Professional Documents
Culture Documents
PG - 01 - EEC506 - Advanced Electrical Machine Lab Manual
PG - 01 - EEC506 - Advanced Electrical Machine Lab Manual
Location of the Lab: Ground floor, academic complex (Room no: 024)
1. Study of parallel operation of two three phase transformers belonging to different vector 2-5
groups
2. Study the Scott connection of two single-phase transformer 6-7
3. Study of Zig-Zag connection of transformer 8-11
4. Measurement of efficiency of a DC compound motor under eddy current loading 12-14
5. Measurement of speed of a DC series motor as a function of load torque 15-17
6. Study of speed control of a 3-Φ squirrel-cage induction motor by V/f control method. 18-20
7. Study of voltage regulation of a 3-Φ alternator by synchronous impedance method 21-25
8. Determination of direct axis reactance ( X d ) and quadrature axis reactance ( Xq ) of a 26-29
1|Page
Department of Electrical Engineering
Course name: Advanced Electrical Machine Lab
Course code: EEC506
Location of the Lab: Ground floor, academic complex (Room no: 024)
Experiment No.: 01
TITLE:- Study of parallel operation of two three phase transformers belonging to the different
vector groups.
OBJECTIVE:-To check the vector groups of two three phase transformers and operate them in
parallel (e.g. Dy1 with another Dy11).
APPARATUS REQUIRED: –
2 Digital Phase
Angle Meter
3 MCB-4 pin
THEORY: -
To facilitate selection of three phase transformers for parallel operation, they are classified by
various ‘Vector Group Symbols’ such as Yy0, Yd1, Yd11, Dy1, etc. where, the first symbol stands
for high-voltage (h.v) winding connection, the second for low-voltage (l.v) winding connection
and the third for the phase displacement of the phasor representing the induced counter voltage
between one l.v. terminal and the l.v. neutral, with respect to the h.v winding phasor representing
the induced counter voltage between the corresponding h.v. terminal and the h.v. neutral. Thus, it
is revealed that careful study of the internal connections of the transformers should be made before
they are put in parallel.
Parallel operation of three phase transformers is done to meet the increased power demand.
Whenever power demand is more than existing rating of transformer, it is needed to connect
another transformer in parallel to the existing transformer, it is needed to connect another
transformer in parallel to the existing transformer. For successful parallel operation of two three
phase transformer, it is necessary to satisfy certain conditions. These are:
2|Page
i. Equal turns ratio, i.e., the magnitudes of the secondary line voltages should be equal,
ii. The kVA ratings must be inversely proportional to their effective impedances so that
load sharing is in proportion to the kVA rating of the transformers,
iii. The same polarity connections,
iv. The same phase sequence and
v. The same vector groups, i.e, the secondary line voltages of the transformers must be in
phase with each other.
CIRCUIT DIAGRAM: -
c2
C2(A1) A2(B1)
a1
N c1
a2
b1
B2(C1) b2
c2
B1(C2)
a1
a2
c1
b1
N
(A1)B2 (C1)A2 b2
3|Page
R
A1 A2 B1 C2
B2 C1 A1 A2 B1 B2 C1 C2
a1 a2 b1 b2 c1 c2 a1 a2 b1 b2 c1 c2
MCB
Fig. 3. Connection Diagram for parallel operation of two three phase transformers belonging to
two different vector groups.
PROCEDURE: -
1) a. Perform the internal connections of transformers Tr-1 as Dy11 and Tr-II as Dy1.
b. For Dy1 or Dy11, change the external connections of any two terminals for both h.v and l.v
sides to convert it to Dy11 or Dy1, respectively.
2) Operate Tr-I and Tr-II in parallel and fill up the following table.
OBSERVATION: -
Line to line voltage Phase difference Line to line voltage Phase difference
angle angle
4|Page
RESULTS: -
The parallel operation of two three phase transformers (belonging to different vector groups) has
been performed and studied successfully by checking their voltage phasors (in terms of both
PRECAUTIONS: -
1. Loose connections should not be made. Connections should be right and tight.
2. Live wire should not be touched.
3. Power supply should be switched off while making a connection
5|Page
Department of Electrical Engineering
Course name: Advanced Electrical Machine Lab
Course code: EEC274
Location of the Lab: Ground floor, academic complex (Room no: 024)
Experiment No.: 02
OBJECT: To obtain a two-phase supply from a balance three-phase supply utilizing two single-
phase transformers.
