Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

Type LGPG111

Digital Integrated Generator Protection Relay


Type LGPG111
Digital Integrated Generator Protection Relay

Figure 1: Relay Type LGPG111

Features Introduction Contacts from external protection


and plant monitoring equipment can
• An optimum mix of generator The LGPG111 is a multi-function be connected to any of the eight
protection functions relay which integrates a number of optically-isolated inputs. This allows
common generator protection external information to be
• Applicable to a wide range of
functions and associated scheme incorporated into the relay’s user-
generators
logic into a single relay case. configurable scheme logic.
• User configurable scheme logic The optically-isolated inputs and
• An alternative setting group Models Available relay outputs may be labelled in the
LGPG111 software for local or remote
• Wide operative frequency range
Incorporating 14 separate monitoring.
• Display of measured values generator protection functions These functions can be recorded in
(see Figure 2). the alarm and event recording
• Fault, event and disturbance
facilities.
recording
• Integral testing to aid
Application The protection functions provided by
the LGPG111 relay are as shown in
commissioning The LGPG111 can be applied to a
Figure 2.
• Remote serial communications wide range of generators. Each of
its protection functions can be
• Power-on diagnostics and self- enabled or disabled to suit
Functions
monitoring individual requirements. Generator differential (87G)
• Eight optically isolated logic This approach avoids the need for
application-specific relay versions, The generator differential function is
inputs for monitoring external
and simplifies the tasks of relay for the protection of phase to phase
plant.
specification, evaluation and project or three-phase stator windings faults
planning. The integrated scheme which normally involve high fault
logic eliminates much panel currents, so that fast fault clearance
engineering work by reducing the is required. This function works on a
need for auxiliary relays and per phase basis and has a dual
associated external wiring. slope bias characteristic as shown

2
in Figure 3: the lower slope
provides sensitivity for internal
87G Generator differential
faults, whereas the higher slope
51N Stator earth fault 60
provides stability under through fault
59N Neutral displacement 27 81U
conditions, especially if the 59 81O
67N Sensitive directional earth fault
generator CTs saturate.
51V Voltage dependent overcurrent
32R Reverse power
Stator earth fault (51N) 87G
32L Low forward power
The stator earth fault function is 46 Negative phase sequence
current operated and can be 40 Field failure
32R
typically set to cover up to 95% of 27 Undervoltage
51V
32L
40 46

the stator windings. It is generally 59 Overvoltage


67N 51N
used on resistively earthed 81U Underfrequency
generators, but can also be used to 81O Overfrequency
59N
respond to current in the secondary 60 Voltage balance
circuit of an earthing transformer
loaded with a resistor. A time-
delayed low set element and an
instantaneous high set element are Figure 2: Protection functions provided by LGPG111
provided.
Differential
Neutral displacement (59N) current
The neutral displacement function is Trip
voltage operated and is used for
detecting stator winding earth faults
on generators which are earthed via
Percentage
a distribution transformer. Two timer bias K2
Percentage
output elements are provided. bias K1
Is1 No Trip
Sensitive directional earth
fault (67N)
When two or more generators are Is2
Maximum mean bias current
connected in parallel directly to a
busbar, the sensitive directional Figure 3: Generator differential bias characteristic
earth fault function is used to
discriminate between internal and
external earth faults. A dedicated Current Current
single-phase CT input is available pick-up pick-up
level level
for the operating current, which can I> I>
accept the residual current from
three line CTs or current from a
dedicated core-balance CT. KI> KI>
The polarising signal for the
directional decision is either the Vs Voltage Vs2 Vs1 Voltage
level level
voltage signal applied to the neutral
voltage VT input or the current Voltage controlled mode Voltage restrained mode
signal applied to the stator earth
fault current input.
Figure 4: Voltage dependent overcurrent functions
The stator earth fault, neutral
displacement and sensitive
directional earth fault functions all
has not been cleared by other It is mainly used for generators
have third harmonic rejection built
protection after a certain period of connected directly to the busbar.
in by means of a software filter.
time. The voltage dependent
When voltage restrained, the
Voltage dependent function can be either voltage
current pick-up level is
overcurrent (51V) controlled or voltage restrained.
proportionally lowered as the
The voltage dependent overcurrent When voltage controlled, the timing voltage falls below a set value,
function is used for system backup characteristic is changed from a producing a continuous variation of
protection and can trip the load to a fault characteristic when timing characteristics. This is
generator circuit breaker, if a fault the voltage drops below a set level. applicable to generators connected

