j*Frdu/(beff*leff)
fjd = 15.83 [MPa] Design bearing resistance [6.2.5.(7)]
Ac,n = 520.99 [cm2] Bearing area for compression [6.2.8.2.(1)]
Ac,y = 260.50 [cm2] Bearing area for bending My [6.2.8.3.(1)]
Ac,z = 260.50 [cm2] Bearing area for bending Mz [6.2.8.3.(1)]
Fc,Rd,i = AC,i*fjd
Fc,Rd,n = 824.99 [kN] Bearing resistance of concrete for compression [6.2.8.2.(1)]
Fc,Rd,y = 412.50 [kN] Bearing resistance of concrete for bending My [6.2.8.3.(1)]
Fc,Rd,z = 412.50 [kN] Bearing resistance of concrete for bending Mz [6.2.8.3.(1)]
COLUMN FLANGE AND WEB IN COMPRESSION
CL = 1.00 Section class EN 1993-1-1:[5.5.2]
Wpl,y = 341.45 [cm3] Plastic section modulus EN1993-1-1:[6.2.5.(2)]
Mc,Rd,y = 80.24 [kN*m] Design resistance of the section for bending EN1993-1-1:[6.2.5]
hf,y = 125 [mm] Distance between the centroids of flanges [6.2.6.7.(1)]
Fc,fc,Rd,y = Mc,Rd,y / hf,y
Fc,fc,Rd,y = 641.93 [kN] Resistance of the compressed flange and web [6.2.6.7.(1)]
Wpl,z = 253.95 [cm3] Plastic section modulus EN1993-1-1:[6.2.5.(2)]
Mc,Rd,z = 59.68 [kN*m] Design resistance of the section for bending EN1993-1-1:[6.2.5]
hf,z = 104 [mm] Distance between the centroids of flanges [6.2.6.7.(1)]
Fc,fc,Rd,z = Mc,Rd,z / hf,z
Fc,fc,Rd,z = 572.74 [kN] Resistance of the compressed flange and web [6.2.6.7.(1)]
RESISTANCES OF SPREAD FOOTING IN THE COMPRESSION ZONE
Nj,Rd = Fc,Rd,n
Nj,Rd = 824.99 [kN] Resistance of a spread footing for axial compression [6.2.8.2.(1)]
FC,Rd,y = min(Fc,Rd,y,Fc,fc,Rd,y)
FC,Rd,y = 412.50 [kN] Resistance of spread footing in the compression zone [6.2.8.3]
FC,Rd,z = min(Fc,Rd,z,Fc,fc,Rd,z)
FC,Rd,z = 412.50 [kN] Resistance of spread footing in the compression zone [6.2.8.3]
Tension zone
STEEL FAILURE
Ab = 2.45 [cm2] Effective anchor area [Table 3.4]
fub = 400.00 [MPa] Tensile strength of the anchor material [Table 3.4]
Beta = 0.85 Reduction factor of anchor resistance [3.6.1.(3)]
Ft,Rd,s1 = beta*0.9*fub*Ab/M2
Ft,Rd,s1 = 59.98 [kN] Anchor resistance to steel failure [Table 3.4]
20
RELACION TEKNIK
Digitally signed by
21
RELACION TEKNIK
Digitally signed by
22
RELACION TEKNIK
Digitally signed by
Shear
BEARING PRESSURE OF AN ANCHOR BOLT ONTO THE BASE PLATE
Shear force Vj,Ed,y
d,y = 0.68 Coeff. taking account of the bolt position - in the direction of shear [Table 3.4]
b,y = 0.68 Coeff. for resistance calculation F1,vb,Rd [Table 3.4]
k1,y = 2.50 Coeff. taking account of the bolt position - perpendicularly to the direction of shear [Table 3.4]
F1,vb,Rd,y = k1,y*b,y*fup*d*tp / M2
F1,vb,Rd,y = 196.36 [kN] Resistance of an anchor bolt for bearing pressure onto the base plate [6.2.2.(7)]
Shear force Vj,Ed,z
