2020 ‫ﯾﻧﺎﯾر‬ Page 1 of 1348

4. Application of Fire Protection Systems


4.2. Super Highrise Building Fire Protection Systems

4.2.1. Super Highrise buildings having a building height greater than 90 m, of any occu-
pancy classification shall be provided with Fire protection Systems in compliance
with Table 9.18. and Auxiliary Rooms Fire Protection Systems as per Table 9.30.

Table 9.18.: Super Highrise Building Fire Protection Systems


CATEGORY SYSTEM REQUIREMENTS COMBINED FIRE PUMP SET AND
FIRE WATER TANK CAPACITIES
A. SUPER i. Sprinklers shall be provided ix. Where a fire pump set is combined
HIGHRISE throughout the building including and serves both yard hydrants and
BUILDING WITH basements and podiums (open as internal building systems, the capaci-
PLOT AREA well as closed) as per Section 3.5. ty of the first fire pump set at the
ii. Auxiliary rooms and various areas lowest level of the building shall be
EXCEEDING
of the building shall be protected 1000 gpm (Irrespective of number of
20,000 M2 as per Table 9.30. stairs and standpipes) at 17 bar.
iii. The wet riser System shall be pro- x. Where a fire pump set is combined
vided throughout the building as and serves both yard hydrants and
per Section 3.4. internal building systems, the com-
iv. Wet risers shall be provided with bined water tank at the lowest level
High Zones and Low zones accord- of the building shall have a capacity
ing to pressure limitations as per of 60 minutes of operation, complete
Table 9.6.13. with low water level detection, dedi-
v. Wet risers shall be interconnected cated direct breeching inlet for refill
both at the lowest level and at the and instantaneous refilling arrange-
highest level of each zone. ment for the utility supply.
vi. A multi level Pump set arrange- xi. Where a fire pump set only serves
ment shall be provided every 90 m internal building systems, the capaci-
height from the lowest fire pump ty of the pump sets located vertically
set level as per Table 9.6.13. at every 90 m intermediate intervals
vii. Yard Fire Hydrants shall be provid- from the lowest level fire pump shall
ed where the plot area exceeds be 750 gpm if there are 2 standpipes
20,000 m2 , as per Section 3.11. and 1000 gpm, if there are more than
viii.Yard hydrants shall not be re- 2 standpipes, at pressure as required
quired where infrastructure yard to satisfy 6.9 bar at the most remote
hydrants are available within 60 m landing valve.
of such towers. Tapping from ex- xii. Fire water tank shall be provided for
isting yard hydrant network shall every upper level pump sets (At eve-
be permitted to extend the yard ry 90 m intervals). Such upper level
hydrants to comply with coverage water tanks shall be for 30 minutes
requirements. operation, complete with automatic
low water level detection, instanta-
neous refilling arrangement, pump-
ing and piping to refill tanks from
lower levels.

| CDGH-OP-25 | September 2018 Page 696 of 1348


4. Application of Fire Protection Systems
4.2. Super Highrise Building Fire Protection Systems

Table 9.18.: Super Highrise Building Fire Protection Systems

CATEGORY SYSTEM REQUIREMENTS COMBINED FIRE PUMP SET AND


FIRE WATER TANK CAPACITIES
B. SUPER HIGHRISE i. Sprinklers shall be provided vii. The capacity of the first fire pump set
BUILDING WITH throughout the building including at the lowest level of the building
PLOT AREA LESS basements and podiums (open as shall be 1000 gpm (Irrespective of
THAN 20,000 M 2 well as closed) as per Section 3.5. the number of standpipes) at 17 bar.
ii. Auxiliary rooms and various areas viii. The water tank at the lowest level of
of the building shall be protected the building shall have a capacity of
OR as per Table 9.30. 60 minutes of operation, complete
iii. The wet riser System shall be pro- with low water level detection, dedi-
C. WHERE SUPER vided throughout the building as cated direct breeching inlet for refill
HIGHRISE per Section 3.4. and instantaneous refilling arrange-
BUILDING IS iv. Wet risers shall be provided with ment for the utility supply..
PROVIDED WITH High Zones and Low zones accord- ix. The capacity of the upper level
YARD HYDRANT ing to pressure limitations as per pump sets located at every 90 m
SYSTEM, Table 9.6.13. intervals from the lowest level fire
v. Wet risers shall be interconnected pump, shall be 750 gpm if there
IRRESPECTIVE
both at the lowest level and at the are 2 standpipes and 1000 gpm if
OF PLOT AREA, highest level of each zone. there are more than 2 standpipes,
AS PART OF vi. A multi level Pump set arrange- at pressure as required to satisfy
INFRASTRUC- ment shall be provided every 90 m 6.9 bar at the most remote land-
TURE DEVELOP- height from the lowest fire pump ing valve.
MENT set level as per Table 9.6.13. x. Fire water tank shall be provided
for every upper level pump sets
(At every 90 m intervals). Such up-
per level water tanks shall be for
30 minutes operation, complete
with automatic low water level
detection, instantaneous refilling
arrangement, pumping and piping
to refill tanks from lower levels.

| CDGH-OP-25 | September 2018 Page 697 of 1348