THEORY:
Scott connection is used to obtain three phases from two-phase supply and vice-versa. From the
balanced three-phase voltage triangle (Fig. 2) ABC it can be seen that
i) The perpendicular from vertex C on AB at a point D gives BD= DA
Thus, if two single-phase transformers I & II (Fig 1) are so chosen that i) Transformer I (known
as the main transformer) has N1 turns in the primary with a midpoint tap D,
ii) Transformer II (known as teaser transformer) has 0.866 N1 turns in the primary and Both
transformers have equal turns N2 in the secondary and the primary are connected as shown in Fig
1, the application of a balanced three-phase voltage across A, B& C will result in in
That is, the voltage across the secondary windings would be in quadrature with each other with
the magnitudes equal to each other (since they have the same number of turns)
APPARATUS REQUIRED: –
3 Multimeter
4 3-Φ auto-transformer
6|Page
CIRCUIT DIAGRAM:
PROCEDURE:
1) Perform the polarity test.
2) Connect the circuit diagram as shown in Fig 1. Apply three-phase voltage to A, B, C through
variac.
3) Check the phase displacement of Eb1 and Eb2 by means of a digital phase angle meter.
4) Check the input 3-phase supply.
5) Measure the line to neutral voltage and verify.
RESULTS: -
The magnitude of voltage in between the main transformer and teaser transformer (secondary
side).
Phase angle in between the main transformer and teaser transformer (secondary side).
PRECAUTION:
7|Page
Department of Electrical Engineering
Course name: Advanced Electrical Machine Lab
Location of the Lab: Ground floor, academic complex (Room no: 024)
Experiment No.: 03
TITLE: Study of Zig-Zag connection of transformer
OBJECTIVE:– To make the phase angle zero degrees in between pairs of voltage.
APPARATUS REQUIRED:–
2 Multimeter
3 3-Φ auto-transformer
THEORY:
8|Page
primary coils. Each phase, therefore, couples with each other phase, and the voltages cancel out.
As such, there would be negligible current through the neutral point, which can be tied to the
ground. Each of the three "limbs" is split into two sections. The two halves of each limb have an
equal number of turns and are wound in opposite directions. With the neutral grounded, during a
phase-to-ground short fault, a third of the current returns to the fault current, and the remainder
must go through two of the three phases when used to derive a grounding point from a delta source.
If one or more phases fault to earth, the voltage applied to each phase of the transformer is no
longer in balance; fluxes in the windings no longer oppose. (Using symmetrical components, this
is Ia0 = Ib0 = Ic0.) Zero-sequence (earth fault) current exists between the transformers neutral to the
faulting phase. The purpose of a zigzag transformer in this application is to provide a return path
for earth faults on delta-connected systems. With negligible current in the neutral under normal
conditions, providing the defective load will be automatically disconnected in a fault condition, an
undersized transformer may be used only as short-time rating is required (i.e. the transformer can
only carry full rated current for, say, 60 s). Impedance should not be too low for desired maximum
fault current. Impedance can be added after the secondary are summed to limit maximum fault
currents (the 3Io path).
A combination of Y (wye or star), delta, and zigzag windings may be used to achieve a vector
phase shift. For example, an electrical network may have a transmission network of 110 kV/33 kV
star/star transformers, with 33 kV/11 kV delta/star for the high voltage distribution network. If a
transformation is required directly between the 110 kV/11 kV network an option is to use a 110
kV/11 kV star/delta transformer. The problem is that the 11 kV delta no longer has an earth
reference point. Installing a zigzag transformer near the secondary side of the 110 kV/11 kV
transformer provides the required earth reference point.