d,z = 0.76 Coeff. taking account of the bolt position - in the direction of shear [Table 3.4]
b,z = 0.76 Coeff. for resistance calculation F1,vb,Rd [Table 3.4]
k1,z = 2.50 Coeff. taking account of the bolt position - perpendicularly to the direction of shear [Table 3.4]
F1,vb,Rd,z = k1,z*b,z*fup*d*tp / M2
F1,vb,Rd,z = 218.18 [kN] Resistance of an anchor bolt for bearing pressure onto the base plate [6.2.2.(7)]
SHEAR OF AN ANCHOR BOLT
b = 0.37 Coeff. for resistance calculation F2,vb,Rd [6.2.2.(7)]
Avb = 3.14 2
[cm ] Area of bolt section [6.2.2.(7)]
fub = 400.00 [MPa] Tensile strength of the anchor material [6.2.2.(7)]
M2 = 1.25 Partial safety factor [6.2.2.(7)]
F2,vb,Rd = b*fub*Avb/M2
F2,vb,Rd = 37.00 [kN] Shear resistance of a bolt - without lever arm [6.2.2.(7)]
M = 2.00 Factor related to the fastening of an anchor in the foundation CEB [9.3.2.2]
MRk,s = 0.28 [kN*m] Characteristic bending resistance of an anchor CEB [9.3.2.2]
lsm = 50 [mm] Lever arm length CEB [9.3.2.2]
Ms = 1.20 Partial safety factor CEB [3.2.3.2]
Fv,Rd,sm = M*MRk,s/(lsm*Ms)
Fv,Rd,sm = 9.42 [kN] Shear resistance of a bolt - with lever arm CEB [9.3.1]
CONCRETE PRY-OUT FAILURE
NRk,c = 11.23 [kN] Design uplift capacity CEB [9.2.4]
k3 = 2.00 Factor related to the anchor length CEB [9.3.3]
Mc = 2.16 Partial safety factor CEB [3.2.3.1]
Fv,Rd,cp = k3*NRk,c/Mc
Fv,Rd,cp = 10.40 [kN] Concrete resistance for pry-out failure CEB [9.3.1]
CONCRETE EDGE FAILURE
Shear force Vj,Ed,y
VRk,c,y0 42.3 [kN CEB
= 5 ] Characteristic resistance of an anchor [9.3.4.(a)]
A,V,y = 0.71 Factor related to anchor spacing and edge distance CEB [9.3.4]
CEB
h,V,y = 1.00 Factor related to the foundation thickness
[9.3.4.(c)]
CEB
s,V,y = 0.91 Factor related to the influence of edges parallel to the shear load direction
[9.3.4.(d)]
Factor taking account a group effect when different shear loads are acting on the individual anchors in a CEB
ec,V,y = 1.00
group [9.3.4.(e)]
,V,y = 1.00 Factor related to the angle at which the shear load is applied CEB [9.3.4.(f)]
CEB
ucr,V,y = 1.00 Factor related to the type of edge reinforcement used
[9.3.4.(g)]
Mc = 2.16 Partial safety factor CEB [3.2.3.1]
Fv,Rd,c,y = VRk,c,y0*A,V,y*h,V,y*s,V,y*ec,V,y*,V,y*ucr,V,y/Mc
Fv,Rd,c,y = 12.80 [kN] Concrete resistance for edge failure CEB [9.3.1]
Shear force Vj,Ed,z
23
RELACION TEKNIK
Digitally signed by
Stiffener check
Trapezoid plate parallel to the column web
M1 = 1.11 [kN*m] Bending moment acting on a stiffener
Q1 = 26.14 [kN] Shear force acting on a stiffener
zs = 27 [mm] Location of the neutral axis (from the plate base)
Is = 348.81 [cm4] Moment of inertia of a stiffener
d = 2.27 [MPa] Normal stress on the contact surface between stiffener and plate EN 1993-1-1:[6.2.1.(5)]
