Professional Documents
Culture Documents
Sohag Water and Wastewater Company Tender Requirements
Sohag Water and Wastewater Company Tender Requirements
¯ protection device for high temperature of PTC electric motor winding 500
It works on a 220 Vac operating voltage with an allowance for the value of the
voltage ± 10% ,50HZ, it must has 1NC and 1NO output contacts
1
● over/under voltage and phase failure/sequence protection relay
¯A quadruple protection device against high and low voltages , phase failure /
sequence with the following technical specifications :
-Rated supply voltage (Us) 3 * 380V AC + Neutral
- Frequency 50 Hz
-Output contacts 1NC/1NO 500
-Under voltage limit 330 - 360 Vac ( Adjustable )
-Over voltage limit 400 - 440 Vac ( Adjustable )
-With Timer (1 – 10) sec ( Adjustable )
2
● over/under voltage and phase failure/sequence and PTC protection relay
¯e protection device against high and low voltages , phase failure / sequence
and protect from high temperature of motor winding with the following
technical specifications :
-Rated supply voltage (Us) 3 * 380V AC + Neutral
- Frequency 50 Hz
200
-Output contacts 1NC/1NO
-Under voltage limit 330 - 360 Vac ( Adjustable )
-Over voltage limit 400 - 440 Vac ( Adjustable )
-With Timer (1 – 10) sec ( Adjustable )
3
● PTC protection device with Digital screen