Professional Documents
Culture Documents
Sp-Me-Me-022-Steam Generators
Sp-Me-Me-022-Steam Generators
Sp-Me-Me-022-Steam Generators
STEAM GENERATORS
1. GENERAL .......................................................................................................................... 3
1.1. Scope........................................................................................................................ 3
1.2. Terminology.............................................................................................................. 3
1.3. References................................................................................................................. 4
1.4. Conflicting Requirements ........................................................................................... 4
2.1. Casing...................................................................................................................... 5
2.2. Radiant Section ......................................................................................................... 5
2.3. Transition Section...................................................................................................... 7
2.4. Convection Section.................................................................................................... 8
2.5. Refractory............................................................................................................... 10
2.6. Radiant Section Refractory Requirement................................................................... 12
2.7. Transition Section Refractory Requirements.............................................................. 13
2.8. Convection Section Refractory Requirements............................................................. 13
2.9. Refractory Gasketing ............................................................................................... 13
2.10. Fuel Burning Equipment.......................................................................................... 14
2.11. Piping System.......................................................................................................... 20
2.12. Instrument Air Supply System................................................................................... 25
2.13. Electrical System..................................................................................................... 25
2.14. Control System........................................................................................................ 30
2.15. Programmable Logic Controller System (PLC).......................................................... 33
2.16. Automatic Combustion Control (A.C.C).................................................................... 33
2.17. Safety System........................................................................................................... 35
2.18. Control Panel.......................................................................................................... 37
2.19. Operator Panel ....................................................................................................... 38
2.20. Skid Structure.......................................................................................................... 39
2.21. Control Cab............................................................................................................ 41
3. FABRICATION................................................................................................................. 41
4.1. General................................................................................................................... 43
4.2. Additional Requirement : ......................................................................................... 43
PT. CALTEX PACIFIC INDONESIA Steam Generators
SP-ME-ME-022 Rev. 1
8. VENDOR’S GUARANTEE............................................................................................... 51
1. GENERAL
1.1. Scope
1.1.1. This specification defines minimum requirements for the design, materials,
fabrication, testing and inspection for Steam Generator. The type of Steam
Generator shall be Fire Tube Boiler with once through and force flow water
circuit design.
1.1.2. The equipment specified herein is subject to the execution by the bidder and the
principle/designer of CONTRACTOR's Guarantee Agreement.
1.1.3. This specification supplements the data sheets which contain the operating
conditions.
1.1.4. Compliance by Vendor with this specification does not relieve Vendor’s
responsibility of furnishing the package and accessories at the minimum
requirement of proper design, mechanically suited to meet operating guarantees
at specified condition on the applicable data sheet.
1.1.5. This specification is intended to be a general performance type specification.
Therefore, if the bidder feels an exception to the materials, components, or
mechanical details specified herein will be to the COMPANY's advantage, the
exception may be quoted as an alternate. Where Vendor takes exception to the
specifications, he may offer additional bids for alternative designs, clearly
showing:
?? How the alternative differs from the original specification.
?? Life cycle cost benefit to COMPANY resulting from the proposed change.
?? Why proposals are equal or superior to the provisions of this specification.
?? Operating experience of existing installations in similar service from which
COMPANY may evaluate reliability of the proposed change.
1.2. Terminology
In this specification, the following words and terms shall have the meanings indicated when
used herein:
1.2.1. COMPANY
Refers to PT. CALTEX PACIFIC INDONESIA, as the ultimate user and owner,
the authorized representative of COMPANY or COMPANY third party
inspection.
1.2.2. CONTRACTOR
Refers to company selected by COMPANY, which may be responsible for the
detailed engineering design, material and equipment procurement, and
construction as specified in Contract, Scope of Work, or Work Order.
1.2.3. Vendor
Refers to company selected by COMPANY or CONTRACTOR, which is
responsible for the purchase agreement or purchase order of goods or services
specified in this specification.
Note:
?? For EPC (Engineering, Procurement and Construction) project purposes:
The terminology shall have the meaning as above.
?? For “ Direct Procurement “ by COMPANY purposes:
Vendor shall also be responsible as CONTRACTOR.
1.3. References
The references listed below form part of this specification. Each publication shall be the
latest revision and addendum in effect on the date this specification is issued for
construction unless noted otherwise. Except as modified by the requirements specified
herein or the details of the drawings, work included in this specification shall conform to
the applicable provisions of these publications :
1.3.1. Related Specification
?? SP-ME-ME-025 Coating and Painting Specification”
?? PP-PC-GG-003 Shipping instruction Procedure
?? PP-PC-GG-004 Packing and Marking Instruction
?? PP-QC-GG-003 Inspection and Test Plan at Shop”
?? PP-QC-GG-004 Inspection and Test Plan at Field”
?? SP-IN-II-006 Programmable Logic Controller (PLC)” Specification
1.3.2. Standards and Codes
?? ASME Boiler and Pressure Vessel Code, Section I
?? ASME Boiler and Pressure Vessel Code, Section VIII
?? ASME Power Test Code
?? ANSI B31.1 Power Piping
?? ANSI B31.3 Chemical Plant and Petroleum Refinery Piping
?? AISC Manual of Steel Construction
?? Standard for Prevention of Furnace Explosions in Fuel Oil - and Natural Gas-
Fired Single Burner Boiler-Furnaces (ANSI/NFPA 85A)
?? National Electrical Code (ANSI/NFPA 70)
?? Steel Structure Painting Council Code
?? Caltex Safety in Designs Field Manual
?? American Welding Society (AWS) D1.1 (Structural Steel Fabrication)
1.4.1. In case of conflict between this Specification and its associated Specifications
and the above Codes and Standards, the Vendor shall bring the matter to the
COMPANY’s attention for resolution and approval in writing. However, the
most stringent requirement shall govern.
1.4.2. Should conflicts exist between this specification and other documents, the
following order of precedence shall a govern:
?? Purchase Order.
