2. Device Identification.................................................................................3
6. Dynamic Variables..................................................................................11
ii HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.13 Command #140: Read Model Number – Table II ............................................................. 39
10.14 Command #141: Read Model Number –Table III ............................................................. 40
10.15 Command #142: Read time in service, percent time in stress, service life remaining41
10.16 Command #143: Read last Time & Date for correct URV, correct LRV for sensor 2 . 42
10.17 Command #144: Read last Time & Date for correct URV, correct LRV for Sensor 1 . 43
10.18 Command #145: Read Previous Time & Date for correct URV, correct LRV for sensor 2
44
10.19 Command #146: Read current Time & Date for correct URV, correct LRV sensor 2 . 45
10.20 Command #147: Read current, last and previous reset correct Time & Date sensor 246
10.21 Command #148: Read power fail counter and its timestamp ........................................ 47
10.22 Command #149: Read ET and electronics temperature tracking values. .................... 48
10.23 Command #150: Read ET lower tracking parameters .................................................... 49
10.24 Command #151: Read CVD1 User Cal values ................................................................. 50
10.25 Command #152: Read CVD2 User Cal values ................................................................. 51
10.26 Command #153: Read Configuration History sequence and database ID ................... 52
10.27 Command #154: Read Configuration history data ......................................................... 54
10.28 Command #155: Read current, minimum operating voltage and its timestamp ......... 55
10.29 Command #156: Reset min terminal voltage and its time stamp .................................. 56
10.30 Command #157: Read M360 core temperature up tracking parameters ...................... 57
10.31 Command #158: Read M360 core temperature down tracking parameters ................. 58
10.32 Command #159: Read AVDD max and time stamp ......................................................... 59
10.33 Command #160: Read AVDD min and time stamp ......................................................... 60
10.34 Command #161: Read sensors and transmitter install dates........................................ 61
10.35 Command #162: Read sensor board stress monitor and sensor board service life . 62
10.36 Command #163: Write transmitter install date to sensor .............................................. 63
10.37 Command #164: Read Model Number –Table IV ............................................................. 64
10.38 Command #165: Read Previous Time & Date for correct URV, correct LRV sensor 165
10.39 Command #166: Read current Time & Date for correct URV, correct LRV sensor 1 . 66
10.40 Command #167: Read current, last and previous reset correct Time & Date sensor 167
10.41 Command #168: Read URL2, LRL2 .................................................................................. 68
10.42 Command #173: Write sensor1 bias value ...................................................................... 69
10.43 Command #174: Write sensor2 bias value ...................................................................... 70
10.44 Command #175: Read/Lock Write Protect Configuration .............................................. 71
10.45 Command #176: Write/Change Write Protect Password................................................ 72
10.46 Command #179: Read UTL1, LTL1, UTL2 ........................................................................ 73
10.47 Command #185: Read LTL2, CJ-UTL, CJ-LL ................................................................... 74
10.48 Command #186: Read all sensor times in service .......................................................... 75
10.49 Command #187: Read HART-DE board firmware revision ............................................ 76
10.50 Command #188: Read the loop control mode, loop controlling sensor, hysteresis value,
Damping for bump-less transfer .................................................................................................. 77
10.51 Command #189: Write Loop control mode ...................................................................... 78
10.52 Command #191: Write sensor1 type ................................................................................ 79
10.53 Command #192: Write PV high and low alarm limits ..................................................... 81
10.54 Command #193: Write RTD1 type ..................................................................................... 82
10.55 Command #194: Write RTD2 type ..................................................................................... 83
10.56 Command #197: Write CJ compensation type ................................................................ 84
10.57 Command #198: Write break detect status...................................................................... 85
10.58 Command #199: Write Mid Range Value((MRV) .............................................................. 86
10.59 Command #200: Write latching status ............................................................................. 87
10.60 Command #201: Write match PV status .......................................................................... 88
10.61 Command #202: Write fixed CJ compensation ............................................................... 89
10.62 Command #203: Write RTD1 lead wire resistance .......................................................... 90
10.63 Command #204: Write RTD2 lead wire resistance .......................................................... 91
10.64 Command #210: Write Display General configuration ................................................... 92
10.65 Command #211: Read Display General configuration ................................................... 94
10.66 Command #212: Read Display Firmware Version .......................................................... 96
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 iii
10.67 Command #213: Read error log part1 .............................................................................. 97
10.68 Command #214: Read error log part2 .............................................................................. 98
10.69 Command #215: Reset error log ....................................................................................... 99
10.70 Command #216: Read error logging status................................................................... 100
10.71 Command #217: Write error logging status .................................................................. 101
10.72 Command #218: Read PV tracking values..................................................................... 102
10.73 Command #219: Read SV up tracking values ............................................................... 103
10.74 Command #220: Read additional status ........................................................................ 104
10.75 Command #221: Set Date/Time for calibration.............................................................. 105
10.76 Command #222: Read sensor firmware version number............................................. 106
10.77 Command #223: Read delta limit, delta, excess delta detection ................................. 107
10.78 Command #224: Write delta limit .................................................................................... 108
10.79 Command #225: Write excess delta detection .............................................................. 109
10.80 Command #226: Write hysteresis value ........................................................................ 110
10.81 Command #227: Write damping for bump less transfer .............................................. 111
10.82 Command #228: Read maintenance flag ....................................................................... 112
10.83 Command #230: Read tamper alarm settings ............................................................... 113
10.84 Command #231: Write Tamper alarm settings .............................................................. 114
10.85 Command #232: Reset executed attempts counter ...................................................... 115
10.86 Command #240: Reset PV tracking values.................................................................... 116
10.87 Command #247: Read SV down tracking values .......................................................... 117
10.88 Command #64768: Write Display Screen configuration I ............................................ 118
10.89 Command #64769: Write Display View configuration II ............................................... 120
10.90 Command #64770: Write View configuration III ............................................................ 121
10.91 Command #64771: Read Display View configuration I ................................................ 122
10.92 Command #64772: Read Display View configuration II ............................................... 124
10.93 Command #64773: Read Display View configuration III .............................................. 125
10.94 Command #64774: Write CVD1 4 Coefficients .............................................................. 126
10.95 Command #64775: Write CVD2 4 Coefficients .............................................................. 127
10.96 Command #64776: Write DO Alarm1 Type .................................................................... 128
10.97 Command #64777: Write DO Alarm2 Type .................................................................... 129
10.98 Command #64778: Write DO Setpoint1 .......................................................................... 130
10.99 Command #64779: Write DO Setpoint2 .......................................................................... 131
10.100 Command #64780: Write DO Alarm Hysteresis............................................................. 132
10.101 Command #64781: Write DO Alarm Latch ..................................................................... 133
10.102 Command #64782: Write DO Alarm Block ..................................................................... 134
10.103 Command #64783: Write DO Deviation Value ............................................................... 135
10.104 Command #64786: Read CVD1 co-efficient Values: ..................................................... 136
10.105 Command #64787: Read CVD2 co-efficient Values: ..................................................... 137
10.106 Command #64790: Write upper calibration point sensor1 .......................................... 138
10.107 Command #64791: Write lower calibration point sensor1 ........................................... 139
