Download as pdf or txt
Download as pdf or txt
You are on page 1of 25

ΕΓΧΕΙΡΙΔΙΟ

ΤΟΠΟΘΕΤΗΣΗΣ & ΡΥΘΜΙΣΗΣ


ΑΥΤΟΜΑΤΩΝ ΠΟΡΤΩΝ ΘΑΛΑΜΟΥ

ASSEMBLING &
REGULATION INSTRUCTIONS
FOR AYTOMATIC CABIN DOORS
CABIN DOORS
INDEX

PARTS DESCRIPTION 26
POSITION OF THE OPERATOR IN THE CABIN 26
ADJUSTMENT OF CLEAR OPENING
IN CENTRE PARTING DOORS 27
ADJUSTMENT OF CLEAR OPENING IN SIDE OPENING DOORS 27
INSTALLATION OF GUIDE SHOES AND HANGERS 28
ADJUSTMENT OF PANELS 28
ADJUSTMENT OF WHEELS 29
LANDING DOOR COUPLING 29
CORRECT ADJUSTMENT BETWEEN CLAMP AND RETAINER 30
LOCKING DEVICE 30
ELEMENTS SITUATION 31
VVVF-4+ MODULE
Programming 33
Inputs 34
Programming Examples 39
Technical Features 40
Start Up Protocol & Autoadjustment Of Vvvf (Inverter) 41
POSSIBLE PROBLEMS & SOLUTIONS 42
PREVENTIVE MAINTENANCE 43
26

PARTS DESCRIPTION

1 Fixation bracket
2 Operator
3 Plate
4 Panels
5 Tread
6 Tread support
7 Toe guard

POSITION OF THE OPERATOR ON THE CABIN

1. Place the brackets in the guide tracks situated in


the cabin roof (fig. 2)
2. Place the operator 220mm higher than the clear
height of the cabin (fig. 1).
3. Tighten the operator to the brackets (fig. 2).
4. Let 30mm between the front part of the cabin and
the outside of the operator regulated with the
brackets (fig. 3).
5. Fix the brackets in the guide tracks.
27

ADJUSTMENT OF CO. IN CENTRE PARTING DOORS

Slow plates:
1. Place the slow plates at the operator extremes.
2. Check that distance between them is X.(fig.1)
3. Tighten the air cord clamps (fig. 2).
Fast plates:
1. Place the fast plates in flush
position with the slow plates.
2. Tighten the air cord clamps
(fig. 2).

* X = CO + 45mm
(In case of fire protected panels) Adjust the opening of the door
*X = CO + 30mm by the slots of the top of the
(In case of non fire protected panels) hanger plates.

ADJUSTMENT OF CO. IN SIDE OPENING DOORS

1. Place the flush plates in open position.


2. Check that between the extreme plate
and the end of opening there is a
distance of X*, as shown fig. 1. Use the
slots of the top plate for adjusting the
door (see figure 1).
3. Once the fast plate is in the flush
position with the slow plate, fix the
syncronization cord (fig. 2).
28

INSTALATION OF GUIDE
SHOES AND HANGERS

Guide shoes (fig. 1)


and hangers (fig. 2)
installation in panel
procedure.

ADJUSTMENT OF PANELS

The following procedure is the Alignment of panels:


same for any type of cabin door The panels should slide
(Central or side opening). smoothly in the tread. If for
1. Once the panels are placed any reason the panels do not
into their corresponding slide smoothly, follow these
plates, slide them through instructions:
the side they open till they 1. Disassemble the inferior
are raised with the frames. guides.
2. Tighen the nuts that hold 2. Straigthen the panels to
the plates with the hangers remain parallel to the tread.
(fig. 1). 3. Assemble the guides.
3. Straigthen the panels with
the help of the hanger nuts
until the panel is parallel
to the post (fig. 1). Check
that between tread, between
panel and panel, and
between panel and post it
exist a distance of 5mm. (fig. 2)
29

ADJUSTMENT OF WHEELS

1. The adjustment will be made by the


inferior wheels (eccentric), rotating the
shaft we can adjust the force done to the
track.
2. This adjustment may be done with an
allen wrench of 5 mm and the flat key.
An excessive tightening could stop the
panel.

Wheels are adjusted in factory, only should be regulated


in case of bad functioning.