?? Data sheets.
?? This Specification
?? Other COMPANY Specifications
?? Other Referenced Publications
?? Approved for Construction Drawings
?? Vendor’s Code
2. BASIC DESIGN
2.1. Casing
2.1.1. Casing of the boiler shall be so designed as to attain gas tightness against positive
internal pressure.
2.1.2. Maximum deflection of the external casing surface shall be smaller than 1 : 360
(deflection/span) within total deflection of 25 mm in a single span, based on the
maximum operating furnace pressure.
2.1.3. Furnace bottom shall be provided with drain to permit removal of flue gas
deposits by water washing.
2.1.4. Thickness of skin casing shall be 3.2 mm or more, if used.
portion may have sloped or vertical sides. The shell sides surrounding the finned
tubes shall have sloped sides with vertical tube sheets.
2.4.2. Minimum Convection Temperature
The convection section shall be designed to provide enough flue gas exhaust
temperature to prevent the sulfuric condensation at the convection tube. The
content of H2 S on the fuel gas and fuel oil can be found in section of Design Data
and Site Conditions within this specification.
2.4.3. Tubesheet
All tube return bends shall be external to convection section tubesheets and
covered by an internally insulated solid metal cover. The space between
tubesheet and all tubes shall be sealed with packing glands. The cover is to be
bolted to the tubesheet with threaded studs and guide pins.
2.4.4. Quick Releasing Door
The convection section shall be equipped with quick-releasing and balanced
doors on two sides. Doors shall be large enough for easy access to convection
tubes for cleaning. Jack screws shall be located in each corner for breaking doors
loose for opening during washdown operations. Guide pins or other devices to
facilitate reinstallation of the doors shall be provided. Doors are to be secured
with threaded stud assemblies with a minimum diameter of 3/4-inch beveled
weld. Pin and wedge type latches are not acceptable. COMPANY shall approve
the ‘quick opening’ latches design prior to fabrication.
2.4.4.1 Door flange and other joint gaskets shall be designed to prevent leakage
under pressure up to 14-inches water column. Door flange minimum
width shall be 6-inches. Gasket material shall be 6"-wide by 1"-thick
ceramic fiber blanket. A 304 or 316 stainless steel supported sealing
surface shall be provided around the perimeter of each door and its
opening in the convection section; gaps shall be provided in the
perimeter plates to allow for thermal expansion.
2.4.4.2 An overhead rail system is to be provided for opening and suspending
doors when washing convection section. Permanent platform(s) with
ladder(s) shall be provided on both sides of the convection section to
facilitate door opening and tube cleaning.
2.4.4.3 A platform shall be provided half way up to the door to allow access to
the door fasteners along the top edge of each door. The platform design
shall comply to Caltex Safety in Design Field Manual.
2.4.5. Thermocouple
A direct reading thermocouple connection for stack temperature indication shall
be provided. This thermocouple shall be no further than 3-inches from the top
row of tubes. The thermocouple shall be installed substantially level, and well
protected from the effects of the wind.
2.4.5.1 Radiant section and transition section drains as well as those for the
steam traps, and other miscellaneous drains shall be tied into a single
drain header. The drain header shall be routed underneath the generator
and sloped to the convection section the end of the generator. The drain
header shall be size NPS 4, increasing to size NPS 6 where the transition
section drain enters. Major drain header sections shall be coupled with
quick removable groove/clamp joint fittings (Victaulic or
COMPANY-approved equal) for ease of disassembly and maintenance.
Gaskets shall be suitable for maximum anticipated temperature. A clean-
out shall be provided at burner end of the generator skid with a NPS 4
cap.
2.5. Refractory
2.5.1. General Requirement
2.5.1.1 The interior surface of the generators shall be insulated with a
combination of ceramic fiber and castable refractories. Exterior surface
temperatures must be no hotter than 140 deg F for 86 deg F ambient
temperature and 15 MPH wind.
2.5.1.2 All interior surfaces of radiant, transition, and convection sections
(including tubesheet covers and doors) shall be commercial sandblasted
to SSPC-SP6 with a surface profile of 1.5 mils to 2.0 mils maximum and
coated with 1/8-inch minimum thickness of Childers Stalastic CP-79 or
COMPANY-approved equal. Coating shall not be done until refractory
anchors, tube hangers, and all others welds are applied.
2.5.2. Castable Refractory System
Castable refractory shall be installed continuously; cold joints are not acceptable.
Castable refractory installation shall avoid sharp corners. Corners and joints shall
be rounded to prevent cracking.
2.5.2.1 Castable Refractory Material
Green Cast-45-L-GR or COMPANY-approved equal with maximum
temperature 2500 deg F and 80 lbs/ft3 density shall be used for all
castable refractory, unless other type is specified.
2.5.2.2 Anchor
Anchor type 310 stainless steel, 1/4-inch diameter, footed wavy vee or
long horn studs, with a length that will extend to 1-inch below the
refractory hot face, shall be used for castable refractory system. Anchors
shall be installed on 10-inch centers, except that 6-inch centers shall be
used in the tunnel between radiant and transition section.
2.5.3. Ceramic Fiber Refractory System
2.5.3.1 Anchor
Module shall be mechanically anchored with anchoring studs that are a
minimum 1/4-inch diameter and full filled welded to the shell.
The anchoring studs and all other hardware shall be 310 Stainless steel or
COMPANY approved alternative. Anchor shall be set 1-inch below the
hot face of the refractory. All anchoring hardware shall be protected from
combustion temperatures and atmosphere at all times.
?? The igniter flame shall be extinguished automatically after main burner flame
is established.
?? Igniter shall be provided to each burner. Transfer of fire from one burner to
another is not acceptable.
2.10.4. Fuel/Pilot Gas
2.10.4.1 Vendor shall provide a piping system to keep the gas clean and free of
liquid. Sufficient volume shall be provided upstream of safety shut off
valves and inlet gas supply reducing regulator to provide a cushioning
effect and reduce pressure surges.