3
to the busbar, each via a step-up
transformer. t
A voltage vector compensation
feature is also available to tMAX
determine the HV phase-phase
voltage signals where a Yd1 or a
Yd11 step-up transformer is used.
K
The timing characteristic can either
be definite time or IDMT.
The effects of the voltage level on
the current pick-up level for both
functions are shown in Figure 4.
tmin
Reverse power (32R) and low
forward power (32L) I2>> I2
Reverse power protection is used to
detect loss of the prime mover.
Low forward power protection can Figure 5: Negative phase sequence tripping characteristic

be applied to steam turbine


X
generators where sequential
shutdown is preferable, under less
urgent operations, to avoid over- R
–Xa
speeding. Both are balanced
conditions, therefore a single phase
measurement is sufficient. For this
function, the relay calculates VIcosθ
for the A-phase.
Xb
In order to provide the required
sensitivity, a special current input is
used for both of these functions.
A compensation angle setting is also
available to compensate for phase
error of the generator’s CT and VT
signals. A delayed drop-off timer is
included in the timing logic which
acts as an integrating timer. This
allows the relay to trip within the Figure 6: Field failure protection characteristic
pre-determined time delay, under
pulsating power conditions.

Negative phase sequence (46) The tripping characteristic is shown A separate thermal capacity
in Figure 5. constant setting Kreset is also
Negative phase sequence function
provided for use when the generator
is for the detection of sustained When high values of K are selected
is cooling, due to a reduction in I2.
unbalanced load conditions. and the negative phase sequence
This is to cater for rotor components
Under such circumstances double currents measured are near to the
with differing cooling time constants.
frequency eddy currents are induced threshold, the operating time may
in the rotor of a generator and can be too slow. In this case, a An independent alarm element with
cause rapid overheating. maximum time setting tMAX is a definite time output is available for
The function has a thermal replica available to provide a safe trip time. pre-trip warning purposes.
curve which simulates the effects of When I2 is high, the operating time
pre-fault heating due to low levels of Field failure (40)
may become too fast and cause loss
standing negative phase sequence of discrimination with other power Severe loss of excitation caused by
current I2. When the I2 value is well system protection under fault field failure can cause a high value
above threshold, the thermal replica conditions. To reduce this risk, the of reactive current to be drawn from
approximates to a t = K/I22 inverse characteristic is provided the power system which can
characteristic, where K is the with an adjustable minimum endanger the generator. The field
generator’s per-unit current thermal operating time setting tMIN. failure protection provided by this
capacity constant in seconds. relay is a single phase impedance
measuring element with an offset

4
mho characteristic, as shown in the relay timer to hold its value abnormal frequency. The operating
Figure 6. An integrating timing when the current drops off, provided frequency range is from 25Hz to
arrangement, identical to that for the that the drop-off period is less than 70Hz for the differential function
power functions, is also provided. the tRESET timer setting. and from 5Hz to 70Hz for the other
This allows the relay to trip within This adjustable reset facility also protection functions.
the pre-determined time delay even enables closer co-ordination with
though the impedance measurement electromechanical induction disc Configuration
may temporarily fall outside the mho relays.
characteristic, eg. under pole- Scheme logic
slipping conditions. Integrating timer facility
The protection scheme logic for a
Time integration is required for the generator set normally involves a
Undervoltage (27) and power function to allow for large number of protection functions
overvoltage (59) reciprocating load conditions where combined together to drive a few
An undervoltage element and a the measuring element may pick up common trip outputs. Some blocking
2-stage overvoltage element are briefly and periodically. The same and interlocking logic may also be
provided. They are primarily used feature is also provided for the field required. In order to accommodate
for backing up the speed control failure function for pole-slipping different generator applications, the
governor and the automatic voltage conditions. Time integration allows scheme logic is flexible and
regulator. When severe overvoltage the function to operate within its pre- reconfigureable.
occurs, the high set of the determined operating time.
The LGPG111 scheme logic is in the
overvoltage element can be set to
To implement timing integration, an form of logic arrays with an
provide fast operation.
additional delayed drop-off timer is architecture commonly found in
Both elements are three-phase
provided. Once the protection programmable logic array devices,
devices.
measurement element has picked having an internal AND-OR
Underfrequency (81U) and up, the relay will operate after the structure shown in Figure 7.
overfrequency (81O) set time delay, provided that the
time interval when the element The OR functions allow one or more
Two underfrequency elements and drops off is within the setting of the of the AND function outputs to
one overfrequency element are delayed drop-off timer tDO. control each output relay, whilst the
provided. The underfrequency AND functions provide blocking or
elements are used to detect Frequency tracking interlocking for two or more inputs,
overloading of the generator caused or just a through connection for one
The relay tracks the power system
by various system disturbances or input. There are 32 inputs to the
frequency and continuously adjusts
operating conditions. scheme logic: 19 from the
its internal sampling clock to exact
The overfrequency element is used protection functions, 8 optically-
multiples of the system frequency.
to back-up the speed control isolated inputs and a selection of
This provides correct measurements
governor if overspeeding occurs. inverted inputs to allow blocking
and operation of the protection
logic to be created. The scheme
Voltage balance (60) functions during start-up and run-
logic controls a total of 15 output
down of the generator set when the
The voltage balance function is relays and has 32 selectable AND
generator unit is operated at
provided to detect VT fuse failure. functions.
It compares the secondary voltages
of two sets of VTs (or from two
From protection elements
separately fused circuits of a single and status inputs
VT) and can be used to block Output matrix
possible incorrect tripping of those
AND
protection functions whose
AND
performance may be affected by the
apparent loss of voltage such as
when a VT fuse ruptures.