10.108 Command #64792: Write upper calibration point sensor2 .......................................... 140
10.109 Command #64793: Write lower calibration point sensor2 ........................................... 141
10.110 Command #64794: Read calibration points sensor1 .................................................... 142
10.111 Command #64795: Read calibration points sensor2 .................................................... 143
10.112 Command #64796: Read DO Values: ............................................................................. 144
10.113 Command #64802: Read CVD1 Coefficient activation: ................................................ 145
10.114 Command #64803: Read CVD2 Coefficient activation: ................................................ 146
10.115 Command #64804: Write CVD1 Coefficient activation ................................................. 147
10.116 Command #64805: Write CVD2 Coefficient activation ................................................. 148
10.117 Command #64806: Write sensor base resistance ........................................................ 149
10.118 Command #64807: Read sensor ET up tracking values .............................................. 150
10.119 Command #64808: Read sensor ET down tracking values ......................................... 151
10.120 Command #64809: Read M360 Core Temp Delta .......................................................... 152
10.121 Command #64811: Write Sensor1 install date .............................................................. 153
10.122 Command #64812: Write Sensor2 install date .............................................................. 154
iv HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.123 Command #64813: Reset CJ tracking parameters ....................................................... 155
10.124 Command #64814: Acknowledge latching .................................................................... 156
10.125 Command #64815: Write Sensor Scratch pad............................................................... 157
10.126 Command #64816: Read Sensor Scratch pad ............................................................... 158
10.127 Command #64817: Write NAMUR Selection .................................................................. 159
10.128 Command #64818: Read NAMUR Selection .................................................................. 160
10.129 Command #64822: Read Sensor 1 and Sensor 2 resistance ....................................... 161
12. Performance..........................................................................................166
12.1 Sampling Rates ................................................................................................................ 166
12.2 Power-Up ........................................................................................................................... 166
12.3 Device Reset ..................................................................................................................... 166
12.4 Self Test............................................................................................................................. 166
12.5 Command Response Times ............................................................................................ 167
12.6 Busy and Delayed-Response .......................................................................................... 167
12.7 Long Messages ................................................................................................................ 167
12.8 Non-Volatile Memory........................................................................................................ 167
12.9 Modes ................................................................................................................................ 168
12.10 Write Protection ................................................................................................................ 168
12.11 Damping ............................................................................................................................ 168
12.12 Damping for bump less transfer ..................................................................................... 168
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 v
List of Figures
Figure 1 Typical Communication Interface ................................................................................. 4
Figure 2 Three-Button Option..................................................................................................... 8
Figure 3 Locating the Failsafe Jumper ....................................................................................... 9
List of Tables
Table 1 Abbreviations and Definitions ........................................................................................ 2
Table 2 Device Identification ...................................................................................................... 3
Table 3 Analog Output Values ................................................................................................... 7
Table 4 Available Display Characteristics..................................................................................10
Table 5 List of Dynamic Variables .............................................................................................11
Table 6 Field Device Status ......................................................................................................12
Table 7 Extended Device Status ...............................................................................................13
Table 8 Additional Field Device Status ......................................................................................14
Table 9 Universal Commands ...................................................................................................16
Table 10 Common Practice Commands ....................................................................................17
Table 11 Device Specific Commands........................................................................................26
Table 12 Unit Codes supported...............................................................................................162
Table 13 Temperature Units....................................................................................................162
Table 14 Command 220 details ..............................................................................................164
Table 15 Sensor type codes..................................................................................................165
Table 16 Sampling Rates ........................................................................................................166
Table 17 Response Times ......................................................................................................167
Table 18 Capability checklist ...................................................................................................169
Table 19 Default Configuration................................................................................................170
vi HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
1. Introduction
1.1 Scope
The Honeywell SmartLine Temperature Transmitter, STT850, device complies with HART
Protocol Revision 7.x. This document specifies all the device specific features and gives HART
Protocol implementation details. The functionality of this Field Device is described sufficiently to
allow its proper application in a process and its complete support in HART capable Host
Applications.
1.2 Purpose
This specification is designed to complement other documentation by providing a complete,
unambiguous description of this Field Device from a HART Communication perspective.
PV Primary Variable
SV Secondary Variable
TV Tertiary Variable
QV Quaternary Variable
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 1
Float An IEEE 754 single precision floating point value (4 bytes)
1.5 References
HART Field Communications Protocol Specification. HCF_SPEC-12, Revision 7.4, dated 29
June 2012.
2 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
2. Device Identification
The Honeywell STT850 is designed to meet hazardous area approvals. Refer to the user
manual on the available methods of protections for use in hazardous locations.
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 3
3. Product Overview
3.1 Transmitter
The STT850 Temperature Transmitter measures the process temperature and transmits an
output signal proportional to the measured variable over a 4 to 20 milli ampere, two-wire loop. A
diagrammatic representation of STT850 is shown in Figure 1.
The STT850 can transmit its output in either an analog 4 to 20 milli ampere format or a digital DE
protocol format for direct digital communications with our TPS system, Allen-Bradley PLCs and
other control systems. Besides the process variable (PV) output, the transmitter also provides the
Cold junction temperature as a secondary variable, Sensor 1& 2 inputs as tertiary and quaternary
variables respectively, which are available as read-only parameters through the MC Toolkit when
the transmitter is in its analog mode.
It supports multiple various TC, RTD; MV & OHM sensor types Refer Annex.
A configuration tool (Honeywell MCToolkit) is connected to the loop wiring of the STT850
transmitter for direct communication with the transmitter. The handheld device communicates with
the transmitter via the HART interface.
Note that multiple mounting configurations are possible and are fully described in the STT850
Installation and User Manuals.
4 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
3.2 Communicator Purpose
The communicator allows the user to adjust transmitter values, or diagnose potential problems from
a remote location such as the control room. The communicator can be used to:
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 5
4. Product Interfaces
4.1 Process Interface
Sensor Input Channel
The primary variable is the temperature derived based on the sensor 1 & 2 inputs and the loop
control mode configured. Temperature sensors are wired externally to the transmitter.
The transmitter is designed to operate in a two-wire power/current loop with loop resistance and
power supply voltage within the operating range.
6 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
Current values are shown in the table below.
* Honeywell will offer the STT850 HART transmitter with NAMUR compliant analog outputs, in
addition to the "Classic" levels traditionally featured in the product.
** For the Lightning protection option, add 1 Volt (internal added 50 Ohm impedance).
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 7
4.3 Local Interfaces, Jumpers and Switches
The STT850 three-button option provides a user interface and operation without the use of the
MC Toolkit. Figure 2 shows the location of the three-button option and the labels for each
button.
