Product datasheet

Specifications

SM6-24 IM500 LBS SM6 Man 630A,


use CIT manual cubicle
F-SM6R-IM-A1

notification_critical_stroke Discontinued

Main
Range Of Product SM6

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Technology Type Air insulated switchgear

Device Short Name IM 500

Product Or Component Type Switch

Internal Arc Classification AFL downward exhaust gas

Internal Arc Protection 12.5 kA 1 s

Rated Frequency (Fr) 50 Hz

Rated Voltage (Ur) 24 kV

Rated Lightning Impulse 125 kV peak


Withstand Voltage (Up)
Rated Continuous Current (Ir) 630 A

Rated Short-Time Withstand 16 kA rms 1 s


Current (Ik)
Standards IEC 62271-200

Complementary
Bus Rated Current 630 A

Counting Device Type Operating counter (optional)

Mass 130 kg

Height 1700 mm

Width 500 mm

Depth 950 mm

Environment
Ambient Air Temperature For -5…40 °C
Operation
Ambient Air Temperature For -40…70 °C
Storage
Ip Degree Of Protection IP22

Vibration Resistance 0.5 gn horizontal class 2


0.4 gn vertical class 2

Operating Altitude <= 1000 m