Timer held facility


Both the overcurrent function, the AND

low set element of the stator earth Input matrix


fault function and the neutral OR OR OR
displacement function are provided
with a timer held facility.
The purpose is to enable faster To output relays
clearance of recurrent intermittent
faults, for example, self-sealing
insulation faults. This facility allows Figure 7: Block diagram of the scheme logic

5
The input and output matrices allow Ancillary Functions 20ms. Thus the duration of a record
the desired connections to be varies with the data type. For raw
created. Each intersection of the Measurements data, the duration is 64 electrical
matrix represents a programmable The magnitudes of all 17 analogue cycles, but for magnitude and phase
interconnection. By designing the inputs to the relay are available for data, the duration is 7.68s.
appropriate interconnections and display. Other derived quantities are The latter set-up allows long
then entering the information into also available. This provides such duration events such as pole-
the relay, through the scheme logic information as the three-phase, slipping to be captured. In either
settings, the required tripping logic residual and earth currents, the case, each data entry is time
can be configured. phase to phase voltages, differential stamped. This is particularly useful
and bias currents, negative phase for the raw data recording, since
The presence of the optically-
sequence current, phase A active the sampling interval varies with the
isolated inputs to the scheme allows
and reactive power plus the phase power system frequency, due to the
external devices such as rotor earth
angle and power system frequency. frequency tracking.
fault relay, temperature sensing
devices and mechanical relays to be All measurements can be displayed The disturbance recorder can be
connected to the scheme, so that the in either primary or secondary triggered from selected relay outputs
tripping facilities, together with the quantities, selectable by the user. and status inputs. A maximum of
alarm and remote communication Primary display quantities are based two records can be stored in volatile
facilities, can be utilised. on the settings for the CT and VT memory. A record remains in the
ratios used by the relay. buffer area until it is uploaded to a
The optically-isolated inputs and
PC, after which the buffer is
relay outputs used in a scheme may Event and fault records
released. If the two buffers are full,
be allocated to any function
Up to 100 event records are no further recording can be made.
required by the application.
available, all of them stored in non-
The relay has a facility to label each Time synchronisation
volatile memory. The latest record
of these by providing an identifier.
will automatically overwrite the The clock for event record time
The identifiers are used during the
oldest one. Event records are tagging has a resolution of 1ms.
configuration of the scheme logic,
generated whenever there is a To provide time synchronisation with
by the input and output status
protection function operation, other equipment in the generator
displays and by the event, fault and
energisation of a status input, station, the clock can be
disturbance recording systems.
operation of an output relay or any synchronised by external clock
Alternative setting group hardware failure. pulses (0.5, 1, 5, 10, 15, 30 or 60
Fault records are also stored as minute period) from an optically-
The relay provides an alternative
events. Out of the 100 event isolated input.
setting group which consists of all
the protection and scheme logic records, up to 50 fault records can Print functions
settings. It can be used during start- be accommodated. Fault records
up or run-down of generators or are initiated when user selected Several print functions are provided
during changes in power system relay outputs operate. The record to allow the relay to provide hard-
configuration. This setting group can consists of the date and time of the copy documentation, via the front
be selected by either energising the fault, the state of the optically- panel parallel port. This consists of
appropriate optically-isolated inputs, isolated inputs, relay outputs and the system settings, protection
or via the relay settings menu. protection functions, together with settings, scheme logic settings, event
the measurement values during the records and fault records.
fault. The scheme logic print-out is
formatted so that it can be
Disturbance records compared directly with the scheme
The internal disturbance recorder logic diagram.
can store up to eight analogue Test features
channels, together with all the status
input and relay output information. A number of features are provided
The analogue channels are user to enable the relay to be thoroughly
selectable from the relay’s 17 tested during commissioning, routine
inputs. maintenance and fault finding
operations:
The data in the analogue channels
can be stored as either raw data or • The measurement functions allow
as magnitude and phase data. the analogue input and its
The raw data is sampled at 12 associated wiring to be checked.
samples per electrical cycle, • Display the on/off states of the
whereas the magnitude and phase status inputs and relay outputs.
data are calculated once every