• Enter (S )
o Enter the top level main menu from the normal PV display mode
o Select a target to go down to the next menu level, up to the previous level or exit
back to the PV display mode
o Accept the current value of an entered parameter
• Down (↓)
o Advance to the next configured screen when in the normal PV display mode
o Scroll down to the next item in a menu
o Advance through a list of parameters for configuration
o Advance through numerical values or alpha characters for data entry
• Up ( Z↑)
o Go back to the previous configured screen when in the normal PV display mode
o Scroll up to the previous item in a menu
o Go back through a list of parameters for configuration
o Go back through numerical values or alpha characters for data entry
8 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
Figure 3 Locating the Failsafe Jumper
Device Malfunction
The direction of indication of a detected malfunction by the analog current output is user-selectable
to up or down, by means of a two-position jumper inside the instrument. STT850 transmitters are
shipped with a default failsafe direction of upscale. This means that the transmitter’s output will be
driven upscale (maximum output) when the transmitter detects a critical status.
Write Protection
The STT850 transmitters have a transmitter security option, also known as a “write protect option,”
which is jumper-selectable. The jumper, located on the transmitter’s printed wiring assembly (PWA),
can be positioned to allow read and write access or read only access to the transmitter’s
configuration database. When the jumper is in the read only position, the transmitter’s configuration
and calibration data can only be read / viewed. The factory-default jumper positions are for read
and write access. The figure above shows the location of the write protect jumper on the PWA. The
Write Protect Hardware Jumper is placed behind the Display PWA. For accessing the hardware
write protect jumper, the Display PWA needs to be removed. Also software write protect is
available. Refer Common Practice command 175 &command 176. When the Device is in Hardware
write protect (Jumper) then the software write protect functionality is inoperative.
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 9
4.4 Meter Display Options
The STT850 temperature Transmitter offers two display options: Basic and Advanced; see
Table 4.
10 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
5. Device Variables
The Device variables are the same as dynamic variables however the units applicable for PV will
apply to TV and QV as well.
6. Dynamic Variables
Four Dynamic Variables are implemented.
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 11
7. Status Information
12 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
7.2 Extended Device Status
The Extended Device Status byte has the following flags:
Device Variable Alert Set when a critical or non-critical error (except “In Fixed
1 Output Current Mode”) associated with the PV has been
detected (see section 7.3).
2-7 Undefined
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 13
Non critical status 2 7 Low Supply Voltage
(Byte 3)
6 No DAC Calibration
5 Tamper Alarm
4 Unreliable sensor communication
3 Loop current noise
2 AO Out of Range
1 URV Set Error - Span Config Button
0 LRV Set Error - Zero Config Button
Non critical status 3 7 Sensor2 input out of range
(Byte 4)
6 Sensor1 input out of range
5 Unused
4 Sensor2 input open
3 Sensor1 input open
2 Sensor over temperature
1 Unused
0 Excess Delta detect
Table 8 Additional Field Device Status
All critical faults will be indicated to the user with bits 4 and 7 set in the Field Device Status byte
of the response.
Some faults are cleared when the error condition is resolved, while all Critical Status faults
require the device be power cycled.
14 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
8. Universal Commands
The transmitter supports version 7.x of the HART protocol and each universal command is as
specified in that standard. The following universal commands are provided by the device:
19 Write Final Assembly Number Writes final assembly number to the device
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 15
Number Name Notes
16 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
9. Common-Practice Commands
9.1 Supported Common Practice Commands
The following common-practice commands are implemented:
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 17
9.2 Burst Mode
This Field Device does not support burst mode..
18 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.Device-Specific Commands
The following device-specific commands are implemented:
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 19
145 Read Previous time and date for correct Reads Calibration records
URV, correct LRV sensor 2 Sensor 2.
146 Read current time and date for correct URV, Reads Calibration records
correct LRV sensor 2 sensor 2.
147 Read current, last and previous reset Reads Calibration records for
correct Time & Date sensor 2 sensor 2 Reset corrects.
148 Read power fail counter and its timestamp The power fail count and Time
stamp are read.
149 Read Electronics Temperature and upper Electronics Temperature
tracking parameters value maximum tracking parameters.
150 Read Electronics Temperature lower Electronics Temperature
tracking parameters value minimum tracking parameters.
151 Read CVD1 User Cal values Reads Read CVD1 values.
152 Read CVD2 User Cal values Reads Read CVD 2 values.
153 Read Configuration History sequence and Read configuration database ID
database ID
154 Read Configuration history data Read configuration history
record data
Read current and min operating voltage and Reads operating voltage and
155
its timestamp minimum Time stamp.
Reset min terminal voltage and its time It resets the Operating Voltage
156
stamp records.
Read M360 core temperature up tracking
157 Reads M360 temp up tracking.
parameters
Read M360 core temperature down tracking Reads M360 temp down
158
parameters tracking.
Read AVDD records and Time
159 Read AVDD max and time stamp
stamp.
Read AVDD records and Time
160 Read AVDD min and time stamp
stamp.
Reads sensor1, sensor2 and
161 Read sensors and transmitter install dates
transmitter installed date.
Read sensor board stress monitor and Reads sensor board Stress and
162
sensor board service life service life.
Writes transmitter install date to
163 Write install date to sensor
sensor. One time writable.
Reads Table IV information. For
164 Read Model Number –Table IV
factory use.
Read Previous time and date for correct Reads Calibration records
165
URV, correct LRV sensor 1 Sensor 1.
Read current time and date for correct URV, Reads Calibration records
166
correct LRV sensor 1 sensor 1.
20 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
Read current, last and previous reset Reads Calibration records for
167
correct Time & Date sensor 1 sensor 1 Reset corrects.
Read differential PV Down tracking
168 Reads PV down tracking.
parameters
Configures the senor1 bias
173 Sensor1 Bias value
value
Configures the senor2 bias
174 Sensor2 Bias value
value
175 Read/Lock Write Protect Configuration Soft Write protection
Enables to view the last 5
178 Read last 5 Configuration history
configuration history.
179 Read UTL1, LTL1, UTL2 Reads the respective values
185 Read LTL2, CJ-UTL, CJ-LTL Reads the respective values
Reads Sensor1, sensor2,
186 Read all sensor times in service
transmitter time in Service.
It reads Communication board
187 Read f/w revision
firmware rev. number.
Read the loop control mode, loop controlling
188 sensor, hysteresis value, Damping for Reads the respective values
bump-less transfer
Configures the loop operation
189 Write the loop control Mode
mode
Configures the types and Id’s of
191 Write Sensor 1 & 2 type & Id
sensor 1 and sensor 2
Configures PV high and low
192 Write PV high and low alarm limits alarm limits needed for PV
tracking
Configures the sensor 1 RTD
193 Write RTD1 type
type
Configures the sensor 2 RTD
194 Write RTD2 type
type
Configures the cold junction
197 Write CJ compensation type
compensation state
Configures the break detect
198 Write Break detect
status
Configures the Mid-range value
199 Write MRV
used in split range mode
200 Write Latching Configures latching status
201 Write match PV’s Configures PV matching status
Configures the Cold Junction
202 Write fixed CJ compensation
compensation value
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 21
Configures the sensor 2 RTD
203 Write RTD1 lead wire resistance
resistance
Configures the sensor 2 RTD
204 Write RTD2 lead wire resistance
resistance
Writes Displays common
210 Write Display Common Configuration features like Rotation time
and Contrast.
211 Read Display Common Setup Reads the display set-up.
Reads Display Firmware
212 Read Display Firmware Version
Version.