g = 29.57 [MPa] Normal stress in upper fibers EN 1993-1-1:[6.2.1.(5)]
= 26.14 [MPa] Tangent stress in a stiffener EN 1993-1-1:[6.2.1.(5)]
z = 45.33 [MPa] Equivalent stress on the contact surface between stiffener and plate EN 1993-1-1:[6.2.1.(5)]
max (g, / (0.58), z ) / (fyp/M0) ≤ 1.0 (6.1) 0.19 < 1.00 verified (0.19)
24
RELACION TEKNIK
Digitally signed by
Connection stiffness
Bending moment Mj,Ed,y
beff = 112 [mm] Effective width of the bearing pressure zone under the flange [6.2.5.(3)]
leff = 188 [mm] Effective length of the bearing pressure zone under the flange [6.2.5.(3)]
k13,y = Ec*(beff*leff)/(1.275*E)
k13,y = 16 [mm] Stiffness coeff. of compressed concrete [Table 6.11]
leff = 155 [mm] Effective length for a single bolt for mode 2 [6.2.6.5]
m= 39 [mm] Distance of a bolt from the stiffening edge [6.2.6.5]
k15,y = 0.425*leff*tp3/(m3)
k15,y = 9 [mm] Stiffness coeff. of the base plate subjected to tension [Table 6.11]
Lb = 230 [mm] Effective anchorage depth [Table 6.11]
k16,y = 1.6*Ab/Lb
k16,y = 2 [mm] Stiffness coeff. of an anchor subjected to tension [Table 6.11]
0,y = 0.34 Column slenderness [5.2.2.5.(2)]
Sj,ini,y = 11225.46 [kN*m] Initial rotational stiffness [Table 6.12]
Sj,rig,y = 7295.40 [kN*m] Stiffness of a rigid connection [5.2.2.5]
Sj,ini,y Sj,rig,y RIGID [5.2.2.5.(2)]
Bending moment Mj,Ed,z
k13,z = Ec*(Ac,z)/(1.275*E)
k13,z = 18 [mm] Stiffness coeff. of compressed concrete [Table 6.11]
leff = 125 [mm] Effective length for a single bolt for mode 2 [6.2.6.5]
m= 29 [mm] Distance of a bolt from the stiffening edge [6.2.6.5]
k15,z = 0.425*leff*tp3/(m3)
k15,z = 18 [mm] Stiffness coeff. of the base plate subjected to tension [Table 6.11]
Lb = 230 [mm] Effective anchorage depth [Table 6.11]
k16,z = 1.6*Ab/Lb
k16,z = 2 [mm] Stiffness coeff. of an anchor subjected to tension [Table 6.11]
0,z = 0.34 Column slenderness [5.2.2.5.(2)]
Sj,ini,z = 20616.12 [kN*m] Initial rotational stiffness [6.3.1.(4)]
Sj,rig,z = 7295.40 [kN*m] Stiffness of a rigid connection [5.2.2.5]
Sj,ini,z Sj,rig,z RIGID [5.2.2.5.(2)]
Weakest component:
FOUNDATION - CONCRETE CONE PULL-OUT FAILURE
Remarks
Thickness of welds joining the pier with the plate is too small. 1 [mm] < 3 [mm]
25
RELACION TEKNIK
Digitally signed by
26
RELACION TEKNIK
Digitally signed by
GEOMETRY
PRINCIPAL BEAM
Section: HEA 1000
Bar no.: 138
= -90.0 [Deg] Inclination angle
hg = 990 [mm] Height of the principal beam section
bfg = 300 [mm] Width of the flange of the principal beam section
twg = 17 [mm] Thickness of the web of the principal beam section
tfg = 31 [mm] Thickness of the flange of the principal beam section