CIRCUIT DIAGRAM:-
9|Page
PHASOR DIAGRAM:-
PROCEDURE:-
TRANSFORMER:-
Primary R Y B
Terminal 0 V A1 B1 C1
Terminal 440 V A2 B2 C2
Secondary
R Y B
Terminal 0 V a1 b1 c1
a3 b3 c3
Terminal 110 V a2 b2 c2
a4 b4 c4
10 | P a g e
OBSERVATION:-
1 VA2B2-Va4b4
2 VB2C2-Vb4c4
3 VC2A2-Vc4a4
RESULT:-
The phase angle between pair of voltages is always 00 in case of zigzag connection of transformers.
PRECAUTIONS:-
11 | P a g e
Department of Electrical Engineering
Course name: Advanced Electrical Machine Lab
Course code: EEC506
Location of the Lab: Ground floor, academic complex (Room no: 024)
Experiment No.: 04
OBJECTIVE:– To study the efficiency of dc compound motor under eddy current loading
APPARATUS REQUIRED: –
Sl. No. Instruments/ Range Quantity Make
Apparatus
1 D.C Series Motor
2 Voltmeter
3 Ammeter
4 Tachometer
5 Eddy current
dynamometer
THEORY:
DC compound motor is a combination of shunt and series motor. this type of motor has both series
and shunt field coils that are connected to the winding of an armature. The field coils which are
connected to the motor armature windings, afford the necessary amount of magnetic flux and lead
to the production of necessary torque to aid the rotation at the desired speed level. It is basically
wound for a shunt field with a fewer number of turns of series winding in the top.
Compound motors may be classified into two main categories based on the way their field winding
is connected to the armature winding and which are long shunt and short shunt.
Cumulative Compounding
When the shunt field flux made by the shunt winding aids the effect of the main field flux made
by the series winding, it may be called that the motor is cumulatively compounded. Cumulative
motors produce high starting torque like a series motor and reasonably good speed regulation at
high speeds like a shunt DC motor. It may work with a huge amount of loads and run smoothly. It
is practically suitable and it is widely used.
12 | P a g e
Differential Compounding
If the shunt field flux reduces the effect of the main series winding, it may be said that the dc motor
is differentially compounded.
One of the most vital parts of any electrical machine is its characteristics. The characteristics of an
electrical machine define its applications and capabilities. The shunt field winding of cumulative
motors and their additional flux from series winding produces a large amount of flux which causes
a large amount of torque at low speed. It means that motors such as cumulative run at a reasonable
speed in light or even no-load conditions. However, in the differential motors, both series and shut
fluxes oppose each other. It means that the flux decreases while the load increases. Actually, in
this condition, the motor with an increase in load produces high speed and it can be horribly
hazardous, especially on a full load.
CIRCUIT DIAGRAM
PROCEDURE:
13 | P a g e
5. The load is then added to the motor gradually and for each load, the voltmeter, ammeter,
spring balance readings, and speed of the motor are noted.
6. The motor is then brought to no-load condition and field rheostat to minimum position,
then DPST switch is opened.
OBSERVATION:
CALCULATION:
1. Draw curves of (i) Efficiency in percentage (ii) Torque (iii) Speed against power output
in watts.
2. Show one sample calculation
PRECAUTIONS:
14 | P a g e
Department of Electrical Engineering
Course name: Advanced Electrical Machine Lab
Course code: EEC506
Location of the Lab: Ground floor, academic complex (Room no: 024)
Experiment No.: 05
OBJECTIVE:– To study the variation of (i) Speed (ii) Torque (iii) Efficiency with power output
of DC series motor
APPARATUS REQUIRED: –
Sl. No. Instruments/ Range Quantity Make
Apparatus
1 D.C Series Motor
2 Voltmeter
3 Ammeter
4 RPM meter
7 Connecting Wires
THEORY:
DC series motor is an electrical machine that is applied at the place where high torque operating
conditions are needed. It is associated in series with the armature winding of the motor. Due to the
series connection, the motor generates high starting torque compared to other types of motors.
From the motor characteristics, it may decide where it may be applied. Let us explain in detail
the characteristics by comparing its speed-armature current, speed-torque, and Torque-armature
current relationships.