6
• Testing the four indicating LEDs. Hardware Description All of the optically-isolated inputs
operate from an auxiliary supply
• Testing the relay outputs and their The relay is housed in a 4U Vx(2), which is independent of the
associated circuits by operating (178mm) high case suitable for main auxiliary supply Vx(1).
the relay output contacts. either rack or panel mounting. The ratings of Vx(1) and Vx(2) may
• Display the operation of each Internally, it consists of a number of be different (see Technical Data).
protection function as a plug-in modules which are
individually tested and calibrated. Two relay output modules are
percentage of the time-to-trip.
The modular hardware architecture provided; each module contains 8
This allows the pick-up, progress
is shown in Figure 8. miniature relays. All relays are self-
and operation of each protection
reset. However, a software function
function to be checked. The microcomputer module consists is available which allows the user to
• Testing the set-up of the scheme of a powerful 16-bit microcomputer select outputs to be latched when
logic settings by manually which controls all of the subsidiary operated.
entering an input pattern to the modules through a 64-way ribbon
cable called the I/O Bus. The front panel consists of a 2 x 16
scheme, and then examining its
The processor performs all of the character alphanumeric liquid
logical output. This test can be
major software functions such as crystal display (LCD) and a 7 push-
performed at any time without
input signal processing, protection button keypad. It provides local
interfering with the relay’s
algorithms, scheme logic, relay access to all of the relay’s features.
operation.
output controls and handling of the There are also 4 light emitting
Power-on diagnostics and self operator interface. diodes for visual indication of the
monitoring relay’s status, a non-isolated
The analogue input module consists IEC 60870 serial port for
Power-on diagnostic tests are of 12 CTs, 5 VTs and 6 optically- connection to a PC, and a parallel
carried out by the relay when it is isolated inputs. The CTs and VTs are port for connection to a printer.
energised. These tests include used to isolate and condition the
checks on the timer, microprocessor, analogue inputs from the main At the rear of the relay, apart from
memory and the analogue input transformers connected to the the normal dc supply and plant
module. Continuous self-monitoring, generator. Their output signals are connections, there is an isolated
in the form of watchdog circuitry, then converted into digital data for IEC 60870 port and a K-Bus port
memory checks and analogue input further processing. for permanent connection to a
module tests, is also performed. In remote PC.
the event of a failure, the relay will In addition to the 6 optically-isolated
inputs on the analogue module, a The remote communications module
either lock-out or attempt a recovery, is responsible for handling the
depending on the type of failure further 8 are provided by the status
input module, making a total of 14 communications protocol and for
detected. controlling the three communication
optically-isolated inputs available to
the relay. Six of these have pre- ports.
defined functions, such as clock
synchronisation, setting group
selection, etc., which leaves 8 inputs
to be fed into the scheme logic.

Microcomputer

Power I/O bus


supply

Relay Remote Status Analogue Front


outputs comms input inputs panel

Figure 8: Hardware architecture

7
User Interface Software is available with each KITZ
to provide access to the relays, to
Front panel user interface read and change settings.
The features of the relay can be Additional software entitled
accessed through a user-friendly Protection Access Software and
menu system. The menu is arranged Toolkit is available to give access to
so that related items (menu cells) are the event recorder, together with
grouped into individual sections, other additional functions.
each of which is identified by a title. Each relay is directly addressable
The user navigates around the menu via the bus to allow communication
by using the arrow keys, first to with the PC. It should be noted that
select a particular section title and protection tripping and blocking
then to select an item within it. signals are not routed via the K-Bus.
The front panel liquid crystal display Separate conventional wiring is
is limited to displaying one menu used for these functions.
cell at a time.

Remote access user interface


The menu can be accessed via the
remote communications facility.
This allows all of the menu cells in a
section to be displayed on the
screen of a PC. Changes to the
menu cell can be made from the PC
keyboard.

Relay interconnection
Three communication ports are
available: the front panel, non-
isolated IEC 60870 port; the rear,
isolated IEC 60870 port; and the
K-Bus port. The IEC 60870 ports use
RS232 signal levels and allow point-
to-point connection. It is applicable
when networking is not required or
during commissioning.
Alternatively, the relays can be
connected via a shielded, twisted
pair called K-Bus. Up to 32 relays
may be connected in parallel to the
bus.
K-Bus can be connected through a
protocol converter, type KITZ, either
directly or via a modem, to the
RS232 port of a PC. K-Bus is RS485
based and runs at 64kbits/s.
The K-Bus connection is shown in
SK1
Figure 9.