rg = 30 [mm] Fillet radius of the web of the principal beam section
Ap = 346.85 [cm2] Cross-sectional area of a principal beam
Iyp = 553846.00 [cm4] Moment of inertia of the principal beam section
Material: S 275
fyg = 275.00 [MPa] Design resistance
fug = 430.00 [MPa] Tensile resistance
BEAM
Section: IPE 270
Bar no.: 16
= 0.0 [Deg] Inclination angle
hb = 270 [mm] Height of beam section
bb = 135 [mm] Width of beam section
twb = 7 [mm] Thickness of the web of beam section
tfb = 10 [mm] Thickness of the flange of beam section
rb = 15 [mm] Radius of beam section fillet
Ab = 45.94 [cm2] Cross-sectional area of a beam
Iyb = 5789.78 [cm4] Moment of inertia of the beam section
27
RELACION TEKNIK
Digitally signed by
PLATE
Type: bilateral
lp = 85 [mm] Plate length
hp = 130 [mm] Plate height
tp = 8 [mm] Plate thickness
Material: S 275
fyp = 275.00 [MPa] Design resistance
fup = 430.00 [MPa] Tensile resistance
BOLTS
WELDS
agp = 5 [mm] Fillet welds connecting plate with principal beam
MATERIAL FACTORS
M0 = 1.00 Partial safety factor [2.2]
M2 = 1.25 Partial safety factor [2.2]
LOADS
Case: 12: ULS /18/ 1*1.35 + 2*1.50 + 10*0.90
Nb,Ed = -19.74 [kN] Axial force
Vb,Ed = 8.07 [kN] Shear force
Mb,Ed = -1.13 [kN*m] Bending moment
RESULTS
BOLT CAPACITIES
Fv,Rd = 77.21 [kN] Shear bolt resistance in the unthreaded portion of a bolt Fv,Rd= 0.6*fub*Av*m/M2
Bolt bearing on the beam
Direction x
k1x = 2.50 Coefficient for calculation of Fb,Rd k1x = min[2.8*(e1/d0)-1.7, 1.4*(p1/d0)-1.7, 2.5]
k1x > 0.0 2.50 > 0.00 verified
bx = 0.65 Coefficient for calculation of Fb,Rd bx=min[e2/(3*d0), fub/fu, 1]
bx > 0.0 0.65 > 0.00 verified
Fb,Rd1x = 58.86 [kN] Bearing resistance of a single bolt Fb,Rd1x=k1x*bx*fu*d*ti/M2
28
RELACION TEKNIK
Digitally signed by
PLATE
Ant = 2.08 [cm2] Net area of the section in tension
Anv = 5.44 [cm2] Area of the section in shear
VeffRd = 122.15 [kN] Design capacity of a section weakened by openings VeffRd=0.5*fu*Ant/M2 + (1/3)*fy*Anv/M0
|0.5*Vb,Ed| ≤ VeffRd |4.04| < 122.15 verified (0.03)
BEAM
Ant = 1.72 [cm2] Net area of the section in tension
Anv = 6.14 [cm2] Area of the section in shear
VeffRd = 126.97 [kN] Design capacity of a section weakened by openings VeffRd=0.5*fu*Ant/M2 + (1/3)*fy*Anv/M0
|Vb,Ed| ≤ VeffRd |8.07| < 126.97 verified (0.06)
29
RELACION TEKNIK
Digitally signed by
WELD RESISTANCE
30
RELACION TEKNIK
Digitally signed by
1.1.1 Assumptions
1.1.2 Geometry:
1.1.3 Materials
1.1.4 Loads:
Foundation loads:
Case Nature Group N Fx Fy Mx My
(kN) (kN) (kN) (kN*m) (kN*m)
DSGN1 design(Foundation weight) ---- 91.51 -0.11 4.36 -3.93 0.11
LL1 live load(Category A) 7 61.01 -0.07 2.71 -2.52 0.07
LL2 live load(Category A) 7 0.51 0.17 1.12 0.20 0.38