213 Read Error log Part 1 Reads the latest 5 errors
214 Read Error log Part 2 Reads the oldest 5 errors
215 Reset Error Log Resets the errors logged
Reads the error logging
216 Read Error Logging Status
status
Configures the error logging
217 Write Error Logging Status
status
Read Highest Value, Lowest Value, Time
218 stamp, High alarm limit, Low alarm limit, Reads the PV tracking values
Counters for PV
219 Read SV up racking values Reads SV up racking values
It reads the Device status in
220 Read additional status
Detail.
Before Calibration it is
221 Set Date/Time for calibration compulsory to enter the Time
and Date.
Reads Sensor Firmware
222 Sensor f/w read
version
Read the delta limit value,
223 Read delta limit, delta, excess delta detection delta value and excess delta
detection status
Configures the delta limit
224 Write delta limit
value
Configures the excess delta
225 Write excess delta detection
detection status
Configures the hysteresis
226 Write hysteresis value
value
Configures the bump less
227 Write Damping for bump-less transfer
damping value
Read the state of “Available for maintenance” Reads the status of “Available
228
flag for Maintenance” Flag
229 Enable “Available for maintenance” message Enables the flag.
22 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
Reads the tamper
230 Read the Tamper configuration
configuration
Writes the tamper
231 Write tamper configuration
configuration.
It resets the Tamper attempts
232 Reset recorded tamper attempts
recorded.
Resets the PV tracking
240 Reset PV Tracking values
values.
Reads SV down racking
247 Read SV down racking values
values
Writes display screen
64768 Write View configuration I
configuration part 1
Writes display screen
64769 Write View configuration II
configuration part 2
Writes display screen
64770 Write View configuration III
configuration part 3
Reads display screen
64771 Read View configuration I
configuration part 1
Reads display screen
64772 Read View configuration II
configuration part 2
Reads display screen
64773 Read View configuration III
configuration part 3
64774 Write CVD1 4 Coefficients Write R0, α, δ, β
64775 Write CVD2 4 Coefficients Write R0, α, δ, β
64776 Write DO Alarm1 Type
64777 Write DO Alarm2 Type
64778 Write DO Set Point1
64779 Write DO Set Point2
64780 Write DO Alarm Hysteresis
64781 Write DO Alarm Latch
64782 Write DO Alarm Block
64783 Write DO Deviation Value
64786 Read CVD1 4 Coefficients Read R0, α, δ, β
64787 Read CVD2 4 Coefficients Read R0, α, δ, β
Sensor1 upper calibration
64790 Write upper calibration point sensor1
point write
Sensor1 lower calibration
64791 Write lower calibration point sensor1
point write
Sensor2 upper calibration
64792 Write upper calibration point sensor2
point write
Sensor2 lower calibration
64793 Write lower calibration point sensor2
point write
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 23
Read sensor1 calibration
64794 Read calibration points sensor 1
points
Read sensor2 calibration
64795 Read calibration points sensor 2
points
Read DO Alarm Type1,
Type2, Set point 1 and Set
point 2,
64796 Read DO parameters DO_alarm_hysteresis,
DO_alarm_latch,
DO_alarm_block,
DO_deviation_value
Read CVD 1 coefficient
64802 Read CVD1 Coefficient activation
activation
Read CVD 2 coefficient
64803 Read CVD 2 coefficient activation
activation
write CVD 1 coefficient
64804 Write CVD1 Coefficient activation
activation
64805 Write CVD 2 Activation Write CVD 3 activation value
Read sensor electronics
64807 Read sensor ET up tracking values temperature up tracking
values
Read sensor electronics
64808 Read sensor ET down tracking values temperature down tracking
values
Read SHM1 ohms, SHM2
Read SHM1 ohms, SHM2 ohms, M360 Core
64809 ohms, M360 Core Temp
Temp Delta
Delta
64811 Write Sensor1 install date
64812 Write Sensor 2 install date
Reset Cold Junction
64813 Reset CJ Tracking values
temperature tracking values
Acknowledge the sensor
64814 Acknowledge Latching
errors
64815 Write 32 byte sensor scratch pad
Reads the sensor scratch pad
64816 Read Sensor scratch pad data
data
Write command for NAMUR enable and
64817
disable
Reads whether NAMUR is
64818 Read NAMUR status
enabled or disabled
64822 Read Sensor 1 and Sensor 2 resistance
64774 Write CVD1 4 Coefficients Write R0, α, δ, β
64775 Write CVD2 4 Coefficients Write R0, α, δ, β
24 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
64776 Write DO Alarm1 Type
64777 Write DO Alarm2 Type
64778 Write DO Set Point1
64779 Write DO Set Point2
64780 Write DO Alarm Hysteresis
64781 Write DO Alarm Latch
64782 Write DO Alarm Block
64783 Write DO Deviation Value
64786 Read CVD1 4 Coefficients Read R0, α, δ, β
64787 Read CVD2 4 Coefficients Read R0, α, δ, β
Sensor1 upper calibration
64790 Write upper calibration point sensor1
point write
Sensor1 lower calibration
64791 Write lower calibration point sensor1
point write
Sensor2 upper calibration
64792 Write upper calibration point sensor2
point write
Sensor2 lower calibration
64793 Write lower calibration point sensor2
point write
Read sensor1 calibration
64794 Read calibration points sensor 1
points
Read sensor2 calibration
64795 Read calibration points sensor 2
points
Read DO Alarm Type1,
Type2, Set point 1 and Set
point 2,
64796 Read DO parameters DO_alarm_hysteresis,
DO_alarm_latch,
DO_alarm_block,
DO_deviation_value
Read CVD 1 coefficient
64802 Read CVD1 Coefficient activation
activation
Read CVD 2 coefficient
64803 Read CVD 2 coefficient activation
activation
write CVD 1 coefficient
64804 Write CVD1 Coefficient activation
activation
64805 Write CVD 2 Activation Write CVD 3 activation value
Read sensor electronics
64807 Read sensor ET up tracking values temperature up tracking
values
Read sensor electronics
64808 Read sensor ET down tracking values temperature down tracking
values
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 25
Read SHM1 ohms, SHM2
Read SHM1 ohms, SHM2 ohms, M360 Core
64809 ohms, M360 Core Temp
Temp Delta
Delta
64811 Write Sensor1 install date
64812 Write Sensor 2 install date
Reset Cold Junction
64813 Reset CJ Tracking values
temperature tracking values
Acknowledge the sensor
64814 Acknowledge Latching
errors
64815 Write 32 byte sensor scratch pad
Reads the sensor scratch pad
64816 Read Sensor scratch pad data
data
Write command for NAMUR enable and
64817
disable
Reads whether NAMUR is
64818 Read NAMUR status
enabled or disabled
64822 Read Sensor 1 and Sensor 2 resistance
Table 11 Device Specific Commands
Each device specific command is detailed below. Only the supported response codes are listed
for a command.
26 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.1 Command #128: Correct Sensor 2 Input to URV
This command performs a calibration trim for the sensor2. The calibration temperature applied to the
transmitter is received with this command and the transmitter trims the sensor2 calibration so that its
output equals the applied value.