LANDING DOOR COUPLING

The cabin door includes the moving skate


that does the opening of the landing door.
When the cabin door is closed, the moving
skate remains closed, so that while the
cabin is moving it does not work with the
landing locks (fig.1).
Before the opening manoeuvre, the moving
skate opens and unlocks the landing lock
so that it can start the opening and closing
of the landing door.
In the closing cycle, the movements will be
other way round, moving the skate while
closing, and closing the skate to free the
landing lock, so that the landing door will
be ready to close and the cabin free to
move.
The correct position of the skate is centred
in relation with the rollers of the landing
lock.
30

CORRECT ADJUSTMENT BETWEEN CLAMP AND RETAINER

Once the skate is placed


(145mm between the end of
the plate and the shaft of the
skate), in locked position,
adjust the clamp-retainer
set by the slots (8 x 25) of the
support with a gap of 0,5 mm
in the horizontal and vertical
shaft. Doors 4 panels be-
tween CO 600 until
CO 915 the measure
is 80mm.

LOCKING DEVICE

Figure A1 and B1
correspond to a
lock set and figures
A2 and B2 show an
open position. In
these drawings we
can notice the
correct situation
of the locking me-
chanism parts.

1. Locked position, between landing cam and


movement bushing should be 10mm to allow the
cabin fit (fig. A1 and B1).
2. Check when cabin is in the floor the locking device
and cam work allowing a correctly opening of the
door (fig. A2 and B2).
31

ELEMENTS SITUATION

D - Distance between treads = 30mm


32

TECHNICAL MANUAL
& ELECTRONICAL MODULE
REGULATION VVVF-4+
33

PROGRAMMING

DESCRIPTION 250 volts AC or DC applied between ter-


OF SWITCHES minals 8 & 10 will open the doors. Without
any signal the door remains open. In the
contrary the door remains close.
The unit may be programmed using the OFF: 2 Inputs
DIL switches on the front of the unit. If The door control module will be controlled
any change is made to any of the above by two independent inputs. Any voltage
switch selections, the Mains Supply to the between 12 to 250 volts AC or DC applied
VVVF-4+ unit MUST be switched OFF and
between terminals 8 & 10 will cause the
ON again to read the new programming.
The switches functions are: doors to close. And between terminals 12
1 1 & 2 Inputs: & 10 will cause the doors to open. In the
ON: 1 Input absence of a signal, the doors will remain
The door control unit will be controlled by static. If both inputs are applied then the
a single input. Any voltage between 12 to open signal has priority.

2 Automatic / Semiautomatic:
ON: Automatic: Operators with skate (automatic landing). In this case a special move-
ment is made for locking and unlocking the skate
OFF: Semiautomatic: Operators without skate (Semiautomatic landing door).
3 Rotation sense (photocell):
ON: The control unit is expecting to control left hand or centre opening doors.
OFF: The control unit is expecting to control right hand opening doors.
(Special Note: The sense is defined from the outside of the car, refering to the direction taken
when the door is opening.)
4 Master and Slave:
ON: Master: The door control unit will execute instructions directly. Example: operation
of the Photoelectric Detector will cause the doors to re-open immediately under control
of the door control unit.
OFF: Slave: There is no automatic re-open movements. The photocell will only react
to instruction given by the main lift controller by the inputs. Example: operation of the
Safety Edge Detector will cause the door operator module to give a signal to the main
lift controller via the PHOTOCELL (36, 37, 38) output. The main lift controller then must
remove the close signal and put the open signal.
34

INPUTS

POWER INPUTS 220-250 V SINGLE PHASE AC (5, 6, 7):


The circuit has been designed to operate on a mains
supply of 230 Volts AC (+10%,-15%, 50 or 60 Hz). The
unit will consume approx 1 Amp from the supply.
In the case of using the new External Emergency Pas-
senger Release System the connection of the power
from the main supply (230V) is done directly on the
unit (3 NEUTRAL - 2 GROUNDING - 3 PHASE). From
there onwards through the interconnection between
of the 2 boxes (VVVF4 5 - 6 - 7 & Emergency Unit 5 - 6
- 7) the power is trasmitted to VVVF (page 35). It is important that the Door
Operator Module has a GOOD
CONTROL INPUTS (8, 9, 10, 11, 12): EARTH CONNECTION.
The circuit can work with external voltage inputs or
by means a volt free contact input.

