Commissioning Manual: (SCM Display Unit)

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

COMMISSIONING MANUAL

SDU (SCM Display Unit)

SDU.943.001-E.b
Technical Service
If you need assistance, please call your local service centre:

Or
HASLER International SA Tel. +33 (0)4 74 16 11 50
F- 38780 PONT-EVÊQUE Fax +33 (0)4 74 16 11 55

HASLER Suisse Sarl Tel. +41 (0)32 720 23 00


CH-2000 NEUCHÂTEL Fax +41 (0)32 720 23 90

HASLER Deutschland GmbH Tel. +49 (0)54 81 80 50


D-49525 LENGERICH Fax +49 (0)54 81 80 51 10

HASLER Industrial Equipment (Shanghai) Co., Ltd Tel. +86 21 591 06 058
CN-201801 SHANGHAI Fax +86 21 591 05 300

Before you call …


Do you have alarm displays?
Are you able to eliminate the cause of the alarm displays?

Have you modified part of the system, feeder, product or operating mode?

Have you tried to remedy the fault in accordance with the operating and service instructions?

Please note:
- the facility number
- the type of feeder
- the motor control type

No part of this publication may be reproduced or transmitted in any form or by any means
electronic or mechanical including photocopy, facsimile or computer generated distribution
without written permission from Hasler International. All translation rights are reserved by Hasler
International. Hasler International has made every effort to ensure the accuracy and validity of this
document. However, errors or emissions cannot be excluded and may be transmitted to one of the
Hasler divisions.

Information in this manual is correct as of the date of publication. Hasler International assumes no
responsibility for damages resulting from misuse of the equipment or negligence on the part of
operating personnel.

Copyright
HASLER International SA
Z.I. de L’Abbaye
F - 38780 Pont-Evêque

Produced and published by


Technical Documentation Department
Hasler Suisse Sarl

Order no.: SDU.943.001-E.b


Date: 26.07.07

Hasler Suisse Sàrl, is part of Hasler International SA


COMMISSIONING MANUAL

TABLE OF CONTENTS
1 SAFETY RULES ............................................... 2
1.1 Conforming use ................................................. 2
1.2 Measures relating to organisation...................... 2
1.3 Operator's responsibilities ................................. 2
1.4 Working in complete safety ............................... 3
1.5 After sales and repair service ............................ 3

2 GENERAL INFORMATION ............................... 4


2.1 General description ........................................... 4

3 ASSEMBLY ....................................................... 5
3.1 Assembly in the control cabinet ......................... 5

4 TECHNICAL DATA ........................................... 6


4.1 General characteristics ...................................... 6

5 DEFINITION OF THE CONNECTORS .............. 7


5.1 Console rear connection .................................... 7
5.1.1 X2 connector ..................................................... 7
5.1.2 SW1 switch ........................................................ 7
5.1.3 X1 connector ..................................................... 7
5.1.4 M4 pin ................................................................ 7
5.1.5 Cable shielding .................................................. 7
5.2 LON com. termination SW1 ............................... 8
5.3 Digital and com input SW1 ................................ 8

6 MAIN FUNCTIONS OF THE KEYBOARD ........ 9


6.1 SDU for Dynamic weighfeeding ......................... 9
6.2 Description of the dynamic feeding keys ........... 9
6.3 SDU for Static weighfeeding .............................. 11
6.4 Description of the static feeding keys ................ 11

7 WHAT TO DO WHEN...? .................................. 13


7.1 Main faults ......................................................... 13

8 MAINTENANCE ................................................ 13
8.1 Cleaning ............................................................ 13
8.2 Transport ........................................................... 13

9 SPARE PART
KSU REPLACED BY SDU ................................ 14
9.1 Assembly ........................................................... 14
9.2 Cabling .............................................................. 14

SDU.943.001-E.b Page 1
COMMISSIONING MANUAL

1 SAFETY RULES

The installation, commissioning and programming of


the controller via the SDU console must be performed
by suitably trained personnel.