Figure 9: K-Bus terminals connection arrangement

8
B1
27 and 81U
inhibit Note: CT and VT assignments
B2 F5
B3 F1 Relay 8 Ia—diff, 87G Generator differential
51V timer
inhibit F3
Ia—bias,
B4 Ib—diff,
B5 F6
B25
51N timer
Relay 9
Ib—bias,
A7 inhibit F2
B6
Ic—diff,
I —residual B26 Vab F4
B7 Ic—bias,
A8 B27 Setting group F7
A23 A B C select Relay 10 Ia, Ib, Ic 51V Overcurrent
Ia—diff B28 Vbc B8 F8
46 Negative phase sequence
A B9 F9
A24 B21 Setting group 40 Field failure (Ia)
A25 select
B22 Vab — comp F11 81U Under frequency (Ia)
Ib—diff B10 Relay 11
B11 F10 810 Over frequency (Ia)
A26 B23 Clock LGPG111
C B
A27 Phase rotation synchronising (Part) F12 Ia—sensitive 32R Reverse power
B24 Vbc— comp
Ic—diff B12 Integrated
G5 D1 F13 32L Low forward power
A28 Logic input 6 Generator
A17 G1 Protection Relay F15 Ie 51N Stator earth fault
Relay inoperative Relay 12
Ia—bias G3 alarm D2 F14 67N SDEF (polarising)
Logic input 7 D5
A18 G6 F16
A19 Ve 59N Neutral displacement
G2 Relay 1 D6 F17 67N SDEF (polarising)
Ib—bias LGPG111
(Part) G4 D9 F19
A20 Logic input 8 I—residual 67N SDEF (operating)
A21 Integrated Relay 13
G7 F18
Ic—bias Generator Relay 2 D10 Vab, Vbc 27 Undervoltage
Protection Relay G8 D13 F20
A22 Logic input 9 59 Overvoltage
A9 G9 F21 81U Underfrequency
D14
Ia—sensitive G11 D15 F23 810 Overfrequency
9

A10 Relay 3 Logic input 10 Relay 14


G10 F22 32R Reverse power (Vab)
A11
G12 D16 F24 32L Low forward power (Vab)
Ia D19
A12 G13 Logic input 11 F25 40 Field failure (Vab)
A13 60 Voltage balance
G15 D20 F27
Ib Relay 4 D23 Relay 15
G14 Logic input 12 F26 Vab—comp 60 Voltage balance
A14
A15 G16 F28 Vbc—comp (Comparison voltages)
D24
Ic G17 D27 H3
Logic input 13
A16
A5 G19 H4 Power
Relay 5 D28 supply Notes:
Ie G18 H5
H13 failure
A6 DC supply + 1. (a) CT shorting links make
G20 H6 alarm
B19 Vx(1) – before terminals disconnect.
Ve G21 H14 (b) Short terminals break before (a).
Case
B20 G23 earth 2. CT connections are typical only.
Relay 6
G22 2 TX 3. SCN = Screen connection for K-Bus.
G24 Rear 3 RX 1 4. The IEC 60870 port at the front panel is non-isolated
IEC 60870 and has different connection arrangements.
G25 port 7 signal ground K-Bus
(isolated) port 5. Frequency tracking on Vab, Vbc and Ia only.
G27
Relay 7 1 protective ground 2 6. Logic inputs are rated at Vx(2).
G26
SCN 7. SDEF = Sensitive directional earth fault.
G28

Figure 10: External connection diagram Type LGPG111 (typical scheme)


Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
Relay 6
Relay 7
Ouput Matrix

EN

Relay 8
Relay 9
Relay 10
Relay 11
Relay 12
Relay 13
Relay 14
Relay 15
EN
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&

Output Inhibited

Input 13
Input 12
Input 11
Input 10
–Input 9
Input 9
–Input 8
Input 8
–Input 7
Input 7
–Input 6
Input 6
60 VB Comp
–60 VB–Prot (Blocking)

Input Matrix
60 VB–Prot
40 Field Failure
67N Sensitive Dir EF
59N–2 Neutral Disp

8ms pick-up, 8ms drop-off


2ms pick-up, 2ms drop-off

2ms pick-up, 8ms drop-off


59N–1 Neutral Disp
51N>> Stator EF
51N> Stator EF
46>> NPS Trip
46> NPS Alarm

Figure 11: Type LGPG111 scheme logic


59 Over Voltage

Note: Speed of the relay outputs are:


27 Undervoltage
81U–2 Underfreq

12, 13, 14, 15


81U–1 Underfreq

Relays 1, 2, 8, 9, 10

Relays 4, 5, 6, 7,
81O Overfreq
32L Low Forward Power

Relays 3, 11
32R Reverse Power
51V Over Current
87G Generator Diff

10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
0
1
2
3
4
5
6
7
8
9
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
10
Technical Data

Ratings
Inputs
AC current In 1A or 5A
AC voltage Vn 100V to 120V
Nominal dc Operative range
(V) (V)
Auxiliary voltage Vx(1) 24/27 19.2 – 32.4
(Relay power supply) 30/34 24 – 40.8
48/54 38.4 – 64.8
110/125 88 – 150
220/250 176 – 300
Auxiliary voltage Vx(2) 24/27 19.2 – 32.4
(Optically isolated status input supply) 30/34 24 – 40.8
48/54 38.4 – 64.8
110/125 88 – 150
220/250 176 – 300
Note: Vx(2) may be different from
Vx(1)
Frequency Fn 50/60Hz