12. Opening Signal: 9. 12 Volt:


Is an isolated signal with an impedance of Isolated 12 Volts output available to
20 kOmh and a sensibility from 12 to 250V. control the door via a volt free contact.
used for ordering the door. If we use the Features are:
control with only one input, it will be clos- a. This supply must only be used for this
ing signal and door will open. purpose.
11. 0 Volts: b. This contact must be isolated from any
Is the negative pole of 12V. When using an other power supply.
internal voltage it should bridged to com- 8. Close signal:
mon (10). It has the same characteristics as the
10. Common: open signal.
Is the reference used for the two inputs.

SERIAL PORT (13, 14, 15, 16):


The serial port is used to connect with external
devices like the diagnostic console, interfaces and
future expansion devices. Operating speed 1.200
Baud, current loop.
35

PHOTOCELL (17, 18, 19, 20):


One of the most relevant characteristics of this control is the optional incorporation
of a photocell. It is composed by a emitter and receptor infrared.

OTHER INPUTS (26, 21, 25, 23):

26. Landing signal: 25. Slow Closing:


This input is for connecting the external This input orders to the operator to close
emergency current supplier that allows the door slowly regardless of the barrier
the opening manouvre in the case of power and control signs. Is created for working
failure by a battery of 12V, able to give with detection of fire centres.
power during 15 seconds for a passengers 23. + 12 V. COM:
rescue. This terminal is used for giving with an
21. Reopening: isolated contact a reopening order or a
This signal is for installing the cabin door slow closing. Always use contacts free of
swich or an external barrier. This signal has tension and usually open.
priority to the closing signal. Use contacts
free on tension. For activating close one
contact with the main supply +12V. (23).
36

EMERGENCY SUPPLY INPUTS (66-67-28-29) AND INTERCONNECTION WITH VVVF


The KLEFER VVVF can be connected with an optional External Emergency Passenger
Release System powered by a 12V battery. In the case of Power Failure the battery
provides sufficient power to release trapped passengers. The Door opening manouevre
is controlled by a free voltage contact, applied between terminals 66 & 67.
Special attention should be paid to the following points:
The connection of the power from the main supply (230V) is done directly on the Unit. (
3-Neutral – 2 Ground – 1 Phase ). From there onwards through the interconnection of
the two boxes (VVVF4 5-6-7 & Emergency Unit 5-6-7), the power is transmitted to the
VVVF4. On the connections 66 & 67 of the Emergency Unit connect the magnetic Nor-
mally Open Switch (NO), which through the assistance of a magnetic belt closes
the circuit.
Special attention should be paid to the connection of the battery. On connector 28 of
the Emergency Unit connect the negative pole and on connector 29 the positive. In any
other case the 20A fuse will be burned. The Battery automatically recharges itself, once
its capacity drops below 70%, and may take up to 48 hours. The situation of the battery
is indicated through a led on the Emergency Unit showing the following three different
statuses.
1. When the led is ON it means that battery is charging. If this lasts for more than 48
hours the battery is defective and should be replaced (2Ah and above).
2. When the led is flashing everything is operating properly.
3. When the led is flashing every 15 seconds a cut in electricity has occurred.
37

OUTPUT RELAYS AND LED INDICATORS (from 30 to 41):


Output relays have been provided to give continuous information to the main lift control-
ler concerning the status of the doors. One 5 Amp/250 Volts volt free change over con-
tact is provided on each relay that may be used by the main lift controller to pilot such
information as “doors fully opened”, “doors fully closed”, “Photoelectric detection”,
“obstruction in the doorway” and “door control O.K.”.

• Opened: Led indicator and relay activated when


the doors are fully open.

• Closed: Led indicator and relay activated when


the doors are fully closed and locked.

• Photocell: Led indicator and relay activated when


the photocell or the reopening input is operated.

• Obstruction: Led indicator and relay activated when


an obstacle is detected that stops the doors from
closing. The signal will reset when the doors reach
the opened or closed position.