Eb = V − I a Ra
Eb
N
T Ia
15 | P a g e
T I a2
CIRCUIT DIAGRAM
PROCEDURE:
OBSERVATION:
CALCULATION:
16 | P a g e
7. Torque, T= (9.81) × (S1 ~ S2) × R, N-m, where R is the radius of the brake drum, Find
the circumference of the brake drum. Using 2πR, R is obtained.
2 NT
8. Output power = W
60
output
9. %efficiency = %
Input
REPORT:
3. Draw curves of (i) Efficiency in percentage (ii) Torque (iii) Speed against power output
in watts.
4. Show one sample calculation
PRECAUTIONS:
1. Ensure that the eddy current coil voltage should not give in idle conditions.
17 | P a g e
Department of Electrical Engineering
Course name: Advanced Electrical Machine Lab
Course code: EEC506
Location of the Lab: Ground floor, academic complex (Room no: 024)
Experiment No.: 06
TITLE:- Study of speed control of a 3-Φ squirrel-cage induction motor by V/f control method
OBJECTIVE:-To determine V/f ratio for the speed control of 3-Φ squirrel-cage induction
motor.
APPARATUS REQUIRED: –
2 Frequency meter
4 Voltmeter
5 Ammeter
6 Tachometer
7 V/f controller
CIRCUIT DIAGRAM:-
18 | P a g e
Fig. 2 Block diagram of V/f control drive
THEORY: -
By changing the supply frequency, the synchronous speed of the induction motor can be controlled
over a wide range according to Eqn. (1) and (2). The Synchronous speed (𝑁𝑆 ) and air gap flux are
given by
120𝑓
𝑁𝑆 = (1)
𝑃
𝑁 = 𝑁𝑆 (1 − 𝑆) (2)
1 𝑉
𝛷𝑔 = 4.44𝐾 ( ) (3)
1 𝑇𝑃ℎ1 𝑓
Where, 𝐾1 = stator winding constant, 𝑻𝑷𝒉𝟏 =stator turns per phase, V = supply voltage, f = Supply
frequency. It may be seen that from the eqn. (3) that if the supply frequency f is changed, the value
of air gap flux also gets affected. Induction motors are normally designed to operate near the
saturation point on their magnetization curves, So the increase in flux due to a decrease in
frequency will cause excessive magnetization currents to flow in the motor. Hence, it is necessary
to maintain air gap flux constant when supply frequency is changed. This can be achieved when
the V/f remains constant. That means when frequency varies then voltage must be varied in the
same proportion so that the net ratio remains the same or constant. This can be achieved V/f control
drive as shown in Fig. 2. In this arrangement, a Variable (V, f) supply can be obtained from a
constant (V, f) supply using the converter-inverter arrangement as shown in Fig. 2. When the
supply frequency to the stator terminal varies, the supply voltage to the stator also varies
automatically in the same proportion. As a result, which V/f ratio remains constant.
PROCEDURE: -
1) Make all the connections as shown in Fig. 1 while keeping all the switches in the off
position.
2) Switch on the power supply and start the motor by pressing the START button.
3) Set the frequency on V-f Control drive to 50Hz and note down the corresponding values
of stator voltage using a voltmeter and motor speed using a tachometer.
19 | P a g e
4) To control the speed decrease the values of frequency on the V-f Control drive step by step
and note down the corresponding readings of stator voltage and motor speed.
5) Stop the motor by pressing the STOP button. Switch off the power supply and remove all
the connections properly.
OBSERVATION TABLE: -
1) Forward Direction
Sl. No. Frequency (Hz) Voltage (V) V/f Ratio Rotor speed (rpm)
2) Backward Direction
Sl. No Frequency (Hz) Voltage (V) V/f Ratio Rotor speed (rpm)
RESULTS: -
The speed of three-phase induction motor has been controlled by V/f method and the value of V/f
ratio is also obtained.
PRECAUTIONS: -
1. The motor input current should not exceed its rated value.
2. Make sure to turn off the motor while switching direction to forward to backward or vice
versa.