None
None
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 27
10.2 Command #129: Correct Sensor 2 Input to LRV
This command performs a calibration trim for the sensor2. The calibration temperature applied to the
transmitter is received with this command and the PV is calibrated to the applied LRV input.
None
None
32 Error Busy
28 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.3 Command #130: Correct Sensor 1 Input to URV
This command performs a calibration trim for the sensor1. The calibration temperature applied to the
transmitter is received with this command and the transmitter trims the sensor1 calibration so that its
output equals the applied value.
None
None
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 29
10.4 Command #131: Correct Sensor 1 Input to LRV
This command performs a calibration trim for the sensor1. The calibration temperature
applied to the transmitter is received with this command and the PV is calibrated to the
applied LRV input.
None
None
32 Error Busy
30 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.5 Command #132: Reset Corrects sensor 2
This command removes the calibration of sensor 2 and returns the performance to factory
calibration. This function is useful as a diagnostic tool to get an indication of characterization
performance.
None
None
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 31
10.6 Command #133: Reset Corrects sensor 1
This command removes the calibration of sensor 1and returns the performance to factory
calibration. This function is useful as a diagnostic tool to get an indication of characterization
performance.
None
None
32 Error Busy
32 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.7 Command #134: Read Transmitter Specifics
The command reads the device type code and display module information.
The Device type code for STT800 SmartLine Temperature Transmitter is 0x22.
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 33
10.8 Command #135: Read sensors extra configuration
The command is used to read configurable sensor parameters common to both sensors.
By default sensors will be in mV and the UTL is 125mV and LTL is -20mV and MRV is
70mV.
Break Detect status is OFF by default.
ON: 01
OFF: 00
Cold Junction Compensation Type:
Internal: 00
External: 01
Fixed: 02
Match PV Status:
ON: 01
OFF: 00
Latching Status:
ON: 01
OFF: 00
Fixed Cold Junction Compensation value is 0 by default
None
34 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.9 Command #136: Read sensor1 configuration
This command reads the sensor 1 configuration parameters. This command reads Sensor1
Type, Sensor1 Id, RTD1 Type, RTD1 lead wire resistance, Sensor1 bias value.
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 35
10.10 Command #137: Read sensor2 configuration
This command reads the sensor2 configuration parameters. This command reads Sensor2
Type, Sensor2 Id, RTD2 Type, RTD2 lead wire resistance, Sensor2 bias value.
None
36 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.11 Command #138: Read URL1, LRL1
The command reads range limits of sensor 1.
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 37
10.12 Command #139: Read Model Number – Key Number, Table I
This command reads the 7 byte key number and 20 byte Table 1 information.
None
38 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.13 Command #140: Read Model Number – Table II
This command reads Model number Table II information.
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 39
10.14 Command #141: Read Model Number –Table III
This command reads Model number Table III information.
None
40 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.15 Command #142: Read time in service, percent time in stress,
service life remaining
This command reads time in service, percent time in stress, service life remaining for the
transmitter.
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 41
10.16 Command #143: Read last Time & Date for correct URV,
correct LRV for sensor 2
This command reads Last Time and Dates for correct URV, correct LRV of sensor 2
None
42 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.17 Command #144: Read last Time & Date for correct URV,
correct LRV for Sensor 1
This command reads Last Time and Dates for correct URV, correct LRV of sensor 1
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 43
10.18 Command #145: Read Previous Time & Date for correct URV,
correct LRV for sensor 2
This command reads Previous Time and Dates for correct URV, correct LRV for sensor 2
None
44 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.19 Command #146: Read current Time & Date for correct URV,
correct LRV sensor 2
This command reads Current Time and Dates for correct URV, correct LRV for sensor 2
None
Response Data Bytes
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 45
10.20 Command #147: Read current, last and previous reset
correct Time & Date sensor 2
This command reads the current, last and previous reset correct T&D for sensor 2
None
Response Data Bytes
46 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.21 Command #148: Read power fail counter and its timestamp
This command reads Power fail count & its time stamp. Timestamp is in seconds.
Note: Power Fail Count value is in seconds and provides the time for which device is on before power
cycle or reset.
None
Response Data Bytes
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 47
10.22 Command #149: Read ET and electronics temperature
tracking values.
This command reads ET value, ET max limit, ET max value, Max time counter, max time stamp (In
seconds) .
None
48 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.23 Command #150: Read ET lower tracking parameters
This command reads ET min limit, min value, min time counter, min time stamp (In seconds).
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 49
10.24 Command #151: Read CVD1 User Cal values
This command reads CVD1 user calibration values.
None
50 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.25 Command #152: Read CVD2 User Cal values
This command reads CVD2 user calibration values.
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 51
10.26 Command #153: Read Configuration History sequence and
database ID
This command provides a Database ID for the requested configuration history code.
0 Enum Sequence ID
(01 :- This is request byte to read latest parameter)
02:- (This is request byte to read second last parameter written)
03:- (This is request byte to read third last parameter written)
04:- (This is request byte to read forth last parameter written)
05:- (This is request byte to read fifth last parameter written) )
0 Enum Sequence ID
(01 :- This is request byte to read latest parameter)
02:- (This is request byte to read second last parameter written)
03:- (This is request byte to read third last parameter written)
04:- (This is request byte to read forth last parameter written)
05:- (This is request byte to read fifth last parameter written) )
Database Id’s:
1. NVM database version - 0
2. Hart/DE selection -1
3. Crc of common data block - 2
4. Conformity - 3
5. Loop current 4mA - 4
6. Loop current 20mA - 5
7. Damping - 6
8. Polling address & Loop Current Mode - 7
9. Namur - 8
10. Pv Units - 9
52 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
11. Sv Units - 10
12. Device number identifier - 11
13. User break point -12
14. Cutoff method - 13
15. Lock device configuration - 14
16. Final assembly number - 15
17. Software write protect - 16
18. User password -17
19. Master password -18
20. Tag, descriptor & date -19
21. Tag -20
22. Message -21
23. Message1 -22
24. Message2 - 23
25. Message3 - 24
26. Message4 - 25
27. Long tag - 26
28. Basic database MX - 27
29. Extended database UT - 28
30. Digital database byte1 -29
31. Broadcast selection - 30
32. Tamper mode configuration - 31
33. Hysteresis band -32
34. Damping for bump less transfer -33
35. Loop control mode, Excess delta detect status, URV, LRV, MRV, Delta Limit-34
36. Excess delta detect status - 35
37. Delta limit -36
38. Error logging status -37
39. URV, LRV, MRV, Delta Limit -38
40. MRV - 39
41. Loop current mode - 40
42. Polling address - 41
43. Date - 42
44. High and Low Alarm Limits – 43
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 53
10.27 Command #154: Read Configuration history data
This command provides a history of the last 5 Configuration changes.
2-34 Enum Value of the parameter for which we have made request
We will get number of byte= size of parameter
Eg, If PV unit is of size 2 byte so we will get 2 byte rest 3-33 bytes will be
garbage.
Rest bytes will be garbage data
When no record is present, it will return 32 garbage bytes.