• Status: Blinking led indicating proper working


conditions.
38

TEST PUSHBUTTON (50): CLOSE SPEED (52):


Operation of the Test pushbutton will The door closing speed can be independ-
cause a door open or close cycle. ently adjusted from 150 mm/s upto 600
mm/s.
AUTOADJUSTMENT PUSHBUTTON (51):
The Autoadjustment pushbutton is used OPEN SPEED (53):
to set up the doors. The doors will do 3 The door opening speed can be independ-
complete movements at first the doors will ently adjusted from 200 mm/s upto 1.000
close completly, then the doors will open mm/s.
slowly counting the pulses from the en-
coder built into the drive motor until they SAFETY (54):
reach the open mechanical stop, and after This potentiometer is used to set the
a short delay the doors will close. From closing pressure onto an obstacle in the
the information gained the microprocessor doorway. The closing pressure can be set
will calculate the acceleration and decel- between 40 and 150 Nw.
eration ramps and the bracking torque
required to give the optimum control of the ENCODER (55):
doors. Once the autoadjustment has been An integral quadrature pulse encoder is
completed the parameter are stored in connected to this input. The purpose of
non- volatile EEPROM and will be used to the encoder, which is situated inside the
calculate the optimum performance. The motor, is to inform the control of the exact
doors will open slowly for the first opera- position and speed of doors.
tion after power has been removed from
the door control unit. Autoadjustment only MOTOR (56):
needs to be used when setting the initial Output to the 3 phase motor varying the
parameters or when changes such as con- voltage and frequency to control speed and
necting or removing the Fermator Safety torque.
Detector are made. For Advanced Start Up
Protocol & Autoadjustment of the VVVF ON/OFF SWITCH (57):
(INVERTER) see Appendix I Disconnects the unit from the 230 Volts AC
mains supply.

Caution: When the supply is switched


off, capacitors in the control system will
remain charged for a short time. Allow
60 seconds before handling the Control
Card or Motor.
39

PROGRAMMING EXAMPLES

MASTER: 1 INPUT
• Configuration
1. ON: 1 Input.
2. Depends on type of door.
3. Depends on type of door.
4. ON: Master photocell.

• Inputs
1. (8) Close 4. Obstacle
Closes the doors with voltage between Door will open if an obstacle is detected by
terminals 8 & 10. Open the doors when the motor ceasing to rotate.
the voltage between terminals 8 & 10 is 5. (25-23) Slow Closing
removed. Closes regardless of the state of the
2. (17...20) Photocell photocell.
Doors will reopen if the photocell beam is
broken. • Priorities
1. (21-23) Reopening.
3. (21-23) Reopening
2. Obstacle.
Doors will not close if this signal is active.
3. (25-23) Slow Closing.
4. (17...20) Photocell.
5. (8) Close.
SLAVE: 2 INPUTS
• Configuration
1. OFF: 2 Inputs.
2. Depends on type door.
3. Depends on type door.
4. OFF: slave photocell.

• Inputs 4. (21-23) Reopening


1. (8) Close Doors will not close if this signal is active.
Closes the doors with voltage between 5. Obstacle
terminals 8 & 10. Doors will not re-open if an obstacle is
2. (12) Open detected by the motor ceasing to rotate.
Open the doors with voltage between 6. (25-23) Slow Closing
terminals 12 & 10. Pryority to close. Closes regardless of the state of the
3. (17...20) Photocell photocell.
Does not re-open the doors when activated
• Priorities
but provides signal to main controller via
1. (12) Open.
the Photocell relay.
2. (21-23) Reopening.
3. (25-23) Slow Closing.
4. (8) Close.
40

TECHNICAL FEATURES

POWER SUPPLY
• AC voltage range......................................................................... 230v +10%, -15%. AC/DC
• Frequency supply.................................................................................................50...60 Hz
• Minimum supply...............................................................................................70 mA-13 W
• Open door power................................................................................................ 0,6 A-80 W
• Nominal power............................................................................................... 0,93 A-140 W
• Maximum power........................................................................................... 1,38 A -190 W

INVERTER
• Carrier frequency..................................................................................................... 16 KHz
• Frequency range...............................................................................................0,5...100 Hz
• Voltage range............................................................................................. 40...200 V AC III
• Maximum output current............................................................................................... 4 A
• Positional control................................................................................Quadrature encoder

MOTOR
• Asynchronous three phase......................................................................................6 poles
• Voltage supply.............................................................................................................250 V
• Power.........................................................................................................................250 W
• Thermic class.........................................................................................................B-130°C
• Nominal speed...................................................................................................... 900 RPM

INPUTS
• Impedance.............................................................................................................20 KOhm
• Voltage...................................................................................................... 12...230 V AC/DC