20 | P a g e
Department of Electrical Engineering
Course name: Advanced Electrical Machine Lab
Location of the Lab: Ground floor, academic complex (Room no: 024)
Experiment No.: 07
TITLE:– Study of voltage regulation of a 3-Φ alternator by synchronous impedance method
APPARATUS REQUIRED: –
THEORY: –
The voltage regulation of an alternator is defined as the increase in voltage from full-load to no-
load (field excitation and prime mover speed remain the same) expressed as a fraction of the rated
terminal voltage.
The regulation of a 3-Φ alternator may be predetermined by conducting the Open Circuit (OC)
and the Short Circuit (SC) tests. The methods employed for the determination of regulation are
EMF or synchronous impedance method, MMF or Ampere Turns method, and the ZPF or Potier
triangle method. In this experiment, the EMF method is used. The OC and SC graphs are plotted
from the two tests. The synchronous impedance is found in the OC test. The regulation is then
determined at different power factors by calculations using vector diagrams. The EMF method is
also called the pessimistic method as the value of regulation obtained is much more than the actual
value.
As shown in Fig 1. (a), a fictitious reactance Xa represents the armature reaction effect. It is
considered to be of such value that it produces flux and emf as those produced by armature reaction
MMF acting alone. In the circuit model, Ef stands for open circuit phase terminal voltage, also
21 | P a g e
known as excitation emf also xl and Rs are the leakage reactance and armature resistance
respectively. Xs is called synchronous reactance.
Fig 1. (a) Equivalent circuit with synchronous impedance and (b) phasor diagram
E f = (V cos + I a Ra ) 2 + (V sin + I a X s ) 2
Open Circuit Characteristics (OCC): - It depicts the magnetization characteristics of the machine.
It is the plot of open-circuit voltage (line-to-line or phase voltage) against field current at a given
speed. The straight-line portion of the line is called the air gap line.
Short Circuit Characteristics (SCC): - It is the plot of armature current against field current when
the machine is driven at its speed with the terminal short-circuited.
22 | P a g e
Fig 2. O.C.C. and S.C.C. of an alternator
CIRCUIT DIAGRAM:–
Fig 3. Circuit diagram for determination of voltage regulation of 3-Φ alternator by synchronous
impedance method (Open Circuit and Short Circuit Tests)
23 | P a g e
PROCEDURE: –
GRAPH: –
1. Draw the Open Circuit Characteristic curve (Generated Voltage per phase VS Field
current).
2. Draw the Short Circuit Characteristics curve (Short circuit current VS Field current)
3. From the graph find the open-circuit voltage per phase for the rated short circuit current
(Isc).
4. By using respective formulae find the Zs, Xs, Eo, and percentage voltage regulation.
OBSERVATION: –
24 | P a g e
CALCULATIONS: –
RESULT: –
Thus, the voltage regulation of the 3-Φ alternator has been predetermined by the synchronous
impedance method as follows:
PRECAUTIONS: –
(i) The motor field rheostat should be kept in the minimum resistance position.
(ii) The alternator field potential divider should be kept in the minimum voltage position.
(iii) Initially all switches are in the open position.
25 | P a g e
Department of Electrical Engineering
Course name: Advanced Electrical Machine Lab
Course code: EEC506
Location of the Lab: Ground floor, academic complex (Room no: 024)
Experiment No.: 08
( )
TITLE:– Determination of direct axis reactance ( X d ) and quadrature axis reactance X q of a
Synchronous Machine (Slip test)
OBJECTIVE:– To determine the direct axis reactance ( X d ) and quadrature axis reactance X q ( )
of a salient pole synchronous machine.
APPARATUS REQUIRED: –
2 DC Motor
3 Ammeter
4 Voltmeter
5 Tachometer
6 3-Φ auto-transformer
7 3-Φ M.C.B
THEORY: -
The salient-pole type synchronous machines have a non-uniform air gap. The air gap is smaller
along the polar axis which is coinciding with the main field pole axis (direct axis or d-axis) than
that of the inter-polar axis (quadrature axis or q-axis). Therefore, the reluctance of the air gap must
not be the same. Along the d-axis, the reluctance of the magnetic circuit is somewhat less than that
along the q–axis. Hence, the effect of magnetomotive force (MMF), when acting along the d-axis,
will be different than that when it is acting along the q-axis. Thus, the effect of armature reaction
in the case of a salient pole synchronous machine also must be taken as two components viz. one
acting along the d-axis and the other acting along the q-axis.