2.10.4.2 Both fuel gas and gas pilot shall be provided with two step pressure
regulator, double block and bleed, low and high pressure switch
complete with monitoring pressure indicator that shall be fully
interlocked with control system. Both block valve for fuel gas, shall be
of MAXON type 808 or COMPANY approved equal, shall be an
electrical trip come with manual reset.
2.10.4.3 Minimum 1/2-inch ball valves shall be used for bleed and drain valve
of the gas piping system. All valves in the gas system shall be forged
steel; cast steel is not acceptable. All piping shall be no less than
schedule 80.
2.10.4.4 Vendor shall provide the flanged end connection for all fuel gas piping
connections. This pilot gas piping shall be connected to the fuel gas
piping, completed with a check valve and a block valve to avoid back
flow to the fuel gas piping.
2.10.5. Fuel Oil
2.10.5.1 Basic Requirement
The fuel oil heating system shall be designed and built to maintain a
near constant (±5°F) temperature at the burner of 200°F (±20°F,
depending upon the fuel oil being used) over the entire range of fuel
flow rates possible during burner operation, which includes flow
through the burner bypass valve when bypassing at maximum rate with
76 SSU oil. The initial fuel oil source may be Sumatran Light, 34.6 deg
API sweet crude. The heating system shall be designed to be bypassed
if not required when this fuel is used.
2.10.5.2 Piping
Fuel oil piping shall be NPS 1 schedule 40 seamless and include
thermowells upstream of each heater and at the burner inlet. All fuel oil
lines shall be insulated in accordance with this specification.
2.10.5.3 Shut-off Valve
An electric solenoid-operated safety shutoff valve, Whitey 3/4-inch
ball valve Model S-65TF12-35C with air actuator, or COMPANY
approved equal, shall be provided in the fuel oil piping downstream of
the fuel oil meter and just upstream of the burner. The shutoff valve
shall be activated by the generator shutdown system.
2.10.14. Burner
?? Furnish for crude oil or natural gas firing a Dual Fuel Burner COEN
Quantum Low Nox or equal without any Flue Gas Recirculation Technology,
with maximum input capacity of 62.5 million BTU/hr.
?? Burner shall guarantee Nox emission on natural gas firing will not exceed 30
ppmv dry at 3 % oxygen. CO emission will not exceed 200 ppmv
?? The Modulating firing range of the burner on gas fuel shall be less than 8 to 1
and on crude oil shall not be less than 6 to 1. The burner shall be capable of
firing fuel with not over 15 % excess air at full load with minimal CO and
unburned combustibles.
?? Lower Electrical Power consumed by the Blower electric motor will be
consider. Operating cost for 5 years service will be used for basic calculation
in the price evaluation.
Burner shall have the following instrumentation :
a. Fuel oil preheat temperature indicator
b. Fuel oil injection pressure indicator
c. Steam (or air) atomization pressure indicator
d. Low blower pressure shutdown switch set for 8-inch H20 column.
?? Burner throat high temperature indicating limit switch
?? Bailey flamon UW3100 or COMPANY approved equal ultraviolet flame
detector with swivel mount. Purge air shall be supplied to detector from
combustion air blower; final connection to sensor shall be with braided
stainless steel hose.
?? Any hinged or quick-release latches on the burner mount shall be provided
with interlock safety switches tied into the generator shutdown system. Any
necessary flexible hose shall be provided to allow the burner swing easily
with minimum connection to be released.
?? Adequate space for installation of additional air dampener shall be provided.
2.10.15. Blower
2.10.15.1 General
?? Boiler shall be furnished with at least one forced draft fan. Detailed
specification is shown in the attached data sheets.
?? Fans shall be of centrifugal type and shall be furnished complete
with suction damper control or variable vane control, inlet screen,
silencer, flexible coupling, coupling guard, bearings, pedestals and
supports.
?? Fan housing or inlet box shall be made of minimum 5 mm plate
and braced for rigidity. Housing shall be designed to allow
horizontal split for rotor removal without dismantling the duck
work.
?? Flow Control
Fan speed control by variable voltage or variable frequency device
may be used.
mounting position specified, even when all grease has liquified due to
centrifugal action or high temperature.
2.13.4.6 Motor frames shall be assigned in accordance with the latest edition of
NEMA Publication No. MG 1.
2.13.4.7 Motor terminal boxes shall be of adequate size to permit terminating
motor leads and other wiring at the motor. For motors rated 600 volts
or less, terminal box shall be sized in accordance with NEMA
MG1-11.06 or MG1-20.62, as applicable. Conduit entrance shall be
adequate for rigid steel conduit required for Type THW or THWN
aluminum conductor power leads sized in accordance with the National
Electrical Code, but not smaller than 3/4-inch diameter. Separate
terminal boxes shall be provided for space heater and temperature
detector leads.
2.13.4.8 Induction motor rotor cages may be of fabricated copper or copper
alloy, fabricated aluminum, or cast aluminum construction. The rotor
cage and core construction shall have proven satisfactory performance
in the size, speed, and horsepower ranges specified.
2.13.4.9 Bearings and lubrication systems shall comply with the requirements
of subsections 3.9 and 3.10 of API RP-541, with the following
exceptions:
?? Grease-lubricated ball bearings shall be provided on all motors up
to 250 horsepower.
?? Ball bearings shall be vacuum-degassed steel, motor quality.
Bearings shall be selected for a minimum AFBMA L-10 Rating
Life of 40,000 hours continuous service at rated motor load and
40°C ambient temperature.
2.13.4.10 All motors shall be suitable for full-voltage starting. Polyphase
integral-horsepower induction motors per NEMA MG1-10.32D shall
have starting capabilities in accordance with NEMA MG1-12.50.