1.1 Conforming use

Only use the SDU console with feed equipment provided


or approved by HASLER.
Only use the SDU console respecting the technical
characteristics.

1.2 Measures relating to organisation

Take note of the safety rules which govern the use of


feeders connected to the controller and the SDU con-
sole.
As a complement to the user guide, observe the general
regulations that apply for preventing accidents and
protecting the environment.
Always keep the user guide close at hand where the
installation is used. Check that the user guide is
complete and legible.

1.3 Operator's responsibilities

Check that only qualified and suitably trained personnel


may use the SDU console.
Determine the personal responsibilities concerning the
operation and maintenance of the controller.
Check that the personnel who work with the SDU con-
sole have understood the instructions to use all the
components installed and especially all the safety rules
indicated in this chapter.
Immediately replace any damaged or missing
component.
The user of the SDU console guarantees that the safety
and accident prevention regulations that apply are
respected.

Page 2 SDU.943.001-E.b
COMMISSIONING MANUAL

1.4 Working in complete safety

Indicate immediately any modifications (even concerning


performance) that affect safety to management.
Systematically accord priority to safety aspects when
carrying out work.
Do not make any adjustments to the SCM controller
when the feeder is operating without measuring the inci-
dence on the behaviour of the machine being controlled.

1.5 After sales and repair service

The SDU console may only be repaired


• by a HASLER approved after sales service centre
or
• by qualified personnel, trained by HASLER.
Only use original spare parts, delivered by HASLER.

SDU.943.001-E.b Page 3
COMMISSIONING MANUAL

2 GENERAL INFORMATION

2.1 General description

The SDU console exists in two versions: one is used to


programme the dynamic weighfeeder controller with SCM2
or SCM controller; the other is used to programme the SCM2
static weighfeeder controller. Only the front panel is different.
This console is also used to command the controller by
remote according to the configuration applied to the SDU
console. The communication with the controller is LON bus
type.

The SDU console is placed on a cabinet. It may also be


delivered in a small portable case for the maintenance of the
controller(s).
Fig. 2.1 Dynamic SDU console overview
The different SDU variants

(1) SDU console for dynamic weighfeeding


(2) SDU console for static weighfeeding
(3) dynamic or static maintenance SDU console
(4) adaptor for maintenance SDU on SCM2 PANEL

2
4

3
Fig. 2.2 Overview of the components in the SDU

Page 4 SDU.943.001-E.b
COMMISSIONING MANUAL

3 ASSEMBLY

3.1 Assembly in the control cabinet

The kit contains the following equipment to assemble the


SDU console in a control cabinet:
• 1 SDU
• 2 attachment elements
• 2 screws, M4 * 16 mm
• 1 self-adhesive waterproof seal 1

1. Remove the attachment elements 2 and 3. 2


2. Paste the waterproof seal to the front of the cabinet 3
3. Insert the SDU (1) into the opening through the front.
4. Insert the attachment elements through the back into the
slots
on the SDU unit (3).
5. Insert the screws (2) and tighten them, to ensure the
assembly is correctly waterproof, but not too much.
Cabinet cutout dimensions

External dimensions

Total depth 72 mm
Internal depth 64 mm
144

Depending on the cabling used, extra depth


of around 20 mm extra for the connections to
X2 or 60 mm extra for the connections to X1
are required for the installation.
Dimensions H x D x W 144 x 72 x 144 mm
64
72

SDU.943.001-E.b Page 5
COMMISSIONING MANUAL

4 TECHNICAL DATA

4.1 General characteristics

Manufacturer: HASLER International SA


Designation: SDU
Dimensions: H x D x L 144 x 72 x 144 mm without connectors
H x D x L 144 x 90 x 144 with the connectors (X2 only)
H x D x L 144 x 130 x 144 with the connectors (DB9)
Net Weight: 1.100 Kg
Power supply:
Voltage: 12 - 24 VAC - DC / ±15%
Frequency: 47 to 63 Hz for VAC
Max consumption: 4W
Current on trigger: max. 2 A for 2 complete periods

Electrical standards:

EMC: According to European directive 2004 / 108 / CE


EN 61000 - 6 - 4: emissions for industrial environments
EN 61000 - 6 - 2: immunity for industrial environments

Safety: According to European directive 73 / 23 / CEE


EN 61010 - 1

Approvals:
Europe: CE

Environmental specifications:
Operating temperature: -20°C to 60°C
Storage temperature: -25°C to 70°C
Max. altitude: 3000 m
Max. humidity : 95% at 25°C without condensation (DIN 40040 Class
F)
Protection class: IP 65 on front only

Main characteristics of the SDU console


• Front part in polyester and fluorescent screen (VFD)
• LON BUS communication up to 1200 m with twisted pair cable
• 4 digital inputs

Page 6 SDU.943.001-E.b
COMMISSIONING MANUAL

5 DEFINITION OF THE CONNECTORS


5.1 Console rear connection
5.1.1 X2 connector
Note:
Pin Function The LON communication and console
1 LON A power supply must be connected either to
terminals 1,2 (LON) and 3,4 (supply) of
2 LON B X2 connector or to terminals 1 to 4 of
3 Negative pole supply - or if alternating ~ connector X1.

4 Positive pole supply + or if alternating ~


5 IN 1 digital input 1 / Security Key - Menu locking
6 GND
7 IN 2 digital input 2 / Kb Lockout - Keyboard locking
8 GND
9 IN 4 digital input 4 / Reserved
10 GND

5.1.2 SW1 switch


Switch Function
1 Security - Menu locking
2 Kb Lockout - Keyboard locking
3 Remote - Remote console
4 Lon Term. - LON network termination resistance

5.1.3 X1 connector
2: Kb Lockout

Pin Function
4: Lon Term.
1: Security

3: Remote
1: LON A
2: LON B

10:GND

1 Lon A
6: GND

8: GND
4: + / ~
5: IN 1

7: IN 2

9: IN 4
3: - / ~

2 Lon B
3 - pole power supply on DIP

X2 1 2 3 4 X1
4 + pole power supply SW1
5-9 Not used

5.1.4 Pin M4
Supply : 12-24V AC / DC / 4W
The earthing is performed IP65 (front)
by this pin, it enables
immunity from disruption.

5.1.5 Cable shielding


Goujon serti
Tightening pinM4-12
M4-12
The cable shielding on the X2
+ rondelles
+ washers andet nuts
écrous
connector must be in contact
and tightened through the plate
provided for the purpose.

SDU.943.001-E.b Page 7
COMMISSIONING MANUAL

5.2 LON com termination SW1

LON bus in Bus topology


The Bus topology requires a termination resistance (fig. 5.1)
at each end. The resistances must be placed at the ends of Console
the LON bus; we would advise you to use termination SDU
RT
resistances as described below:
Module Module Module
1. On the back of the SDU console, select switch 4 on switch A2 A2 A2
SW1 and push it to ON.
2. On the SCM2 which is the furthest from the SDU console,
position jumper JU1 on the CPU board to ON. SCM2 SCM2 SCM2
1 2 3
Caution: only two termination resistances must be launched RT
on a LON line.
Check your installation's cabling diagram to make sure you
do not make an error. Fig. 5.1 LON Network Bus topology

Note
The total length of the LON cables must not exceed 1200 m
for a bus type LON typology.

5.3 Digital and com input SW1

The functions available on the digital inputs and the SW1


switch are:
Digital input 1, IN1, SW1 switch 1: Menu locking function, if
used blocks the accessibility of certain menus and sub-
menus related to configuring the level of security. To modify
the Security level parameter you must return the switch to
OFF.

Digital input 2, IN2, SW1 switch 2: Keyboard locking function,


if used the console's keyboard is locked and no operations,
actions or modifications may be performed.

Digital input 3, IN3 (not accessible by X2), SW1 switch 3:


Remote console, if used the SDU remote console is declared
as the console which responds to the remote function.

Digital input 4, IN4: this input is currently reserved for a future


functionality.