OUTPUTS
• Contacts................................................................................................................Switched
• R. contact................................................................................................................. 50 mW
• Swich time....................................................................................................................5 ms
• Output current........................................................................................................5 Α max
• Voltage.........................................................................................................................250 V

PRESTACIONES
• Open Speed.............................................................................................. 200...1000 mm/s
• Close speed................................................................................................ 150...600 mm/s
• Maximum acceleration........................................................................... 800...1500 mm/s2
• Safety force....................................................................................... 40...150 N adjustable
• Maintenance torque (Opened Door).................................................................. 80 Nm/cm
41

START UP PROTOCOL & AUTOADJUSTMENT OF THE VVVF (INVERTER)

1. Put the cabin between floors, in order to make adjustments separately from landing doors.
2. Put the door middle opened, after switching off the unit (switch 57).
3. Disconnect the signals coming from the main controller (8, 9, 10, 11, 12 & 21, 23, 25).
4. Programm in 2 INPUTS and MASTER (Microswitches 1 in OFF and 4 in ON) independ-
ently to how you will program the doors afterwards. Microswitches 2 and 3 according
to the kind of door. (Right-Left-Central sense and semiautomatic or automatic landing door).
5. Adjust the 3 potentiometers (52, 53, 54) in maximum, in order to overcome little
mechanical disorders.
6. Switch on the unit by means the main switch (57).
7. The door must remain stopped. If the door moves check the micro switch 1 in OFF position.
8. Press the AUTO ADJUSTMENT button (51) to make an auto adjustment cycle.
Α. The door should close.
• In case it opens you should check the micro switch 3 and if it is correct then any motor phases
is inverted and it will have to interchange 2 of them and make the auto adjustment again.
• If the door doesn’ t move, check the motor wires and the motor connector (56).
• If the door stops before closing completely, the information from the encoder is not
correct.
• Check the encoder (55) and try the auto adjustment again.
• If the door stops in the locking skate movement, check manually if the locking and de-locking
skate movement is made easily and completely. (See the Mounting cabin doors instructions).
• If the door doesn’t close completely disconnect the VVVF and check if there is any
mechanical obstruction.
B. Once the door is fully closed it will activate the CLOSE led and after a few seconds
will open slowly and the led will be deactivated.
The door should open slowly until the mechanical rubber stopper.
• If it only opens 26cm, the encoder information doesn’ t arrive to the VVVF. Check the
connections or change the encoder or the wire if they are damaged.
• If it doesn’ t open completely, check the mechanical because the motor torque is
enough to drag any kind of door (Check the wheels, the leaves, e.t.c.)
C. The door will close again without hitting.
• If the door doesn’t close, one encoder phase fails. Verify the wire and the encoder.
• If the door stops for some seconds before the close movement there is too much
mechanical friction detected by the system. The system will work, but the door
operator should be checked mechanically.
• If the door closes hitting, check the microswitch No.2 (type of landing door).
At this point by pressing TEST button the door will make a closing or opening move-
ment. It should open and close without hitting with the standard movements pre-pro-
grammed. So now it is the time to adjust the speeds (52 and 53).
D. Be sure that the 3 movements (CLOSE-OPEN-CLOSE) are well completed when run-
ning the autoadjustment function. Check all the functions: obstruction, photocell, the
inputs, open/close movements, etc.
E. If the VVVF control works correctly, we can switch off the circuit and program accord-
ing to your requirements and connect the input signals from the manoeuvre lift control.
42