Burdens
AC current
Generator differential <0.05VA per input at In
(for 1A relay)
<0.20VA per input at In
(for 5A relay)
Voltage dependent overcurrent,
field failure and negative
phase sequence <0.05VA per input at In
(for 1A relay)
<0.22VA per input at In
(for 5A relay)
Reverse and low forward power <0.15VA at In (for 1A relay)
<0.30VA at In (for 5A relay)
Stator earth fault and
sensitive directional earth fault <0.12VA per input at In
(for 1A relay)
<0.25VA per input at In
(for 5A relay)
AC voltage <0.005VA per input at Vn
DC auxiliary voltage (Vx(1)) 15W quiescent, max.
34W operating.
DC auxiliary voltage (Vx(2)) Less than 0.32W on average
per input

Transformer ratios
CT ratios 1:1 to 9999:1 in 0.01 steps
VT ratios 1:1 to 9999:1 in 0.01 steps

11
CT requirements
Generator differential
Biased differential Vk ≥ 50In (Rct + 2RL + Rr) where maximum
settings at Is1=0.05In, through fault current
k1=0%, Is2=1.2In, = 10 x In and
k2=150% maximum X/R = 120
Vk ≥ 30In (Rct + 2RL + Rr) where maximum
through fault current
= 10 x In and
maximum X/R = 60
Note: Minimum knee point voltage = 34V

Earth fault protection functions


Sensitive directional Vk ≥ 6In (Rct + 2RL + Rr) where maximum
earth fault, using three X/R = 5 and
residually connected maximum earth fault
line CTs current = 1 x In
Sensitive directional Vk ≥ 6NIn (Rct + 2RL + Rr) where maximum
earth fault, using core X/R = 5 and
balance CT maximum earth fault
current = 2 x In
Stator earth fault Vk ≥ 6NIn (Rct + 2RL + Rr)

Ancillary protection functions


Voltage dependent Vk ≥ 20In (Rct + 2RL + Rr)
overcurrent, field failure
and negative phase
sequence
where Vk = Minimum current transformer knee-point voltage for stability
In = Relay rated current (1A or 5A)
Rct = Resistance of current transformer secondary winding (Ω)
RL = Resistance of a single lead from relay to current transformer (Ω)
Rr = Resistance of any other protection functions sharing the current
transformer (Ω)
Maximum earth fault current
N =
Core balanced CT or earth CT rated primary current
Note: N should not be greater than 2. The core balance CT or earth CT
ratio must be selected accordingly.

Power function
For settings >3% Pn Use correctly loaded class 5P protection CT
For settings ≤3% Pn Use metering class CT. See table below.

12
Metering CT class recommended for
power setting less than 3%Pn

Reverse/low forward Power Setting Metering CT Class


(%Pn)
0.2
0.1
0.4
0.6
0.8
0.2
1.0
1.2
1.4
1.6
1.8
2.0 0.5
2.2
2.4
2.6
2.8
1.0
3.0

Thermal withstand
Continuous withstand CT input 4 x In
VT input 400V
Short time withstand CT input 100A for 1s (In = 1A)
400A for 1s (In = 5A)

Setting ranges
Generator differential
Basic differential current setting Is1 0.05In to 0.1In in 0.01In steps
Threshold for increase bias Is2 1In to 5In in 0.1In steps
Bias K1 (Ibias < Is2) 0% to 20% in 5% steps
Bias K2 (Ibias > Is2) 10% to 150% in 10% steps

Stator earth fault


Low set element:
Characteristic Standard inverse/Definite time
Current setting Ie> 0.005In to 0.5In in 0.005In steps
Time multiplier setting TMS 0.05 to 1.2 in 0.05 steps
0.14
IDMT Operating characteristic t= x TMS
(I/Ie>)0.02–1
Definite time setting t> 0.1s to 10s in 0.1s steps
Reset timer setting tRESET 0s to 60s in 1s steps
High set element:
Current setting Ie>> 0.005In to 2In in 0.005In steps
Time setting t>> 0s to 5s in 0.1s steps

13
Neutral displacement
Voltage setting Ve> 1V to 25V in 1V steps
Timer 1 setting t1 0.5s to 5s in 0.5s steps
Timer 2 setting t2 1s to 10s in 1s steps
Timer 2’s reset timer t2RESET 0s to 60s in 1s steps

Sensitive directional earth fault


Operating current Ires> 0.005In to 0.02In in 0.005In steps
Polarising voltage Vp> 1V to 10V in 1V steps
Polarising current Ip> 0.005In to 0.02In in 0.005In steps
Relay characteristic angle RCA –95° to 95° in 1° steps

Voltage dependent overcurrent


Functions Voltage controlled/Voltage
restrained/Simple
Characteristic Standard Inverse/Definite Time
Current setting I> 0.5In to 2.4In in 0.05In steps
Time multiplier TMS 0.05 to 1.2 in 0.05 steps

