Professional Documents
Culture Documents
Specifications - 2024 03 18 14 25 48
Specifications - 2024 03 18 14 25 48
Incoming cable entry should be from the bottom of the panel. Panel
should be designed for minimum 03 nos. bottom cable entry of 185 sq.
mm. DWA 11 KV (UE) cable. Therefore, the bottom entry box of the panel
should be extended accordingly.
Separate outdoor terminal box on the side of the panels having three
holes side exit suitable to connect 185 sq. mm (UE) XLPE/PVC cable. The
outdoor terminal box should be extended to a suitable size for proper
termination of 03 nos. cable.
13 Indoor type, IP-4x, enclosure compartment, PT chamber, Incoming & Lot 01
outgoing bus-bar compartment, thickness 1.6/2 mm MS Sheet steel,
color RAL-7032, Glossy finish.
ii. 3.3 KV Incoming Outgoing Panel (Cable In- Out Panel) – 1no.
Note: No glass fuse should be used for control of the panel, only MCB’s of
proper rating 2 Amps/4Amps/16 Amps should be used for control
winding.
8 2000 Amps - Suitable Copper Bus Bar with heat shrinkable PVC Sleeve Lot 01
Insulation
9 Earth Bus –50 x6x1Run GI Bus Bar Lot 01
10 MS Sheet steel enclosure suitable for Indoor installation with MS Base Lot 01
Channel, Internal Arc- 1 sec.
11 Power Pack 110VAC/24VDC, battery based, sourced from auxiliary Lot 01
supply, backup ability to serve tripping & closing coil (multiple trip-close).
Also give supply to 220 VAC spring charge motor during Mains failure.
12 Cable Entry and Exit: No. 01
Incoming cable entry should be from the bottom of the panel. Panel
should be designed for minimum 03 nos. bottom cable entry of 240 sq.
mm. DWA 11 KV (UE) cable. Therefore, the bottom entry box of the panel
should be extended accordingly.
Separate outdoor terminal box on the side of the panels having three
holes side exit suitable to connect 240 sq. mm (UE) XLPE/PVC cable. The
outdoor terminal box should be extended to a suitable size for proper
termination of 03 nos. cable.
13 Indoor type, IP-4x, enclosure compartment, PT chamber, Incoming & Lot 01
outgoing bus-bar compartment, thickness 1.6/2 mm MS Sheet steel,
color RAL-7032, Glossy finish.
3.3 kV, 1250 Amps Floor Mounted Horizontal Draw out/isolation VCB
fitted with Manual/Motor operated Spring charging mechanism with 110
V AC motor and motor control limit switch, Close / Shunt trip coil of
24VDC, Mechanical ON/OFF indicator, Mechanical operation counter,
Automatic safety shutters and Manual ON/OFF Push button. Short Circuit
Rating 40 kA/3 sec. (4 O/G)
Make: ABB/ L&T/Siemens /GEC/Jyoti/BHEL/CGL
2. Three Phase Segregated Fixed Type PT with HT PT fuses of ratio:11KV/√3- Lot 01
110V/√3, Core 1-Cl: 0.5, 100 VA (in I/c)
3. Single phase Current Transformer: 1600/1-1 A, Core1: Cl: 0.5, Burden: Lot. 01
15VA, Core2: Cl: 5P10, Burden: 15 VA (1 I/C)
Note: No glass fuse should be used for control of the panel, only MCB’s of
proper rating 2 Amps/4Amps/16 Amps should be used for control
winding.
8 2000 Amps - Suitable Copper Bus Bar with heat shrinkable PVC Sleeve Lot 01
Insulation
9 Earth Bus –75 Lot 01
x6x1Run GI Bus Bar
10 MS Sheet steel enclosure suitable for Indoor installation with MS Base Lot 01
Channel, Internal Arc 1 sec.
11 Power Pack 110VAC/24VDC, battery based, sourced from auxiliary Lot 01
supply, backup ability to serve tripping & closing coil (multiple trip-close).
Also give supply to 110VAC spring charge motor during Mains failure.
12 Cable Entry and Exit: No. 01
For incomer: Incoming cable entry should be from the bottom of the
panel. Panel should be designed for minimum 04 nos. bottom cable entry
of 240 sq. mm. DWA 11 KV (UE) cable. Therefore, the bottom entry box
of the panel should be extended accordingly.
For outgoing panels bottom exit of the panel of with minimum 02 holes
should be planned of cable size 240 sq. mm DWA.
13 Indoor type, IP-4x, enclosure compartment, PT chamber, Incoming & Lot 01
outgoing bus-bar compartment, thickness 1.6/2 mm MS Sheet steel,
color RAL-7032, Glossy finish.