2.13.4.11 Motors shall be capable of accelerating actual driven load, or load
inertia in accordance with NEMA MG1-20.42 where driven load is not
known, with 80% of rated voltage applied. Vendor shall submit with
his bid the following data for motor accelerating its load under the
above conditions: line current, efficiency, power factor, and
acceleration time versus speed or slip. Data may be in the form of
plotted curves or tabular computer output.
2.13.4.12 Vendor shall specify the guaranteed minimum efficiency for each
motor per IEEE 112 Method F. The stray-load losses shall be assumed
as 1.2% for motors below 2500 horsepower.
2.13.4.13 The minimum permissible stall (locked rotor) time shall be either 150
% of, or 5 seconds more than, (whichever is greater), the time required
to accelerate the actual driven load, or load inertia in accordance with
NEMA MG1-20.42 where driven load is not known, with 80% or rated
voltage applied.
All instrument air lines outside the control console shall be stainless
steel tubing, of 3/8-inch diameter and 0.035-inch wall thickness
minimum. 1/4 inch diameter tubing may be used inside the control
panel. Fittings shall be Swagelok or COMPANY approved equal.
Instrument air lines shall be installed in a neat and workmanlike
manner, parallel or perpendicular to structural members. Appropriate
support fittings shall be installed on structural members as needed.
Where bends are required, they shall be made with suitable tube
bending equipment. Uniform circular cross section of the tubing shall
be maintained at such bends. No single bend shall be greater than 90°.
2.14.1.3 Air Lines End Connection
The connection for instrument air system shall be provided by Vendor
on the generator at skid beam level on the control cab end. It shall be
equipped with pressure gauge and block valve. The instrument air
system shall include an inlet filter/separator. COMPANY will supply
instrument air to the generator skid boundary at 100-125 psig. Vendor
shall provide all necessary pressure regulators and gauges.
2.14.2. Instrumentation
2.14.2.1 General
Instrument ranges shall be selected such that the normal operating
range is between 35% and 75% of the instruments total range.
Instruments shall be approved by an independent testing laboratory
(UL, FM, CSA, or BASEEFA) for the service in which it is used and
shall bear their label or listing. Use of instruments without agency
listing will require written approval from COMPANY.
??Instrument components exposed to the environment shall be
weatherproof and of suitable design to withstand environmental
conditions as described in data sheets.
??All safety devices shall be set fairly close to the operating
conditions. Vendor shall submit the setting proposal for approval.
??Instrument drafting symbols and identification shall be per
COMPANY’s Drawing Standards.
2.14.2.2 Gages Installation
The gages shall be perpendicular to the process pipe flow. For steam
application it shall be installed at the top of the pipe. The gages shall be
located in a straight section of the pipe that contain streamline flow.
All Pressure gauges shall have Root connection, 2-way valve manifold
to block and bleed the pressure from the system. Root valve size shall
½ inch FNPT
2.14.2.3 Pressure Gauge
All pressure gauges in water/steam service shall be glycerineor silicone
oil-filled or other type that has a dampening effects. All pressure
gauges shall have a 4 1/2-inch dial face (0-2000 psi) with blowout plug
in the case, 1/2-inch NPT stem, stainless steel bourdon tube mounted
locally. Pressure gauges in steam service shall be equipped with steel
siphons. Gauges will have shatterproof glass and safety blowouts and
shall be of the safety front design. Dials will be white with black
markings.
2.14.2.4 Pressure Switches
Pressure switches will be of the snap-acting type, utilizing DPDT rated
not less than 4 amps at 120 VAC. All switches will be field adjustable
and will have a proof pressure at least 1-1/2 times the maximum
operating pressure to which they will be subjected. The operating
pressure shall be no more than 70 % of the maximum range.
Each pressure switch shall has its own root connection, not connected
from the same root valve connection that is made for other instrument.
Root valve shall be used with a plug tee to bleed the process pressure
to the atmosphere. Union connection shall be provided downstream the
switches for maintenance purpose.
Syphon shall be installed for steam application. Locking device shall
be provided in the pressure switch.
2.14.2.5 Thermowell
Protective wells manufactured from drilled 316 SS barstock shall be
used with all temperature elements. All wells shall be bored to 0.260-
inch and designed for use with bi-metallic thermometers. All test wells
shall be provided with a suitable plug and chain.
Thermowells shall be located in a downstream of Pressure Indicator
root connection at 2 - 5 diameter distance.
2.14.2.6 Thermometer
Thermometer will be of the 5-inch dial bi-metallic type, every-angle.
The number of ranges shall be kept to a minimum. It shall be of filled
system or has other type of dampener.
2.14.2.7 Electronic Instruments
Electronic instruments will be moisture and fungus proof and will
utilize a standard 4-20 mA DC transmission level. All Transmitter shall
be Smart Type.Thermocouples may be run directly to a receiver in the
control panel.
2.14.2.8 Pressure Regulators
Pressure regulators for instruments shall be filter/separator type, Fisher
67FR or COMPANY approved equal.
2.14.2.9 Safety-Relief Valves
Safety-relief valves shall be provided in accordance with ASME Boiler
and Pressure Vessel Code and the ANSI Code for Pressure Piping, as
applicable. Valve body material shall conform to piping specification.
Bellows seal or balanced-type valves shall be used.
All safety-relief valves will be of the spring loaded type with metal-to-
metal seats. Valve leakage shall conform to API RP-527 for
commercial tightness. Lifting levers shall be provided on thermal relief
valves.
2.14.2.10 Alarm and Shutdown System
Alarm and shutdown systems is shown on COMPANY P&ID drawing.
In general, shut down systems shall be design for maximum protection
of the operating personnel and equipment. Where applicable, shutdown
systems will be energized during normal plant operation, i.e., de-
energized to trip. Shutdown functions will be alarmed, and where
practical, an alarm will actuate prior to the shutdown. Alarm devices in
transmitter outputs are acceptable.
2.14.2.11 Solenoid Valve
All solenoid valves shall have Group 1, Class F coils that are moisture
and fungus proof and epoxy molded construction. The enclosure shall
meet the NEMA type 4 classification; i.e., watertight and dust tight or
explosion proof if required by area classification.