54 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.28 Command #155: Read current, minimum operating voltage
and its timestamp
This command reads Loop Voltage Current value, Loop Voltage min value, Loop Voltage min time
stamp,
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 55
10.29 Command #156: Reset min terminal voltage and its time
stamp
This command Resets min terminal voltage and its time stamp.
None
None
32 Error Busy
56 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.30 Command #157: Read M360 core temperature up tracking
parameters
This command reads the M360 (Sensor’s Microprocessor) core temperature up tracking
parameters.
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 57
10.31 Command #158: Read M360 core temperature down tracking
parameters
This command reads the M360 core temperature down tracking parameters.
None
58 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.32 Command #159: Read AVDD max and time stamp
This command reads the AVDD max and time stamp.
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 59
10.33 Command #160: Read AVDD min and time stamp
This command reads the AVDD min and time stamp.
None
60 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.34 Command #161: Read sensors and transmitter install dates
This command reads the senor install dates.
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 61
10.35 Command #162: Read sensor board stress monitor and
sensor board service life
This command reads the sensor stress monitor and sensor service life.
None
62 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.36 Command #163: Write transmitter install date to sensor
This command writes transmitter install date to sensor.
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 63
10.37 Command #164: Read Model Number –Table IV
This command reads the 20 byte Model Number –Table IV
None
64 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.38 Command #165: Read Previous Time & Date for correct URV,
correct LRV sensor 1
This command reads Previous Time and Dates for correct URV, correct LRV for sensor 1
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 65
10.39 Command #166: Read current Time & Date for correct URV,
correct LRV sensor 1
This command reads Current Time and Dates for correct URV, correct LRV For sensor 1.
None
66 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.40 Command #167: Read current, last and previous reset
correct Time & Date sensor 1
This command reads the current, last and previous reset correct T&D for sensor 1
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 67
10.41 Command #168: Read URL2, LRL2
The commands read the range limits of sensor 2
None
68 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.42 Command #173: Write sensor1 bias value
This command configures the sensor1 bias value
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 69
10.43 Command #174: Write sensor2 bias value
This command configures the sensor1 bias value
32 Error Busy
70 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.44 Command #175: Read/Lock Write Protect Configuration
This command reads or Locks Write Protect Configuration based on selection.
0x01 – Enabled
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 71
10.45 Command #176: Write/Change Write Protect Password
This command is used to Write/Change Write Protect Password.
5-8 ASCII Current password (field valid only for password change command)
32 Error Busy
72 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.46 Command #179: Read UTL1, LTL1, UTL2
The command reads the transducer limits sensor1 upper limit, sensor1 lower limit, sensor
2 upper limit
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 73
10.47 Command #185: Read LTL2, CJ-UTL, CJ-LL
The command reads the transducer limits sensor2 lower limit and cold junction upper and
lower limits.
None
74 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.48 Command #186: Read all sensor times in service
This command reads the Sensor Times in Service.
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 75
10.49 Command #187: Read HART-DE board firmware revision
This command reads the HART-DE board firmware revision.
None
76 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.50 Command #188: Read the loop control mode, loop controlling
sensor, hysteresis value, Damping for bump-less transfer
Reads the HART communication board parameters loop control mode, loop controlling
sensor, hysteresis value, Damping for bump-less transfer
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 77
10.51 Command #189: Write Loop control mode
This command configures the loop control mode.
32 Error Busy
78 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.52 Command #191: Write sensor1 type
This command configures the types and Id’s of sensor1 and sensor2.
1 Enum Sensor 1 Id
(if sensor1 type is MV then
0 = MV,
1 = MV1,
if sensor1 type is TC then
0 = TC Type E,
1 = TC Type J,
2 = TC Type K,
3 = TC Type N,
4 = TC Type T,
5 = TC Type S,
6 = TC Type R,
7 = TC Type B,
8 = TC Type C(w5w26),
if sensor1 type is RTD then
0 = RTD Pt 25,
1 = RTD Pt 100,
2 = RTD Pt 200,
3 = RTD Pt 500,
4 = RTD Pt 1000,
5 = RTD Ni 120,
6 = RTD Cu 10,
if sensor1 type is OHMS then
0 = OHM 500,
1 = OHM 2K,
2 = OHM 3K)
2 Enum Sensor 2 type
(0 = MV,
1 = TC,
2 = RTD,
3 = OHMS)
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 79
3 Enum Sensor 2 Id
(if sensor2 type is MV then
0 = MV,
1 = MV1,
if sensor2 type is TC then
0 = TC Type E,
1 = TC Type J,
2 = TC Type K,
3 = TC Type N,
4 = TC Type T,
5 = TC Type S,
6 = TC Type R,
7 = TC Type B,
8 = TC Type C(w5w26),
if sensor2 type is RTD then
0 = RTD Pt 25,
1 = RTD Pt 100,
2 = RTD Pt 200,
3 = RTD Pt 500,
4 = RTD Pt 1000,
5 = RTD Ni 120 ,
6 = RTD Cu 10 ,
if sensor2 type is OHMS then
0 = OHM 500,
1 = OHM 2K,
2 = OHM 3K)
1 Enum Sensor 1 Id
3 Enum Sensor 2 Id
32 Error Busy
80 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.53 Command #192: Write PV high and low alarm limits
This command configures the PV high and low alarm limits.
For mV type if URV is 120 and LRV is -20 then High limit is 106mV
For mV type if URV is 120 and LRV is -20 then Low limit is -6mV
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 81
10.54 Command #193: Write RTD1 type
This command configures the sensor1 RTD type and by default it will be 3wire.
32 Error Busy
82 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.55 Command #194: Write RTD2 type
This command configures the sensor2 RTD type and by default it will be 3wire.
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 83
10.56 Command #197: Write CJ compensation type
This command configures the Cold Junction compensation type and by default it will be internal.
0x01 = External,
0x02 = Fixed)
0x01 = External,
0x02 = Fixed)
32 Error Busy
84 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.57 Command #198: Write break detect status
This command configures the break detection status and by default it is OFF.
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 85
10.58 Command #199: Write Mid Range Value((MRV)
This command configures the Mid range value, this value is used for split range loop control
mode.
32 Error Busy
86 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.59 Command #200: Write latching status
This command configures the sensor information bits latching status and by default it is OFF.
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 87
10.60 Command #201: Write match PV status
This command configures the PV matching status.
32 Error Busy
88 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.61 Command #202: Write fixed CJ compensation
This command configures the fixed cold junction compensation.
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 89
10.62 Command #203: Write RTD1 lead wire resistance
This command configures the sensor1 lead wire resistance.
32 Error Busy
90 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.63 Command #204: Write RTD2 lead wire resistance
This command configures the sensor2 lead wire resistance.
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 91
10.64 Command #210: Write Display General configuration
This command writes the following General Local Display Configuration parameters.
Language, Sequence Time, Screen Rotation Selection, display password and LCD contrast.
If the advanced display loaded is of western version package then below list is valid.
• Language:
• English-0,
• French-1,
• German-2,
• Spanish-3,
• Russian-4,
• Turkish-7,
• Itaian-8
If the advanced display loaded is of Eastern version package then below list is valid.
