Professional Documents
Culture Documents
T-7 Maintenance Report
T-7 Maintenance Report
Primary Maintenance
Submitted By: Ehtisham Arshad
Usama Zafar
拉合尔换流站
Lahore Converter Station
2023 年 07 月 25
Contents
Type of Testing:...........................................................................................................................................3
Capacitance and Dissipation Factor Measurement.....................................................................................4
AI-6000L Tester......................................................................................................................................5
T-7 Transformer:..........................................................................................................................................7
H.V to L.V.................................................................................................................................................7
H.V to L.V and Earthing............................................................................................................................7
L.V to H.V and Earthing............................................................................................................................8
Connection and Testing of C.T:....................................................................................................................9
C & DF testing Procedure:.......................................................................................................................9
Potential Transformer and its Testing.......................................................................................................11
C & DF testing Procedure:......................................................................................................................12
Purity Test of SF6 gas:................................................................................................................................14
Procedure:.............................................................................................................................................14
Parameter Results & Ranges:................................................................................................................15
Surge Arrester Counter testing:.................................................................................................................16
Procedure:.............................................................................................................................................16
Maintenance of T-7 and its
related equipment
Introduction:
On the 21st and 22nd July, Maintenance of T-7 Transformer and its related equipment was done to
test whether the equipment technical parameters are within Range. Testing of different
equipment was done which includes
T-7 Transformer
Current Transformers
Potential Transformers
Surge Arrester
SF6 Breaker
Below is the 132kv yard area which includes the equipment that was under test
Type of Testing:
Capacitance and Dissipation Factor Measurement
Discharge counter measurement
Capacitance and Dissipation Factor Measurement
The capacitance and dissipation factor test of a transformer is a type of electrical test performed to
evaluate the insulation quality and condition of the transformer's windings and insulation system. It is
also commonly known as the power factor or dielectric loss test.
Capacitance Test:
The capacitance test measures the capacitance of the transformer winding insulation.
Transformers have inherent capacitance due to the presence of insulating materials between the
windings and the ground. This capacitance allows a small amount of current to flow between the
windings and the ground even under normal operating conditions.
In case of CT, main insulation consists of oil-impregnated paper layers wrapped around the
primary winding with semi conductive aluminum foils in between the layers to allow a smooth
electric field distribution. This forms a capacitance, from the primary winding to the outermost
screen, known as the main insulation capacitance or Cx. The leakage resistance of these
capacitive layers is denoted by Rx
Dissipation Factor:
The health of an electrical insulator can be determined by the ratio of the resistive component to
the capacitive component. For good insulator, this ratio would be quite low. This ratio is
commonly known as tanδ, tg δ or tan delta. Sometimes, it is also referred to as the dissipation
factor.
When the test conditions are basically the same, the difference of two measured
capacitance shall not exceed ±5%.
Secondly, the tan delta percentage value shall not exceed 1%
AI-6000L Tester
Fully automatic anti-interference dielectric loss tester AI-6000L is a high- precision instrument
for measuring dielectric loss tangent value and capacitance of various high-voltage power
equipment in power plants, substations and other fields. Because the frequency conversion
technology is adopted, it can ensure the accurate measurement under the strong electric field
interference. The instrument adopts Chinese menu operation, and the microcomputer
automatically completes the whole process of measurement.
HV connected to 10kv
Following are the connection scheme for this configuration. In this configuration High
voltage side delta connected 132Kv side is connected to 10Kv of tester and Low Voltage
11kv Terminals is connected to body ( Earthing) and Capacitance Terminal Cx of Tester
AI-6000L.
HV connected to 10Kv
Following are the connection scheme for this configuration. In this configuration Low
voltage side Y connected 11Kv is connected to 10Kv of tester and High Voltage
Terminal Delta is Connected to Capacitance Terminal Cx of Tester AI-6000L.
HV connected to Cx
Figure: three phase LV side connection Figure: three phase HV side connection
Conclusion:
From table we can clearly see that Dissipation factor is normal but Capacitance values are out of
range of 5% threshold.
Purity Test of SF6 gas:
To ensure the safety and reliability of the Circuit Breaker E3Q1, it is recommended to analyze
the SF6 gas inside the breaker.
In an SF6 Circuit breaker, Sulphur hexafluoride gas is used as the arc quenching medium. The
gas captures the conducting free electrons in the arc to form relatively immobile negative ions.
This loss of conducting electrons in the arc quickly builds up enough insulation strength to
extinguish the arc.
For this purpose, we use JH5000D-4 SF6 gas analyzer to measure the Purity, Dew point,
decomposed gas (SO2, H2S, HF and CO) and humidity of the SF6 gas in Circuit Breaker.
Procedure:
1. Close the intake valve and connect the exhaust pipe.
2. Connect the air duct with the filter end to the adapter, then connect the exhaust port of the
device under test & connect the other end to the air inlet of the instrument.
3. Turn on the power supply and check self-test Normal, enter the preheating interface, select
zero calibration & observe for about 2 minutes. When the difference between the current
position and the original position is < 10% save the current position & select preheating and
return to preheating interface
4. Adjust the intake valve to make the gas flow.
5. When there is no moisture to be detected Preheat ->main menu -> equipment selection ->
detection-> automatic determination of the detection end point;
6. When moisture is detected, it is recommended to ventilate and warm up for 10 min
7. Return to main menu -> device selection -> item selection -> detection -> automatic
determination of the detection end point.
8. Receive the result chit from machine.
Parameter Results & Ranges:
Test Date: 25/07/2023
SF6 Electrical Equipment Gas Comprehensive
Detector JH5000D-4
Parameters Values Range
SO2 0 < 5 uL/L
H2S 0 < 0.1 uL/L
CO 21.7 < 5 uL/L
HF 0 < 1 uL/L
Purity (V) 99.98 % ≥ 99.9%
Purity (W) 99.99 % ≥ 99.9%
Dew Point -41.94 °C -80 °C to +20°C
Humidity 61.15 uL/L @ +20 °C
Humidity 102.55 uL/L @30.0 °C
Conclusion: The Air Chamber is Normal and SF6 Gas Purity is Good.