2.14.2.12 Announciator
An announciator shall have “First Out” capability with a choice of
N.O./N.C. signal contact. The unit shall contain an audible alarm, 120
V 60 Hz power supply. The display shall have two lamps per position.
2.14.2.13 Thermocouple
Thermocouple extension wire type "JX" shall be run in rigid steel
conduit separate from power cables. Vendor shall minimize wire
splices. All extension wire runs from thermocouple heads to recording
or indicating instruments in the generator control panel shall be made
without splices, except where wires are terminated on iron-constant
terminal strips provided in terminal boxes for this purpose. Extension
wires originating from thermocouples in the radiant section shall be
terminated in the radiant skid terminal box. Vendor shall provide
sufficient extension wire coiled in this terminal box for purchaser to
complete interconnection in the field. Extension wires originating
from thermocouples in the burner section shall be terminated in the
generator control panel through the burner skid terminal box. Rigid
steel conduits shall be installed from terminal boxes to shipping split as
required for CONTRACTOR's field wiring.
?? Control, indication, recording and alarm functions of the A.C.C. system shall
be integrated in the boiler control panel installed in control room
2.16.2. Master signal
?? Unless otherwise specified, pressure of the main steam shall be employed as
the master signal for the A.C.C. system
?? In case it is specified on the data sheet that both of the steam pressure and
steam flow are to be employed as master signal, change-over station shall be
provided in the boiler control panel.
?? Change-over of the master signal shall be done without causing any bumping
due to switching.
?? Auto/manual change-over switch shall be provided.
?? In case multiple boiler are connected to a common header, a common master
signal generator (at the main header) may be employed. In such case, load
distributing station shall be provided for respective boiler.
2.16.3. Control of Fuel
?? Flow quantity of fuel (gas or oil) shall be controlled by A.C.C.
?? If fuel (gas or oil) pressure at supply point is too high to be reduced by a flow
control valve, a pressure control system shall be provided.
?? For limiting maximum opening of fuel control valves, adjustable mechanical
stopper shall be provided.
?? Atomizing steam pressure for liquid fuel firing shall be controlled by a
differential pressure controller or a constant pressure controller. Diagram of
differential pressure pick-up cell shall be made of corrosion resistant
material.
?? In case multiple fuels are to be automatically controlled simultaneously, sum
of the fuel flow as the feed back signal to the A.C.C. system shall be
converted into the value of amount of heat.
?? In case of multiple fuel control, “auto-manual” switch-over station shall be
provided for each fuel.
?? In case of multiple fuel control, “bumpless” switch-over system for selecting
automatically controlled fuel from one fuel to another shall be provided.
2.16.4. Control of Air
?? Flow rate of air shall be controlled by the A.C.C. system by regulating inlet
vane of the forced draft fan.
?? Variable fan speed control by changing the electric frequency may be used.
?? An air-rich control system shall be provided for fuel/air control circuit.
?? Air flow shall be measured and feed-back.
?? In case a tandem driving system with automatic driver change-over is applied
for the forced draft fan, temporary automatic fuel reduction system shall be
applied. Whereas air flow shall be controlled keeping ‘air rich’ condition.
2.16.4.1 Burner fire shall be kept stable at the specified turned-down condition. ‘ON-
OFF’ control of fire is not acceptable.
2.16.4.2 Minimum sustainable firing rate shall be specified by Vendor.
2.16.5. Feed Water Control
?? The feed water flow to the boiler shall be controlled by a three element
control which rations water flow to steam flow and is reset by drum level,
unless otherwise specified.
?? Signal for water level control shall be raised by differential pressure type
transmitter. Signal for boiler trip by extremely low water level shall be raised
by displacement type transmitter. Each function mentioned above shall be
extracted from each individual column.
2
?? Trip-triggering primary element for boilers of 100 kg/cm G class and over
may be of differential pressure type instead of displacement type.
2.16.6. Steam Temperature Control
?? In case of superheated steam boiler, steam temperature control shall be
provided.
?? In the S.T.C control range, steam temperature fluctuation shall be within
+3?C of the rated steam temperature
?? In case a high response is needed, S.T.C. loop configuration shall be as
specified in the attached data sheet.
overloads in each motor lead. All starters shall be provided with circuit
breaker/disconnects. All starters and breaker/disconnects shall be Square D or
COMPANY- approved equal.
2.18.4. Circuit breakers rather than fused switches shall be used for protection of all
power, lighting and control circuits.
2.18.5. All shutdown and control circuits shall be 120-volt, single phase, 60 Hz.
2.18.6. The generator shall have a control console to facilitate monitoring pressures,
temperatures, flows, control functions, and alarms. It shall be installed out of the
cab area and shall have at least the minimum access clearances specified by the
National Electrical Code.
2.18.7. The control console shall be a free-standing ventilated NEMA 4X enclosure of
minimum 7 gauge hot-rolled steel plate. It shall contain all electrical controls
mounted for ease of monitoring pressures, temperatures, flows, and control/alarm
functions in a single location.
2.18.8. All pane l-mounted select switches, pushbuttons, and indicating lamps shall be
Allen-Bradley 800H or COMPANY-approved equal.
2.18.9. Lighting transformer shall be encapsulated dry type of weatherproof construction
for outdoor installation. Transformers shall have type H (220°C ultimate
temperature) insulation and have a 115°C or less temperature rise at full-rated
load. The transformer shall have a rated capacity of at least 125% the initial
connected load.
2.18.10. A branch circuit panel shall be provided for all lighting, single phase power and
control loads.
2.18.11. The control areas shall be provided with manually- controlled fluorescent
lighting using enclosed, industrial type luminaries.
2.18.12. A 115-volt, 20 amp weatherproof receptacle with ground fault protection shall be
provided at the control console exterior for maintenance hand tool operation.