SW1 switch 4: LON termination resistance, see chapter 5.2


for the use of this switch.

Page 8 SDU.943.001-E.b
COMMISSIONING MANUAL

6 MAIN FUNCTIONS OF THE KEYBOARD


6.1 SDU for dynamic weighfeeding
The explanations below deal with the SDU console's basic
functionalities; for more information on the parameters displayed on the
screen please refer to the maintenance manual .

Volumetric LED
Display screen
Totaliser key
Setpoint key
Programmable key
Alarm + LED key
Programmable key
Main page key
Start + LED key
Return key
STOP + LED key
Menu key
Enter key
Next key

Previous or erase key

6.2 Description of the dynamic feeding keys

The Screen enables the different menus, sub-menus and parameters related to
the type of feeder to be displayed.

The Setpoint key is used to read, and depending on the configuration, modify the
setpoint applied to the feeder.

The red alarm LED enables the detection of a new alarm if it is flashing, or if it is
on set an alarm which is still present.
The alarm key is used to display one or more alarms after the key is pressed
once, then after the alarms present are noted and the problems resolved, a sec-
ond press acknowledges the alarms.
Note: If the LED remains on after the acknowledgement, the alarm has not disappeared or other
alarms are still active. This LED will go off on its own even when the alarms acknowledged have
disappeared.

The main page key is used to quickly display the main parameters.

The previous key is used to go back one step in the display hierarchy.

SDU.943.001-E.b Page 9
COMMISSIONING MANUAL

The menu key is used to display the menus, sub-menus and parameters related
to the feeder.

The next key is used to move onto the next line in the menu list.

The return or erase key is used to go back in the menu list or parameters dis-
played or to erase a value in the case of programming a parameter.

The blue volumetric LED when lit indicates that the feeder is operating in volumet-
ric mode, if it is off the feeder is in gravimetric mode.

The totaliser key is used to reset the daily totaliser to zero. Once you press this

key you must then enter the value zero (0) then press the enter key to

reset the daily totaliser. Caution: once you have reset to zero you cannot go back.

The F1 and F2 keys are keys on which you can program actions or direct ac-
cesses through these two keys, for example, launching a tare of empty belt on the
F1 key and reading the belt load on the F2 key.
To assign a parameter or a function to one of these two keys you must find the
parameter or function by navigating around the different menus and sub-menus
then once you have found the element press the F1 or F2 key depending in the
key to be programmed for 5 seconds.

The start key is used to start the feeder. The green start LED provides information
on the start-up status. See the table below.
The stop key is used to stop the feeder. The red stop LED provides information
on the shutdown status. See the table below.

STAR T LED STOP LED

Feedi ng stopped and ready to start Flashi ng On

Feedi ng stopped but not ready to start Off On

Wai ti ng for the slavi ng si gnal to start On On

Feeder started On Off

Feeder emptyi ng On Flashi ng

Belt Tari ng Flashi ng Off

The entry or validate key is used to enter in the selected line in the menu hierar-
chy or to validate a new parameter modification.

Page 10 SDU.943.001-E.b
COMMISSIONING MANUAL

6.3 SDU for Static weighfeeding


The explanations below deal with the SDU console's basic
functionalities; for more information on the parameters displayed on the
screen please refer to the maintenance manual.

Stability reached LED


Display screen
Totaliser key
Formula key
Programmable key
Alarm + LED key
Pause key
Main page key
Cycle start key + LED
Return key
Emptying key + LED key
Menu key
Enter key
Next key

Previous or erase key

6.4 Description of the Static feeding keys

The Screen enables the different menus, sub-menus and parameters related to
the type of feeding and mechanics associated with the controller.

The Formula key is used to read, and depending on the configuration, modify the
selection of formula used for feeding.

The red alarm LED enables the detection of a new alarm if it is flashing, or if it is
on set an alarm which is still present.
The alarm key is used to display one or more alarms after the key is pressed
once, then after the alarms present are noted and the problems resolved, a sec-
ond press acknowledges the alarms.
Note: If the LED remains on after the acknowledgement, the alarm has not disappeared or other
alarms are still active. This LED will go off on its own even when the alarms acknowledged have
disappeared.