26 | P a g e
“Blondel’s two-reaction theory” considers the effects of these armature reactions separately.
Neglecting saturation, their different effects are considered by assigning to each, an appropriate
value of armature-reaction “reactance”: the direct axis synchronous reactance ( Xd ) and
( )
the quadrature axis synchronous reactance X q . They are the steady state reactance of the salient-
pole type synchronous machine. The values of X d and X q can be measured by the slip test on a
synchronous machine.
The basic circuit diagram for conducting this test is shown in Fig. 1. Here the armature terminals
are supplied with a subnormal voltage of rated frequency with the field circuit left open. The
generator is driven by a prime mover at a slip speed that is slightly more or less than the
synchronous speed. This is equivalent to the condition in which the armature MMF remains
stationary and the rotor rotates at a slip speed with respect to the armature MMF. As the rotor poles
slip through the armature MMF, the armature MMF will be in line with the d-axis and q-axis,
alternately. When it is in line with the d-axis, the armature MMF directly acts on the magnetic
circuit and at this instant, the voltage applied on the machine divided by armature current gives
the value of X d . At this instant, the armature current per phase is minimum and the terminal
When the armature MMF coincides with the q-axis, then the voltage impressed divided by
armature current gives the value of X q . At this instant, the armature current per phase is maximum
Since, X d X q , the armature current, hence the pointer of the ammeter will oscillate from a
minimum to a maximum value. Similarly, the terminal voltage will also oscillate between the
minimum and maximum.
27 | P a g e
CIRCUIT DIAGRAM:-
Fig. 1. Connection diagram for the measurement of X d & X q of the synchronous machine.
PROCEDURE: -
1) Connect the machine as in Fig. 1. and set the output of the variac to zero.
2) Switch on the DC supply and run the DC motor at a rated speed closer to the synchronous
speed of the alternator but less than the synchronous speed while keeping its field circuit
open.
3) Switch on the AC supply and increase the variac output to a suitable value (normally ¼ of
rated voltage). Observe the variations in the readings of the voltmeter and ammeter.
4) Adjust the speed of the DC motor finely to get maximum swings in ammeter and voltmeter
pointers.
5) Record maximum and minimum readings of the voltmeter and the ammeter.
6) Take additional sets of readings by adjusting the different outputs of the variac.
7) Now adjust the DC motor speed to a value little greater than the synchronous speed and
take similar readings as above.
28 | P a g e
OBSERVATION: -
RESULTS:-
The values of X d and X q of three-phase salient-pole alternator have been found which are:
X d = ohm.
Xq = ohm.
PRECAUTIONS:-
29 | P a g e
Department of Electrical Engineering
Course name: Advanced Electrical Machine Lab
Course code: EEC506
Location of the Lab: Ground floor, academic complex (Room no: 024)
Experiment No.: 09
TITLE:– Measurement of negative sequence reactance of a 3-Φ alternator
OBJECTIVE:– To obtain the value of the negative sequence reactance of a 3-Φ alternator.
APPARATUS REQUIRED: –
THEORY: -
The negative sequence reactance may be found by applying balanced negative sequence
voltage to the armature terminals. The machine is driven by the prime mover at its rated
synchronous speed with the field winding short-circuited. The ratio of voltage per phase and
armature current per phase gives the negative sequence reactance per phase. Another method
of measuring negative sequence reactance is found from the armature terminals. The machine
is driven at synchronous speed and the field current is so adjusted until the rated terminal
current flows in the phases shorted through the armature and a current coil of wattmeter,
respectively. The value of negative sequence reactance ( X neg ) is given by
V
X neg =
3I sc
30 | P a g e
CIRCUIT DIAGRAM:-
PROCEDURE: -
31 | P a g e
RESULTS: -
X neg =_____ohm.