2.18.13. Electrical items shall be furnished as described on the attached Electrical Bill of
Material. The quantities as shown in the Bill of Materials are for the minimum
requirement only. Vendor shall be responsible to provide all necessary materials
in conformance with this specification.
2.18.14. A start-up procedure/caution written on the plate shall be posted closed to control
panel.
?? Ignition transformer.
?? Flame scanner controller
?? Power switch
2.19.2. The start-up panel shall have grounding earth connection.
2.19.3. The start-up panel shall be of weather-proof, corrosion resistant type.
2.19.4. Control panel shall be equipped with all control, indication, recording and
annunciating equipment.
2.19.5. All supervision and control of the boiler under any kind of operation shall be
possible from control panel, except for light-off operation.
2.19.6. Remote light-off operation is not acceptable.
2.19.7. Function of each panel shall be as follows.
LEGEND : o : Possible
w : Possible (partially)
x : Impossible
components are the burner and control, radiant, transition, and convection
sections. Vendor shall supply all gasketing material required to reassemble the
sections after delivery. Skid size and shape shall be in accordance with the
following dimensions and drawing. Any deviation from these dimensions shall
be disqualified by COMPANY.
2.20.4. Grating
All areas requiring clean-up (under burner, etc.) shall be fully covered with
removable safety grating. Other personnel access area shall be covered with
safety grating. All grating shall be serrated, hot dipped galvanized and fastened
with clips spaced at maximum 3-foot intervals, and at each corner. Grating shall
be trimmed to fit around pipe supports and other penetrations.
2.20.5. Sleeve for Pipe Penetrations
Where penetrations through structural components are required for routing piping
or conduit, a sleeve shall be installed to ensure structural integrity. Sleeves shall
consist of schedule 40 pipe one size larger than the pipe (or outside diameter of
insulation, if insulated) or conduit passing through the structural member, and
seal welded on each side of the sleeve.
2.20.6. Others
Skids shall be of adequate strength to maintain alignment of equipment during
shipment, to minimize vibrations during generator operation, and to distribute
loads to the concrete generator foundation. Lifting lugs shall be provided as
necessary to facilitate field installation. Any special spreader bars or apparatus
necessary for lifting and setting the skids shall be furnished by Vendor.
3. FABRICATION
3.1. Welding
The profile of welding grooves shall conform to the requirements of the manufacturer’s
qualified procedure. Any welding of pressure holding parts shall be done by qualified
welder.
3.3. Insulation
3.3.1. Insulation Requirements
3.3.2. Material
Mineral wool, Bradford Enercon ‘Enerok 1200’ or COMPANY-approved equal
shall be installed on all hot lines, heat exchangers, and heater. For the line that is
subject to be stepped by, the weatherproofed, preformed, hydrous calcium
silicate insulation, John-Manville “Thermo 12” or COMPANY-approved equal
shall be used. The insulation will be of sufficient thickness to only allow a
maximum 100 deg F outside surface temperature at design conditions. Use 2-1/2-
inches minimum of insulation for high pressure steam lines. All insulation
materials shall be asbestos-free.
3.3.3. Insulation shall be secured with 16-gage galvanized wire spaced on 9-inch
centers. See detail 1 of Standard Drawing GD-N99783-5
3.3.4. Metal End-Cap
All insulated piping shall use a metal end-cap where the insulation terminates and
the pipe continues onward, uninsulated. A metal end-cap shall also be used
adjacent to flanges. The end of the insulation shall be covered by seal lap with
1/8-inch thick coating of weatherproof mastic that laps the pipe two inches. See
detail 6 of Standard Drawing GD-N99783-5. Clearance between the flange and
metal end-cap shall be provided to allow insertion and removal of stud bolts.
3.3.5. Ring Supports
Insulation on vertical piping shall have ring supports installed at the bottom of
the pipe run and above interruptions in the pipe run such as at flanges and valves.
See detail 3 and 4 of Standard Drawing GD-N99783-5
3.3.6. Expansion joints shall be provided at the tangent points of elbows when the pipe
temperature exceeds 425 deg F, and at the following spacing between tangent
points:
Pipe Operating Temperature (deg F) Maximum Spacing (ft)
below 425 None
425 - 459 36
460 – 650 24
3.3.8.3 Installation
Weather jacket shall be overlap 2-inches longitudinally and
circumferentially. Longitudinal joints shall be staggered between the
three o’clock and nine o’clock positions. Longitudinal seams on
aluminum jacket shall have a 1/4-inch rolled hem.
3.3.8.4 Secure the jacket with 1/2-inch x 0.015-inch straps and buckles. Joints in
weather jacket shall be caulked with sealant.
3.3.8.5 Weather jacket on vertical piping shall have S-clips, spaced 180 degrees
apart, to maintain it in position. See detail 3 of Standard Drawing GD-
N99783.
3.3.9. Surface Conditions
All surfaces to be insulated shall be clean and dry. The surface operating below
200 deg F shall be prime with coating. No insulation shall be installed until
completion of any stress-relieving and chemical cleaning and hydrotest
inspection and release in writing.
3.3.10. Flexible Removable Insulation Covers
All carbon steel or low alloy valve bodies, pipe flanges, manways, and exchanger
body flanges that operate at temperature over 100 deg F shall be insulated.
Flexible, reusable insulation covers shall be provided except for screwed and
welded fitting/valves where permanent insulation prefers.
4.1. General
Unless otherwise specified, Coating and Painting shall be in accordance with SP-ME-ME-
025 “Coating and Painting Specification”.
Paint:
Primer : Inhibited Alkyd, 2.0 - 3.0 mils DFT
(Hempalin Primer 1205 Red 5041 or equal)
Topcoat : Alkyd Enamel, 2.0 - 3.0 mils DFT
(Hempalin Enamel 5214 Green 410 RS or equal)
Touch-up : use this system, the color shall be Caltex Forest Green or COMPANY
approved equal.
