FAHU with Enthalpy Wheel, Cooling Coil & Horse Shoe Heat Pipe lab

E
n
t 6
h
a
l
p
y
1H 2 Heat Pipe 3 4 5
Cooling Heat Pipe -
-
coil Reheat
R Pre-Cool

Supply Air
Supply Air (CFM) - 185.00 87
(L/S) -
Return Air
Return Air (CFM) - 0.00 0
(L/S) -
s
1 2
REF
DBT, F WBT, F grs/lb RH, % DBT, F WBT, F grs/lb RH, %
FAHU 95 89.6 200.3 87 86.9 80.7 128.6 74.1
35 32 30.5 27.05
3 4
REF
DBT, F WBT, F grs/lb RH, % DBT, F WBT, F grs/lb RH, %
FAHU 95.0 87.8 200 87 78 66.7 80.6 60
35 32.3473682 28.73684 24.5737
5 6
REF
DBT, F WBT, F grs/lb RH, % DBT, F WBT, F grs/lb RH, %
FAHU 76 63 67.2 50 78 66.7 80.6 60
27.9999998 23.2105262 28.73684 24.5737

Cooling Coil Load (MBH)


REF
Sensible Latent Total TON 2 fan kw dx kw total
FAHU 3.40 15.02 18.42 1.53 0.19 2.61 2.79

Heat pipe efficiency considered is 70%