Professional Documents
Culture Documents
1121 - Lakos Filter
1121 - Lakos Filter
1121 - Lakos Filter
EO Sterilization Facility
Description: Lakos Filter for cooling towers system, TCX-1100-ABV2, 40HP Pump, 460/3/60
Submittal Information
Items Detail
D D
1" 25 TYP NOTES:
SUBMITTAL DRAWING 4
5
INLET/OUTLET PRESSURE GAUGES: 0-100 psi, GLYCERIN-FILLED.
PURGE EQUIPMENT: ABV-15-120V.
This drawing is submitted for spatial 6 BASKET STRAINER.
consideration only. Do not pre-plumb
to these dimensions.
DWG NO.
4
2
1 6
122735
B
84-15/16" 2157
SH
1 REV.
3
B
16-7/8" 429
5
ANGLES SURVEYS
± 1/2" .XX ± .01
WWW.LAKOS.COM
± 1/4° APPROVALS DATE
.XXX ± .005
.XXXX ± .0005
DRAWN TITLE
2-5/8" 67 DO NOT SCALE DRAWING TCX-1100-ABV, TC SYSTEM,
FRONT VIEW W/O STRAINER
HSK 5/23/05
MATERIAL
SWEEPER HTX-0500, 460V 60HZ DELUXE
ENGR
PER LAKOS SPEC DLW 8/27/07
MFG
FINISH
- -
122735
SIZE MODEL NO. DWG NO. REV.
B
AS ASSEMBLED
WORK ORDER QTY. C
SCALE EST. WT. SHEET
1:12 2489 lb 1 OF 1
4 3 2 1
4 3 2 1
REVISIONS
ZONE REV. DESCRIPTION DATE APPROVED
POWER SUPPLY
GND
L1 L2 L3 G LUG
D D
EARTH
DISCONNECT GND
SWITCH
CLASS J FUSE
CLIPS
CPT 300VA
3A GND
460 V 120 V HAND-OFF-AUTO
OL 8-PIN RELAY DIAGRAM
M
C 3A 4A 3 4 A1 A2 95 96 C
4 3
M OL
MINIMUM WIRE SIZE
1 2
#3 AWG CU. 13 14 97 98
AUTO START
DRY CONTACT DRY CONTACT
REMOTE CONTROL
"RUN STATUS" "TRIPPED STATUS"
DEVICE
(IF USED) (IF USED)
(IF USED)
DWG NO.
L1 L2 L3 - INPUT +
M BLUE
RED
129499
OL
B 6 5 4 3
T1 T2 T3
SH
1 REV.
MOTOR
D
ABV/EFS VALVE
GND ACTUATOR
MANUAL 7 8 1 2
PURGE 3 OPEN
2 COM
1 CLOSE
3 4
A UNLESS OTHERWISE SPECIFIED: ENGINEERED FOR: A
DIMENSIONS ARE IN: INCHES [mm]
TOLERANCES ARE: 50-60HP ABV
FRACTIONS DECIMALS ANGLES ®
±1/4" .XX ± .01 ± 1/4° APPROVALS DATE
.XXX ± .005
.XXXX ± .0005
DRAWN TITLE
A. PURGE TIMER: REPEAT CYCLE ON START, OMRON 100-240VAC, SUPPLIED BY LAKOS #121226. DO NOT SCALE DRAWING ADJ - MOTOR CTRL BOX 85A, 3/60/460V/120V D90,
MATERIAL
B. DEFAULT SETTINGS: CHANGE AS NEEDED. -
ENGR
- - 100A DISC 24"x16", 50-60 HP, TC SYSTEM ABV
1. PURGE DURATION (ON): 20 SECONDS. FINISH REVIEW
- -
129499
SIZE MODEL NO. DWG NO. REV.
2. PURGE FREQUENCY (OFF): 8 HOURS. -
WORK ORDER QTY. C D
C. ACTUATOR VALVE: 120/240VAC, INSTALLED BY LAKOS. SCALE
NTS
EST. WT.
-
SHEET
1 OF 1