4.2.3. Coating System 2.0 (Self-Cured Inorganic Zinc/Pure Silicone)
This system shall be applied on :
?? All stairs, walkways, platform, guards
?? All structural steel not within 6-inches of the radiant, transition, or
convection section
?? Cab roofs and supports
?? Blower ducting
Surface Preparation : SSPC-SP10 Near-white blast finish
Anchor Pattern : 1.5 - 2.5 mils
Paint:
Primer : Self-cured Inorganic Zinc, 3.0 - 4.0 mils DFT
(Ameron “Dimetcote 6 or 9” or equal)
Topcoat : High temperature Silicone 1, 1.5 - 2.5 mils DFT
(Ameron “Amercoat 878 “ or equal)
Touch-up : Pure silicon topcoat only, 2 coats. The color shall be Caltex
Forest Green or equal.
4.2.4. The electrical/control panel shall be primed on the external surface with one coat
of polymide-catalyzed epoxy coating applied to a minimum dry film thickness of
2 mils. After priming the exterior, apply two coats of polyamide-catalyzed epoxy
green finish on all outside surfaces, a minimum of 2 mils dry film thickness per
coat. Paint dry film thickness after completion shall be at least 6 mils. The
internal surfaces shall have one primer coat and two topcoats of white, with final
minimum dry film thickness of 6 mils.
4.2.5. Vendor shall propose the brand and color of the paint for COMPANY approval.
Each multi-coat system shall use materials from a single manufacturer.
4.2.6. Surface Preparation
4.2.6.1 Solvent Cleaning
All surfaces to be coated shall be clean of all contaminants that would
affect the integrity of the coating system. Detergent or solvent cleaning
shall be performed as outlined in SSPC-SP-1.
4.2.6.2 Abrasive Blasting
4.2.7.3 Both primer and finish paints shall be capable of withstanding maximum
expected temperatures and shall be chemically compatible. Paint top coat
shall produce a semi gloss finish to allow easy cleaning of steam
generator
4.2.7.4 All coating film thickness shall be free of defects such as pinholes, voids,
and bubbles. Prior to the application of any coat, all damage and defects
in previous coats shall be repaired.
4.2.8. Inspection
Vendor shall perform all inspection necessary to ensure that surface preparation
and coating application complies with the requirements of this specification. All
work shall be subject to COMPANY inspection.
4.2.8.1 Surface Preparation
4.2.8.2 Immediately prior to priming, blasted surfaces shall be inspected by the
following methods to verify that the specified surface preparation has
been achieved.
4.2.8.3 The anchor pattern shall be verified using Testex Inc. “Press-O-Film”
tape or COMPANY approved equal. The measurement shall be recorded
on the Coating Inspection Record.
4.2.8.4 The degree of cleanliness shall be verified by comparison to the
appropriate visual standard included in SSPC-VIS 1-67. Surface profile
shall be visually inspected using the Keane-Tator Surface Profile
Comparator.
4.2.8.5 Coating Application
Dry film thickness shall be measured using a “Microtest” magnetic film
thickness gage or COMPANY approved equal. Dry film thickness shall
be recorded on the Coating Inspection Record for each coat as work
proceed as well as for the total thickness of each finished coating system.
Vendor shall furnish all necessary data listed on the attached Vendor Data Requirements
List in accordance with quantities, type, and timing specified in the list.
5.3. Inspection Data Report and Certificate
Vendor shall also furnish necessary pressure vessel inspection data reports and safety relief
valve certificates as required by COMPANY, including:
5.3.1. Engineering dimensional drawings
5.3.2. Material specifications
5.3.3. Spring specification showing spring range and number
5.3.4. Manufacturer's Test Certificate
5.3.5. ASME Form U-1 Manufacturer's Data Report for Pressure Vessels
5.4. Radiographic
Radiographic inspection requirements are as follows:
5.4.1. Piping for which the applicable code is ASME Section I shall have 10 % of
welds radiographed. Acceptance criteria shall be per ASME Section I.
5.4.2. Piping for which the applicable code is ANSI B31.3 shall have 10 % of welds
radiographed. Acceptance criteria shall be ANSI B31.3 standards for 100 %
radiography.
5.4.3. Tube hangers radiography
5.4.4. Tube hangers shall be subjected to 10% radiography, to detect casting defect
before being installed, witnessed by COMPANY’s Inspector.
5.4.5. Dye Penetrant Test shall be applied on 10% weld of tube hangers and shells
witnessed by COMPANY Inspector.
5.4.6. Selection of welds for radiographic inspection shall be made with agreement of
COMPANY inspector.
5.4.7. Vendor shall quote unit price per NDT film. COMPANY may elect to perform
radiographic inspection more than the required 10% at COMPANY’s expense.
5.4.8. Any welds that fail to pass radiographic test shall be repair and be re-
radiographed at Vendor’s expense. For any failure Vendor will be penaltied to
radiograph additional welds in amount that grows exponentially at Vendor’s
expense. Example: if there is one failure weld, in addition to repair and to re-
radiograph, Vendor shall radiograph other two welds (number of failure times
two) that is not included in 10% provision. If this penaltied-radiography fail
Vendor shall radiograph additional four times number of failure and so forth.
5.5. Hydrotest
All the piping, except for the drain line, shall be hydrotested at 1.5 times allowable working
pressure (MAWP). All gas and pneumatic piping shall be tested with dry air at 1.1 times
MAWP. After hydrotest, piping shall be purged with dry air to ensure removal of all scales,
slag, and debris from piping. This hydrotest does not release Vendor from the responsibility
for any leakages found during COMPANY’s hydrotest after unit being installed in
COMPANY’s site.
5.6. Pre-assembling
Vendor shall pre-assemble every generator at his plant before shipment to COMPANY.
Subsequent disassembly should be done only as necessary to ensure safe shipment of the
component skids.
Compliance to this obligation does not release Vendor from the responsibility for any
mismatch during field assembly caused by any deterioration occurred during the shipment.