IDMT Operating characteristic t= 0.14 x TMS


(I/I>)0.02–1
Definite time setting t 0s to 10s in 0.1s steps
Reset timer setting tRESET 0s to 60s in 1s steps
Voltage settings:
Vs (for voltage controlled) 20V to 120V in 1V steps
Vs1 (for voltage restrained) 80V to 120V in 1V steps
Vs2 (for voltage restrainted) 20V to 80V in 1V steps
K factor 0.25 to 1.00 in 0.05 steps
Voltage vector rotate None or Yd

Current pick-up level

Voltage Controlled Voltage Restrained

I> for V> Vs I> for V > Vs1

KI > for V≤ Vs KI> +


I> – KI> (V – V for Vs1≥ V ≥ Vs2
S2)
VS1 – VS2
KI> for V < Vs2

Reverse power
Power setting –P> 0.2W to 8W in 0.05W steps
(for 1A relay)
1W to 40W in 0.25W steps
(for 5A relay)
Delayed pick-up timer t 0.5s to 10s in 0.5s steps
Delayed drop-off timer tDO 0s to 5s in 0.1s steps

14
Low forward power
Power setting P< 0.2W to 8W in 0.05W steps
(for 1A relay)
1W to 40W in 0.25W steps
(for 5A relay)
Delayed pick-up timer t 0.5s to 10s in 0.5s steps
Delayed drop-off timer tDO 0s to 5s in 0.1s steps
Compensation angle θcomp –5° to +5° in 0.1° steps
(for both reverse and
low forward power)
Note: The power settings are single phase quantities.

Negative phase sequence trip element


Trip threshold setting I2>> 0.05In to 0.5In in 0.01In steps
Thermal capacity constant (heating) K 2s to 40s in 1s steps
Thermal capacity constant (cooling)
Kreset 2s to 60s in 1s steps

Operating characteristic
t=–
K
log 1–
I2>> 2
e
(under no pre-heating condition) I2>>2 I2
Maximum operating time tmax 500s to 2000s in 10s steps
Minimum operating time tmin 0.25s to 40s in 0.25s steps

Negative phase sequence alarm element


Alarm threshold I2> 0.03In to 0.5In in 0.01In steps
Alarm timer setting t> 2s to 60s in 1s steps

Field failure
Mho offset –Xa 2.5Ω to 25Ω in 0.5Ω steps
(for 1A relays)
0.5Ω to 5Ω in 0.1Ω steps
(for 5A relays)
Mho diameter Xb 25Ω to 250Ω in 1Ω steps
(for 1A relays)
5Ω to 50Ω in 0.2Ω steps
(for 5A relays)
Delayed pick-up timer t 0s to 25s in 0.1s steps
Delayed drop-off timer tDO 0s to 5s in 0.1s steps

Undervoltage
Voltage setting V< 30V to 110V in 1V steps
Timer setting t 0.1s to 10s in 0.1s steps

Overvoltage
Voltage settings V> ,V>> 105V to 185V in 1V steps
Timer settings t>, t>> 0s to 10s in 0.1s steps

15
Underfrequency
Frequency settings F1< ,F2< 40Hz to 65Hz in 0.05Hz steps
Timer settings t1, t2 0.1s to 25s in 0.1s steps

Overfrequency
Frequency settings F> 40Hz to 65Hz in 0.05Hz steps
Timer settings t 0.1s to 25s in 0.1s steps

Voltage balance
Voltage setting Vs 5V to 20V in 1V steps

Digital inputs
Optically isolated inputs 14 (6 dedicated, 8 available to the
scheme logic)

Contacts
Output relays 10 dual make
2 single make
3 change-over
Power supply failure alarm 1 single make
1 single break
Relay inoperative alarm 1 change-over
Contact rating Make: 30A and carry for 0.2s
Carry: 5A continuous
Break: dc 50W resistive
25W inductive
(L/R = 0.4s)
ac 1250VA
Subject to maxima of 5A and 300V
Durability
Loaded contact 10,000 operations
Unloaded contact 100,000 operations

16
Communications
Language Courier

IEC 60870 port (front/rear)

Transmission mode Asynchronous


Signal levels RS232
Message format IEC 60870 FT1.2
Data rate 600 – 19200 bits/s
Connection Single-ended
Cable type Screened multi-core
Cable length 15m
Connector 25-way D-type female
Isolation Front (non-isolated)
Rear (1kV rms for 1 minute to case
earth and other circuits)

K-Bus port

Transmission mode Synchronous


Signal levels RS485
Message format HDLC
Data rate 64 kbits/s
Connection Multidrop (32 units)
Cable type Screened twisted pair
Cable length 1000m
Connector Screw terminals
Isolation 2kV rms for 1 minute

Voltage withstand
Dielectric withstand
IEC 60255-5: 1977 2.0kVrms for 1 minute between all
terminals and case earth
2.0kVrms for 1 minute between
terminals of independent circuits,
including contact circuits
1.0kVrms for 1 minute across
open contacts of output relays
1.0kVrms for 1 minute between
IEC 60870 rear port and earth
High voltage impulse
IEC 60255-5: 1977 Three positive and three negative
impulses of 5kV peak, 1.2/50µs,
0.5J between all terminals of the
same circuit (except output
contacts), between independent
circuits and between all terminals
connected together and case earth
Insulation resistance
IEC 60255-5: 1977 >100MΩ