WIND1 wind 7 0.59 3.50 1.12 -1.07 8.50
WIND2 wind 7 9.72 1.97 9.74 -20.06 4.78
WIND3 wind 7 7.25 -1.93 8.98 -18.87 -5.08
WIND4 wind 7 -0.25 -3.20 0.53 -0.96 -8.12
WIND5 wind 7 -23.06 -2.01 -5.33 14.25 -4.71
WIND6 wind 7 -40.11 -0.35 -20.18 39.86 0.08
WIND7 wind 7 -24.14 1.76 -5.18 14.59 4.60
31
RELACION TEKNIK
Digitally signed by
Stress calculations
32
RELACION TEKNIK
Digitally signed by
Load eccentricity:
|eB| = 0.03 (m) |eL| = 0.14 (m)
Equivalent foundation dimensions:
B' = B - 2|eB| = 2.24 (m)
L' = L - 2|eL| = 2.92 (m)
qu = 0.30 (MPa)
Uplift
Uplift in ULS
Design combination ULS A1 : 1.50WIND6
Load factors: 1.00 * Foundation weight
1.00 * Soil weight
Contact area: s = 0.16
slim = 0.17
Sliding
Average settlement
Settlement difference
Rotation
About OX axis
Design combination ULS A1 : 1.50WIND6
Load factors: 1.00 * Foundation weight
1.00 * Soil weight
Weight of foundation and soil over it: Gr = 261.93 (kN)
Design load:
Nr = 201.77 (kN) Mx = 105.19 (kN*m) My = -0.66 (kN*m)
Stability moment: Mstab = 419.09 (kN*m)
Rotation moment: Mrenv = 201.45 (kN*m)
Stability for rotation: 2.08 > 1
About OY axis
Design combination: ULS A1 : 1.50WIND6
Load factors: 1.00 * Foundation weight
1.00 * Soil weight
Weight of foundation and soil over it: Gr = 261.93 (kN)
Design load:
Nr = 201.77 (kN) Mx = 105.19 (kN*m) My = -0.66 (kN*m)
Stability moment: Mstab = 301.34 (kN*m)
Rotation moment: Mrenv = 69.97 (kN*m)
Stability for rotation: 4.307 > 1
1.3 RC design
1.3.1 Assumptions
• Exposure : X0
• Structure class : S1
Punching
Spread footing:
bottom:
ULS : 1.50LL1+1.50LL2+0.90WIND1
My = 22.90 (kN*m) Asx = 12.09 (cm2/m)
ULS : 1.05LL1+1.05LL2+1.50WIND2
Mx = 48.53 (kN*m) Asy = 12.09 (cm2/m)
top:
ULS : 1.50WIND6
My = -11.56 (kN*m) A'sx = 12.09 (cm2/m)
ULS : 1.50WIND6
Mx = -60.16 (kN*m) A'sy = 12.09 (cm2/m)
Column pier:
Longitudinal reinforcement A = 7.51 (cm2) A min. = 7.20 (cm2)
A = 2 * (Asx + Asy)
Asx = 0.64 (cm2) Asy = 3.11 (cm2)
Spread footing:
Bottom:
Along X axis:
20 A500HW 16 l = 2.18 (m) e = 1*-1.42 + 19*0.15
Along Y axis:
14 A500HW 16 l = 3.08 (m) e = 1*-1.03 + 13*0.16
Top:
Along X axis:
20 A500HW 16 l = 2.18 (m) e = 1*-1.42 + 19*0.15
Along Y axis:
14 A500HW 16 l = 3.08 (m) e = 1*-1.03 + 13*0.16
Pier
Longitudinal reinforcement
Along X axis:
3 A500HW 12 l = 3.68 (m) e = 1*-0.21 + 2*0.21
Along Y axis:
2 A500HW 12 l = 3.73 (m) e = 1*-0.21 + 1*0.41
Transversal reinforcement
8 A500HW 8 l = 1.99 (m) e = 1*0.21 + 5*0.20 + 2*0.09
2 Material survey:
35
RELACION TEKNIK
Digitally signed by
• Steel A500HW
• Total weight = 296.53 (kG)
• Density = 39.33 (kG/m3)
• Average diameter = 15.0 (mm)
• Survey according to diameters:
36
RELACION TEKNIK
Digitally signed by