5.7. COMPANY’s Inspector
While work on this purchase order contract is being performed, Inspector(s) designated by
COMPANY shall have free duty entry to all parts of Vendor's premises involving the
manufacture, inspection, and testing of material to be supplied to COMPANY. The Vendor
shall afford the inspector(s), free of cost, all necessary and reasonable use of facilities for
determining that the material is being furnished in accordance with this specification. All
tests and inspections by said inspector(s) shall be made at the place of manufacture before
shipment and shall be so conducted to minimize interference with operation of Vendor's
plant.
5.8. Inspection by COMPANY shall not relieve the manufacturer of complying with any
expressed or implied specification or Vendor's guarantee.
No change arising out of inspection shall be made to this contract until such change has
been approved by COMPANY representative in writing.
5.9. Subcontractor
Vendor shall notify any subcontractors of COMPANY's inspection requirements, and
obtain their consent to comply with these requirements.
5.10. COMPANY shall approve all subcontractors in writing prior to Vendor entering into legal
agreements with said subcontractor(s).
5.11. Steam Generator Test
The first generator completed shall be given a low-fire test run at the Vendor's plant. All
other units shall be given a complete, documented, functional mechanical, electrical, and
pneumatic tests and check-out before shipment to COMPANY. These tests may be
witnessed by COMPANY representatives.
5.12. DEPNAKER Approval
The Vendor shall arrange and obtain wet stamped from "Departemen Tenaga Kerja
(DEPNAKER)" on the fabrication drawings and ASME Code calculations for the steam
generators.
8. VENDOR’S GUARANTEE
8.1. Vendor guarantees that the equipment specified herein is free from fault in design,
workmanship, and material. Vendor guarantees that these items are of sufficient size and
capacity and proper material to fulfill satisfactorily the operating conditions specified by
COMPANY.
8.2. Should any defect in design, material, or operating characteristics develop during the first
year of equipment operation, Vendor agrees to make all necessary repairs, alterations, and
replacements free of charge. If the defect or failure to function properly cannot be
corrected, Vendor agrees to replace promptly without charge said equipment.
8.3. Vendor guarantees that each steam generator package is complete and in a good condition
as COMPANY receives it in the delivery point. Any discrepancies of materials and
structural damages happened during the shipment is the responsibility of Vendor.
8.4. Vendor Performance Requirement
The Vendor’s steam generator design must have demonstrated at least 10 years of proven
oil field operation in wet steam (i.e. 80% steam quality) service for reliability and
efficiency. Vendor shall submit the experienced-user list for reference.
8.5. Efficiency Guarantee
8.5.1. The steam generators, in new and clean condition, shall be designed to operate at
a minimum 88 % gross thermal efficiency (percentage of gross BTU input of
fuel that is realized as useful BTU output) based on 20 % excess air for crude oil-
fired operation or 84 % gross thermal efficiency based on 10 % excess air for
fuel gas-fired operation.
8.5.2. Efficiency must be guaranteed in the new and clean condition. Vendor must
submit full efficiency testing procedure for review and acceptance.
8.5.3. Guarantee for efficiency must include all repairs or additions to be made to
achieve the minimum efficiency at no cost to the COMPANY.
Electrical one line and control (ladder) diagrams. Instrument identification on the control
Diagram shall correspond to identification on the P&ID.
supplied in Indonesia, number of units fabricated in Indonesia and year, as well as a world-
wide user's list for similar equipment.
10.21. Major Components Supplier
Define extent of Indonesian and foreign supply of major components, including: control
panel, control valves, instruments, exchanger/generator coils, insulation, and structural
components.
10.22. Fabrication Site Facilities
Indonesian domestic fabrication site, including: covered shop area, open yard area, paint
shop area, wharf frontage area, water depth and crane lift capacity (tons), proposed method
of load-out of completed units, number and types of employees.
10.23. Number of welders qualified to ASME Code. Define Code category to which they are
qualified. Fabrication yard ASME Code authorized to use "U" or "S" stamp (answer Yes
or No).
10.24. Service personnel available and their location for providing start-up/commissioning
assistance. Include their perdiem rate
12.2. One reproducible (mylar) set of final, Certified, "As-Built" drawings shall be transmitted to
COMPANY on or before shipment of the first generator. Two sets of blue-line copies of
these "As-Built" drawings shall be shipped with the first generator.
12.3. Vendor shall furnish six sets of Operating and Maintenance (O&M) Manuals for the
generators on or before the shipment of the first generator. Manuals shall provide
recommended operating and maintenance procedures for all furnished equipment, spare
parts lists, catalog data, bills of material referenced to the P&ID, certified copies of P&ID,
electrical one-line, and generator outline drawings, manufacturer's data sheets, lubrication
recommendations, etc.
12.4. Vendor shall furnish a reproducible set and two copies of the following data sheets,
completed to reflect "As-Built" instrumentation and equipment information. In addition,
one copy of each shall be included in each O&M Manuals.
12.4.1. Instrument summary
?? Temperature transmitters
?? Thermocouples
?? Thermocouple extension lead wire
?? Thermometers
?? Temperature wells
?? Pressure transmitters
?? Control valves
?? Miscellaneous instruments
?? Flow meters
?? Pressure safety valves
?? Switches - pressure, temperature, flow
?? Heat exchangers
?? Electric motor data sheets
?? Fired-Heater data sheet
12.4.2. Master parts list with part numbers and serial numbers. This list shall be tied to
identification numbers used on the generator P&ID for easy cross reference by
field personnel.
12.4.3. Oils and lubricants required, standard description and grade including alternate
suppliers with their designations.
12.4.4. Nameplate rubbings or photographs.
12.5. Progress Schedule Report
Vendor shall provide a project schedule showing design, material procurement, fabrication,
assembly, and testing activities. The schedule shall be of sufficient detail to allow accurate
progress monitoring for each generator purchased as well as overall project progress. The
schedule shall be updated regularly, at least once each month, and transmitted to
COMPANY.