• English-0,
• Chinese-5,
• Japanese-6
• 0x00: Disable
• 0x01: Enable
0 Enum Language
92 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
Response Data Bytes:
0 Enum Language
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 93
10.65 Command #211: Read Display General configuration
This command reads the Display General Configuration.
If the advanced display loaded is of western version package then below list is valid.
• Language:
• English-0,
• French-1,
• German-2,
• Spanish-3,
• Russian-4,
• Turkish-7,
• Itaian-8
If the advanced display loaded is of Eastern version package then below list is valid.
• English-0,
• Chinese-5,
• Japanese-6
• 0x00: Disable
• 0x01: Enable
None
0 Enum Language
94 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
Command-Specific Response Codes
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 95
10.66 Command #212: Read Display Firmware Version
This command reads the Display Firmware Version.
None
96 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.67 Command #213: Read error log part1
This command reads the 5 latest errors information.
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 97
10.68 Command #214: Read error log part2
This command reads the 5 oldest errors information.
None
98 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.69 Command #215: Reset error log
This command initializes the error log data to zeros.
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 99
10.70 Command #216: Read error logging status
This command reads the error logging status.
None
100 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.71 Command #217: Write error logging status
This command configures the error logging status.
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 101
10.72 Command #218: Read PV tracking values
This command reads Primary Variable tracking values.
None
102 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.73 Command #219: Read SV up tracking values
This command reads Secondary variable up tracking values.
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 103
10.74 Command #220: Read additional status
This command reads the additional Status.
None
104 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.75 Command #221: Set Date/Time for calibration
This command is used to Set Date/Time for calibration.
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 105
10.76 Command #222: Read sensor firmware version number
This command reads the sensor Firmware revision number.
None
106 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.77 Command #223: Read delta limit, delta, excess delta
detection
This command reads delta limit, delta, and excess delta detection.
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 107
10.78 Command #224: Write delta limit
This command configures the delta limit.
32 Error Busy
108 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.79 Command #225: Write excess delta detection
This command configures excess delta detection status
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 109
10.80 Command #226: Write hysteresis value
This command configures the hysteresis value.
32 Error Busy
110 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.81 Command #227: Write damping for bump less transfer
This command configures the damping for bump less transfer value.
Limit/Range for damping for bump less transfer is 0.00 to 99.9 sec
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 111
10.82 Command #228: Read maintenance flag
This command reads the maintenance flag.
None
112 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.83 Command #230: Read tamper alarm settings
This command reads tamper alarm settings.
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 113
10.84 Command #231: Write Tamper alarm settings
This command writes Tamper alarm settings.
32 Error Busy
114 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.85 Command #232: Reset executed attempts counter
This command resets the tamper attempt count.
None
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 115
10.86 Command #240: Reset PV tracking values
This command initializes the PV tracking values.
116 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.87 Command #247: Read SV down tracking values
This command reads Secondary variable down tracking values.
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 117
10.88 Command #64768: Write Display Screen configuration I
This command writes part 1 of screen configuration.
118 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
2 Enum Screen Selection
screen 1:-Hex 3E
screen 2:-Hex 3F
screen 3:-Hex 40
screen 4:-Hex 41
screen 5:-Hex 42
screen 6:-Hex 43
screen 7:-Hex 44
screen 8:-Hex 45
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 119
10.89 Command #64769: Write Display View configuration II
This command writes part 2 of screen configuration.
32 Error Busy
120 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.90 Command #64770: Write View configuration III
This command writes part 3 of screen configuration.
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 121
10.91 Command #64771: Read Display View configuration I
This command reads view configuration I.
8-9 enum Trend duration, Duration of a trend screen in hours. Valid range 1 – 999
122 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
Command-Specific Response Codes
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 123
10.92 Command #64772: Read Display View configuration II
This command reads the View configuration II
124 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.93 Command #64773: Read Display View configuration III
This command reads the View configuration III.
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 125
10.94 Command #64774: Write CVD1 4 Coefficients
This command writes the Sensor CVD1 coefficients 1 to 4 (R0, α, δ, β).
32 Error Busy
126 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.95 Command #64775: Write CVD2 4 Coefficients
This command writes the Sensor CVD2 coefficients 1 to 4 (R0, α, δ, β).
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 127
10.96 Command #64776: Write DO Alarm1 Type
This command writes the DO Alarm1 Type.
32 Error Busy
128 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.97 Command #64777: Write DO Alarm2 Type
This command writes the DO Alarm2 Type.
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 129
10.98 Command #64778: Write DO Setpoint1
This command writes the DO Setpoint1.
Range for DO Setpoint1 for PV high and Low alarm limit is -999.9f to +9999.9f
Range for DO Setpoint1 for DO Rate of change and deviation alarm is -100 to +100
32 Error Busy
130 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.99 Command #64779: Write DO Setpoint2
This command writes the DO Setpoint2.
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 131
10.100 Command #64780: Write DO Alarm Hysteresis
This command writes the DO Alarm Hysteresis.
32 Error Busy
132 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.101 Command #64781: Write DO Alarm Latch
This command writes the DO Alarm Latch.
Disable – 0
Enable – 1
Clear - 2
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 133
10.102 Command #64782: Write DO Alarm Block
This command writes the DO Alarm Block.
OFF – 0
ON – 1
32 Error Busy
134 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.103 Command #64783: Write DO Deviation Value
This command writes DO Deviation Value.
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 135
10.104 Command #64786: Read CVD1 co-efficient Values:
This command Reads CVD1 co-efficient values.
None
136 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.105 Command #64787: Read CVD2 co-efficient Values:
This command Reads CVD2 co-efficient values.
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 137
10.106 Command #64790: Write upper calibration point sensor1
This command configures the sensor1 upper calibration value.
32 Error Busy
138 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.107 Command #64791: Write lower calibration point sensor1
This command configures the sensor1 lower calibration value.
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 139
10.108 Command #64792: Write upper calibration point sensor2
This command configures the sensor2 upper calibration value.
32 Error Busy
140 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.109 Command #64793: Write lower calibration point sensor2
This command configures the sensor2 lower calibration value.
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 141
10.110 Command #64794: Read calibration points sensor1
This command reads the sensor1 calibration values.
142 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.111 Command #64795: Read calibration points sensor2
This command reads the sensor2 calibration values.
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 143
10.112 Command #64796: Read DO Values:
This command Reads DO Values.
None
144 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.113 Command #64802: Read CVD1 Coefficient activation:
This command Reads CVD1 Coefficient activation.
None
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 145
10.114 Command #64803: Read CVD2 Coefficient activation:
This command Reads CVD2 Coefficient activation.
None
146 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.115 Command #64804: Write CVD1 Coefficient activation
This command writes the Sensor CVD Activation of CVD1.
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 147
10.116 Command #64805: Write CVD2 Coefficient activation
This command writes the Sensor CVD Activation of CVD2.
32 Error Busy
148 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.117 Command #64806: Write sensor base resistance
This command writes the sensor base resistance.
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 149
10.118 Command #64807: Read sensor ET up tracking values
This command reads the sensor ET up tracking values.
150 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.119 Command #64808: Read sensor ET down tracking values
This command reads the sensor ET down tracking values.