PRECAUTIONS: -
32 | P a g e
Department of Electrical Engineering
Course name: Advanced Electrical Machine Lab
Course code: EEC506
Location of the Lab: Ground floor, academic complex (Room no: 024)
Experiment No.: 10
TITLE:– Study of different types of starter for the starting of 3-Φ squirrel-cage induction motor
OBJECTIVE:– To find torque ratio for each method of starting of 3-Φ squirrel-cage induction
motor.
MACHINE UNDER TEST:-
1 3-Φ squirrel-cage
induction motor
APPARATUS REQUIRED:–
THEORY:– In a 3-Φ induction motor, the magnitude of an induced e.m.f. in the rotor circuit
depends on the slip of induction motor. This induced e.m.f. effectively decides the magnitude
of the rotor current. The rotor current/phase in the running condition is given by,
sE 20
I2r =
R22 + (sX 20 )
2
Where ‘E20’ is rotor induced voltage/phase at standstill, ‘R2’ is rotor resistance/phase, ‘X20’ is
rotor reactance/phase at standstill and ‘s’ is the slip. But at start, the speed of the motor is
zero and slip is at its maximum i.e. unity. So, magnitude of rotor induced e.m.f. is very large
at start. As rotor conductors are short circuited, the large induced e.m.f. circulates very high
current through rotor at start. This excessive current results in a large voltage drop in the
distribution network and stop other machine which are already running on the supply
mains.To avoid such effects, it is necessary to limit the current drawn by the motor at start.
33 | P a g e
Small induction motor (up to 2 kW capacity) may be connected directly to the supply mains
whereas higher capacity motor are strictly prohibited to connect directly due to their high
starting current which is 5 to 7 times the full-load current.
The starter is a device which is basically used to limit high starting current by supplying
reduced voltage to the motor at the time of starting. Not only the starter limits the starting
current but also provides the protection to the induction motor against overt loading, single
phasing and low voltage situations. Torque produced by the induction motor is given by,
3
2
sE 20 R2 3 I 2r 2
T= = R ,
2ns R2 2 + (sX 20 )2 2 n s s
2
Where ‘ns’ = 120f/p is the synchronous speed (rps), ‘f’ is supply frequency (Hz) and ‘p’ is the
number of poles in the motor. Three types of starting method is used generally for squirrel
cage induction motor-
1. Direct-on-line (DOL) starting:– This is the most common starting method available in
the market. Fig. 1 shows the DOL starter, consist of main contactor and thermal or electronic
overload relay. The motor is directly switch on to the supply mains. This met hod is restricted
to small motor up to 5 kW rating for which starting torque is about twice the full load torque.
The ratio of starting to no load torque is given by :
2
Tst I 2 st
= snl,
Tnl I 2 nl
Where, ‘ Tst ’ is starting torque, ‘ Tnl is no-load torque, I 2 st is starting current, I 2 nl is no-load current, snl is full
load slip.
2. Auto-transformer starting:– A 3-Φ star connected autotransformer can be used to reduce the
voltage applied to the stator. The schematic diagram of autotransformer starter is shown in the Fig.
2.When the switch is in the start position, the stator winding is supplied with reduced voltage.
34 | P a g e
When motor gathers 80% of the normal speed, rated voltage gets applied to stator winding. The
motor starts rotating with normal speed. It can be used for both star and delta connected stator of
3-Φ induction motors. The ratio of starting to no-load torque is given by,
2
Tst I
= X 2 2 sc snl,
Tnl I 2 nl
Where ‘X’ is the ratio of stator terminal voltage at starting to supply voltage and I2sc is the starting
current when full supply voltage is applied.
35 | P a g e
PROCEDURE:–
i. Make all the connections as shown in figure in off position.
ii. Switch on the power supply and start the motor by pressing START button.
iii. Note down the reading of ammeter, voltmeter in starting and running condition.
iv. Stop the motor by pressing STOP button, switch off the power supply and remove all the
connections properly.
RESULTS :–
I. DOL starting :
Sl. Voltage Stator I 2 st (A) I 2 nl (A) ns nr Snl Tst
No. (V) connection Tnl
PRECAUTIONS:–
3. All connections should be proper and tight.
4. The motor input current should not exceed its rated value.
36 | P a g e