POSSIBLE PROBLEMS & SOLUTIONS

The door doesn’t answer to the test is not correct, as the motor of the door
or auto-adjustment buttons. operator has always enough power to
• Switch OFF (57) and try again. open in normal circumstances.
The door only closes 35cm. The door reopens when the skate is closing.
• This is the clear entrance of any • Check the regulation of the skate,
controller that has never been adjusted. because probably the locking system
Therefore an auto adjustment is required. of the skate is not well adjusted and
The door opens but doesn’t close. the door has a mechanical friction, and
• Check if the photocell LED is activated. consequently the door reopens and the
• Check if the close signal arrives to the obstruction LED lights.
system using a multimeter or the console. The door hits when it opens.
• Check if the re-opening signal is activated. • Check that the skate un-locking is well
• Check that there is no stray voltage in fixed before the door starts to open. In
the open signal. case the skate is not fully fixed you should
The door re-opens by itself. check the skate adjustment because it is
• Check the sensibility of the re-opening probably too hard.
(# 54) Safety regulation potentiometer. The “ON” LED is activated and the door
• Check that the photocell is not activated. doesn’t obey to the signals.
• Check that there is no mechanical • There has been an obstruction at
obstruction on the door. opening and then the door enters into an
• In case of having the same problem, “out of order stage” during 15 seconds.
disconnect the photocell and try again • There is a continuous obstruction and
with the TEST button, and if the door the lift controller has not changed the
doesn’t open totally there must be a close signal by the open signal in slave mode.
mechanical obstruction on the door. • There has been a short circuit in the
The photocell is activated intermittently. output of the motor, and the system will
• Check the “grounding” connection (#6). be deactivated during 3 seconds.
• Check the correct plugs connection. The door hits when is fully opened,
• Remove the photocell wiring from any the “open” LED is not activated and
place where there are “electric noises” the system gets out of order.
such as motors, supplies wiring, etc. If • Check the tension of the toothed belt,
you can use a console, please check the because probably it is not correctly
stability of the signal. adjusted and it slips on the pulley of the
• Do not extend the wires especially the motor and consequently the encoder is
reception one (green colour). sending a wrong information.
• Take in mind that in master mode
The system gets power but doesn’t work
the system recognizes automatically
and the led ON is off.
the photocell detector after making
• Check if the external fuse is burned and
a complete open - close cycle with the
change it for another of the same type
beam free controlled by the input signals.
(250V, 4A ceramic fast speed).
The door doesn’t reach the fully open position.
• The mechanical adjustment of the door
43

The LEDS are working but the door controller, the encoder wires and
doesn’t move. program the switch 1 in ON position.
• The power module (and the internal fuse (Only mains supply and motor connected).
related) is blown and the controller must Switch on the circuit. If the door starts
be sent back to be repaired. Do not try to to open, then the turning sense is
change it by yourself as it could give an correct, but if the door starts to close,
electric shock and damage more components. interchange two motor phases.
The motor is moving intermittently. • Connect the encoder wire and the
• Check the wiring connections or if a system inputs.
phase of the motor is falling. How to check the encoder
The door opens less centimeters in each • If the door opens 26cm only, the encoder
movement and the opened led is acti- information doesn’t arrive to the VVVF.
vated, but the door is not really opened. Check the connections or the wires if
• If the motor box protection has been they are damaged or change the encoder.
de-mounted, be sure that the encoder • If during the start up, the door opens
wire is free inside the box. Maybe the completely (after closing), it remains
wire is pressed between the motor and a opened, although the CLOSED led is
plastic nerve and the encoder informa- activated, a phase of the encoder is
tion does not arrive properly to the VVVF. failing and we have to interchange the
two central wires. Even if after the above
How to check the correct direction
the door doesn’t work properly, change
of rotation of the motor.
the encoder.
• Disconnect the input signals from the

PREVENTIVE MAINTENANCE FOR CABIN DOORS VVVF


1. Check and replace the electric contact as necessary. (Approximately after 2 million cycles).
2. Periodically check that the closing cycle ends resting on the rubber stop.
3. Concentric and eccentric wheels require no maintenance. Replace them when they
have signs of wear, noisy operation... (Approx. after 10 million cycles).
4. To prolong the life of the hanger wheels keep the top tracks clean. Never apply grease
to the top tracks.
5. Once a year grease the shafts of the skate. Use only SAE-20 lubricants (Do not use
spray lubricants).
6. Replace the guide shoes when they appear to be worn.
7. Periodically check the tension of the belt. With the correct tension the life of the belt
is almost unlimited.
8. Once a year grease the shaft of return splined pulley (Do not use spray lubricants).
9. Periodically check and adjust the tension of the air cords. Replace them when they
have signs of breaks, wear... (approximately after 6 million cycles).
10. Synchronization wheels (air cord pulleys) need no maintenance. Replace them when
the have signs of wear, cracks or noisy operation... (approx. 8 million cycles).
Βιομηχανική Περιοχή Κιλκίς,
61100 Ελλάδα
Τηλ: 23410 75 730
Fax: 23410 75 733
Kilkis Industrial Area,
61100 Greece
Tel: +30 23410 75 730
Fax: +30 23410 75 733
www.klefer.gr, commercial@klefer.gr

You might also like