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 151
10.120 Command #64809: Read M360 Core Temp Delta
This command reads the sensor advanced diagnostic parameters shm1 ohms, shm2 ohms and
M360 core temperature delta value
152 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.121 Command #64811: Write Sensor1 install date
This command is used to write the sensor1 install date.
2 Unsigned-8 Day
3 Unsigned-8 Month
4 Unsigned-8 Year
2 Unsigned-8 Day
3 Unsigned-8 Month
4 Unsigned-8 Year
5 Unsigned-8 Hour
6 Unsigned-8 Minute
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 153
10.122 Command #64812: Write Sensor2 install date
This command is used to write the sensor2 install date.
2 Unsigned-8 Day
3 Unsigned-8 Month
4 Unsigned-8 Year
2 Unsigned-8 Day
3 Unsigned-8 Month
4 Unsigned-8 Year
5 Unsigned-8 Hour
6 Unsigned-8 Minute
154 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.123 Command #64813: Reset CJ tracking parameters
This command is used to reset the cold junction (SV) tracking parameters.
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 155
10.124 Command #64814: Acknowledge latching
This command is used to acknowledge sensor errors.
32 Error Busy
156 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.125 Command #64815: Write Sensor Scratch pad
This command is used to write sensor scratch data.
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 157
10.126 Command #64816: Read Sensor Scratch pad
This command is used to read sensor scratch data
158 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.127 Command #64817: Write NAMUR Selection
This command is used to write NAMUR enable or disable.
32 Error Busy
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 159
10.128 Command #64818: Read NAMUR Selection
This command is used to read NAMUR selection.
160 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
10.129 Command #64822: Read Sensor 1 and Sensor 2 resistance
This command is used to Read Sensor 1 and Sensor 2 resistance for TC and RTD types
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 161
11.Table Unit Codes
2 Degrees Fahrenheit 33
3 Degrees Rankin 34
4 Kelvin 35
5 Milli Volt 36
6 Ohms 37
7 Percent 57
Temperature Units
Internally, the transmitter uses degrees Celsius for the temperature variable. Conversions to
the other supported units are made using the following equations:
Kelvin TK = TC + 273.15
Table 13 Temperature Units
162 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
11.2 Command 220 details
Type Bit Command 220 bit status
DAC Failure 7 SPI Failure
(HART/DE) 6 Packet Error
(BYTE1) 5 Over Current Status
4 Under Current Status
3 Temp Above 140C
2 Temp Above 100C
1 Unused
0 Unused
Communication 7 Unused
(HART/DE) 6 Unused
(BYTE2) 5 Unused
4 Unused
3 Brownout Status
2 Program Flow Failure
1 ROM Failure
0 RAM Failure
Display 7 Sensor Input 2, terminal 7 opened
(HART/DE) 6 Sensor Input 1, terminal 7 opened.
(BYTE3)
5 Sensor Input 2, terminal 9 opened.
4 Sensor Input 2, terminal 8 opened.
3 Sensor Input 1, terminal 6 opened.
2 Display Configuration Data Corrupt.
1 Display Communication Timeout.
0 Sensor Input 1, terminal 5 opened.
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 163
Sensor 7 Sensor2 input fault
(BYTE6)
6 Sensor1 input fault
5 SV Bad
4 QV Bad
3 TV Bad
2 User corrects activated
1 Sensor2 Excess cal Correction
0 Sensor1 Excess cal Correction
Database Integrity 7 Unused
(BYTE7) 6 Display Common Config DB corrupt
5 Display View Config DB corrupt
4 Adv Diag DB corrupt
3 Config Change DB corrupt
2 General Config DB corrupt
1 Vital Config DB corrupt
0 Common DB corrupt
164 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
11.3 Sensor Type Codes
0 MV125
1 MV1200
2 Thermocouple Type E
3 Thermocouple Type J
4 Thermocouple Type K
5 Thermocouple Type N
6 Thermocouple Type T
7 Thermocouple Type S
8 Thermocouple Type R
9 Thermocouple Type B
11 RTD Pt 25
12 RTD Pt 100
13 RTD Pt 200
14 RTD Pt 500
15 RTD Pt 1000
16 OHM 500
17 OHM 2K
18 OHM 3K
19 RTD Ni 120
20 RTD Cu 10
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 165
12.Performance
12.2 Power-Up
On power up, the transmitter initializes the data in RAM and the HART communication links and
starts the task scheduler to sample the input.
The device will not respond to HART commands during the Power Up sequence.
Fixed-current mode is cancelled by power loss or software reset (command 42, for instance).
In very short succession after power is applied to the transmitter, the device will set its output to the
user-selected burnout level, then briefly transition to 50% (12 mA nominal), and then begin
publishing the primary variable.
166 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
12.5 Command Response Times
Minimum 18.236ms
Typical 64ms
Maximum 208.643ms
Table 17 Response Times
BUSY Response code is implemented for the commands, where NVM writing is
involved. Each time when the NVM write command comes, first it is checked if the
device is busy in writing NVM in background, when some configuration is done from
display OR long string parameters like tag/date/descriptor, Long tag, Message from
previous HART command, in the background task.
a. If device is busy in writing long string parameters then the device issues RC-32
to the HART command and completes the NVM write activity in hand in the
command itself using its response time of 250ms. As device sends RC-32 to the
HART command, the host is expected to send the same command again until it
gets a success response code or till the limited number of retries as decided by
host in case of BUSY RC.
b. If the NVM write background task is in progress for the parameters configured
from display, the device sends BUSY RC to the host, and keeps on sending
BUSY RC’s to the next coming HART commands until it finishes this background
task of NVM write.
For any IPC command if the Comm PWA is unable to respond in 240mSec as it may
have not received response from sensor/display, for the first time it sends BUSY
response so that host can retry, then if again the Comm PWA is unable to respond in
240mSec then it sends a Device specific error (RC=0x06) to HART host.
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 167
12.9 Modes
Fixed current mode is implemented, using Command 40. This mode is cleared by power loss or
reset. When the device is in fixed current mode, the analog output will not track the input.
12.11 Damping
The damping is available from 0 to 102 seconds in HART.
168 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
Annex A. Capability Checklist
Manufacturer, model and revision Honeywell Intl (23)., STT850, rev.5
Burst mode? No
Write-protection? Yes
Table 18 Capability checklist
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 169
Annex B. Default Configuration
Parameter Default value
Sensor type MV
170 HART® 7.x Field Device Specification for Honeywell STT850 Revision: 2.0
Annex C. Revision History
Document Device DD
Date Description
Revision Revision Revision
14th Feb,
0.2 1 Updated transmitter details
2014
20th August
0.3 5 5.1 Series 2 updates
2020
Revision: 2.0 HART® 7.x Field Device Specification for Honeywell STT850 171
Sales and Service
For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one
of the offices below.
Singapore
Honeywell Pte Ltd.
Phone: +(65) 6580 3278
Fax: +(65) 6445-3033
South Korea
Honeywell Korea Co Ltd
Phone: +(822) 799 6114
Fax: +(822) 792 9015
Process Solutions
Honeywell
2101 City West Blvd
Houston, TX 77042