17
Electrical environment
DC supply interruptions
IEC 60255-11: 1979 The relay will withstand a 10ms
interrupt in the auxiliary supply,
under normal operating conditions,
without de-energising
AC ripple on dc supply
IEC 60255-11: 1979 The unit will withstand 12% ac
ripple on the dc supply
High frequency disturbance
IEC 60255-22-1: 1988 Class III 2.5kV peak between
independent circuits and between
independent circuits and case earth
1.0kV peak across terminals of
the same circuit (except metallic
contacts)
Electrostatic discharge
IEC 60255-22-2: 1996 Class 2 4.0kV discharge in air with cover
in place.
4.0kV contact discharge with cover
removed.
Fast transient disturbance
IEC 60255-22-4: 1992 Class III 2.0kV, 5kHz applied directly to
auxiliary supply
2.0kV, 5kHz applied directly to
all inputs
Class IV 4.0kV, 2.5kHz applied directly to
auxiliary supply
4.0kV, 2.5kHz applied directly to
all inputs
Radio frequency interference
Radiated immunity
IEC 60255-22-3: 1989 Class III field strength 10V/m
Extended frequency range 20MHz
to 1000MHz
Conducted immunity
IEC 60801-6: 1994 10V rms, 0.15MHz to 80MHz
Radiated emissions
EN55022: 1994 Class A
Conducted emissions
EN55022: 1994 Class A
EMC compliance
89/336/EEC Compliance with the European
EN50081-2: 1994 Commission Directive on EMC is
EN50082-2: 1995 claimed via the Technical
Construction File route.
Generic Standards were used to
establish conformity

18
Product safety
73/23/EEC Compliance with the European
Commission Low Voltage Directive.
EN 61010-1: 1993/A2: 1995 Compliance is demonstrated by
EN 60950: 1992/A11: 1997 reference to generic safety
standards.

Atmospheric environment
Temperature
IEC 60255-6: 1988 Storage and transit
-–25°C to +70°C
Operating
–25°C to +55°C
Humidity
IEC 60068-2-3: 1969 56 days at 93% relative humidity
at 40°C.
Enclosure protection
IEC 60529: 1989 IP50 (dust protected)

Mechanical environment
Vibration
IEC 60255-21-1: 1988 Vibration response Class 2
Vibration endurance Class 2
Shock and bump
IEC 60255-21-2: 1988 Shock response Class 2
Shock withstand Class 2
Bump Class 1
Seismic
IEC 60255-21-3: 1993 Class 2

19
Case
The relay is housed in a multi-
module Midos case as shown in
Figure 12.

483mm Rack details


Dimensions to IEC 297
7 max.
438
Rack mounting
31.75
±0.4

12.7
±0.4

Hinged front 450 min.


panel U Scale
Removable 432 U = 44.45 465.1 ±1.6
cover Push button
projection 10mm max. Tolerance between
any two holes
10 within a distance
178 of 1mm ±0.4
101.6
10
7
465 252 Allow a minimum of 10.6
483 37 50mm for terminal block
and wiring
Side Fixing hole detail
Front

All dimensions in mm
Terminal screws:
M4 x 8 brass Cheese Head with
Lockwashers are provided

438 Mounting screws are not provided


Panel mounting
Panel cut-out detail

400
200

Hinged front
panel 180.5 191
Removable 432 Push button
cover projection
10mm max.
10
440
Fixing holes
Ø5.4
201 178
10
252
443 37 Allow a minimum of 50mm for
Side terminal block and wiring
Front

Figure 12: Case outlines

Additional Information
LGPG111 Service Manual R5942
Courier Communications leaflet R4113

20
Information Required
with Order

Unit type: LGPG111 01

Case mounting
Flush panel P
Rack R

Vx(1) auxiliary voltage


24 – 27V dc 1
30 – 34V dc 2
48 – 54V dc 3
110 – 125V dc 4
220 – 250V dc 5

Vx(2) auxiliary voltage


24 – 27V dc 1
30 – 34V dc 2
48 – 54V dc 3
110 – 125V dc 4
220 – 250V dc 5

VT and CT rating
100/120V – 1A L
100/120V – 5A M

Language
English E
French F
German G
Spanish S

21
22
23
ALSTOM T&D Protection & Control Ltd St Leonards Works, Stafford, ST17 4LX England
Tel: 44 (0) 1785 223251 Fax: 44 (0) 1785 212232 Email: pcs.enquiries@tde.alstom.com Internet: www.alstom.com
©1999 ALSTOM T&D Protection & Control Ltd

Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should
only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
ALSTOM T&D Protection & Control Ltd cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.

Publication R4106H 039910 CPS Printed in England.

You might also like