The main page key is used to quickly display the main parameters.

The previous key is used to go back one step in the display hierarchy.

SDU.943.001-E.b Page 11
COMMISSIONING MANUAL

The menu key is used to display the menus, sub-menus and parameters related
to the feeder.

The next key is used to move onto the next line in the menu list.

The return or erase key is used to go back in the menu list or parameters dis-
played or to erase a value in the case of programming a parameter.

The blue stability LED when lit indicates that the weight measurement on the
scales is stable.

The totaliser key is used to reset the daily totaliser to zero. Once you press this

key you must then enter the value zero (0) then press the enter key to

reset the daily totaliser. Caution: once you have reset to zero you cannot go back.

The F1 key is a key on which you can programme the launch of an actions or
read a direct access parameter through this key, for example, reading the weight
on the scales by pressing the F1 key.
To assign a parameter or function to this key you must find the parameter or func-
tion by navigating through the different menus and sub-menus then once you
have found the element press the F1 key for 5 seconds.

The cycle start key is used to start the feeding cycle. The green cycle start LED
provides information on the start-up status. See the table below.

The start emptying key starts the feeding cycle emptying phase. The green start
emptying LED provides information on the status of the cycle. See the table be-
low.

LED STAR T EMPTYIN G


C YC LE LE D

Feedi ng stopped and ready to start a new cycle Flashi ng Off

Fi lli ng cycle runni ng On Off

Awai ti ng emptyi ng On Flashi ng

Hopper emptyi ng On On

Feedi ng cycle paused Flashi ng Flashi ng

The entry or validate key is used to enter in the selected line in the menu hierar-
chy or to validate a new parameter modification.

Page 12 SDU.943.001-E.b
COMMISSIONING MANUAL

7 WHAT TO DO WHEN...?

7.1 Main faults

Fault Cause Resolution

The SDU console does not • No power supply • Check the power supply
switch on • Check the connections

The parameters are not • Power supply interrupted • Check the power supply
displayed • LON communication inter- • Check the LON commu-
rupted nication cable

Note:
The following connections are required for the SDU console to operate correctly:
- Power supply
- BUS LON to connect the controller, e.g. SCM2
- Correct configuration of the digital inputs (may block the operation of the keyboard
according
to the statuses!)
8 MAINTENANCE

8.1 Cleaning

Clean out the dust or dirt which has built up on the outside
surface of the unit with a soft cloth and standard cleaning
products.

Precautions
Never use a corrosive or solvent product.
If you use alchohol, avoid leaving any deposits of alcohol and
wipe the surface clean straight away.

8.2 Transport

In special anti-static transport packaging for electronic equip-


ment.

SDU.943.001-E.b Page 13
COMMISSIONING MANUAL

9 SPARE PART
KSU REPLACEMENT BY SDU

9.1 Assembly

Before you replace a KSU type console with an SDU type


console, to be able to assemble it you must first increase the
cutout opening in the door in which the SDU console will be
mounted.
The new cutout must therefore be 137 mm by 137 mm.

9.2 Cabling

The cables will be run from the KSU console to the SDU
console as follows:

1. The console must be earthed on the M4 pin.


2. The cable shielding must make contact and be tightened
on the cable holding plate connected to terminal X2.
3. The two wires connected to the KSU console terminal
JP5 terminals 1 and 2 must be connected on the SDU
console
to the terminal X2 terminals 1 and 2.
4. The two wires connected to the KSU console terminal
JP3 terminals 1 and 2 must be connected on the SDU
console
to the terminal X2 terminals 3 and 4.
5. On the SDU console make a bridge to terminal X2
terminals 5 and 6 or set Switch 1 on switch SW1 to ON.

6. If the KSU console has a bridge to the JP4 connector


terminals 3 and 4 on the SDU console you must set
switch 3 on dipswitch SW1 to ON.

Page 14 SDU.943.001-E.b

You might also like