Professional Documents
Culture Documents
EQRDCodes Print
EQRDCodes Print
ground motion may cause liquefaction or excessive damping, given by expressions below:
total and differential settlements. Such sites should be a) For use in equivalent static method
avoided preferably for locating new structures, and [see Fig. 2(a)]:
should be avoided for locating structures of important
projects. Otherwise, settlements need to be 2.5 0 < T < 0.40 s
investigated, and appropriate methods adopted of For rocky
or hard 1 0.40 s < T < 4.00 s
compaction or stabilization to achieve N values soil sites T
indicated in Note 4 of Table 1. Alternatively, deep pile 0.25 T > 4.00 s
foundations may be adopted and anchored at depths
well below the underlying soil layers, which are likely 2.5 0 < T < 0.55 s
For med-
to liquefy or undergo excessive settlements. Sa 1.36
= ium stiff 0.55 s < T < 4.00 s
Also, marine clay layers and other sensitive clay layers g soil sites T
are known to liquefy, undergo excessive settlements or 0.34 T > 4.00 s
even collapse, owing to low shear strength of the said
2.5 0 < T < 0.67 s
soil; such soils will need special treatment according For soft 1.67
to site condition (see Table 2). 0.67 s < T < 4.00 s
soil sites T
A simplified method is given in Annex F, for evaluation 0.42 T > 4.00 s
of liquefaction potential.
b) For use in response spectrum method
6.4 Design Acceleration Spectrum [see Fig. 2(b)]
6.4.1 For the purpose of determining design seismic 1 + 15T T < 0.10 s
force, the country is classified into four seismic zones
as shown in Fig. 1. For rocky2.5 0.10 s < T < 0.40 s
or hard 1
6.4.2 The design horizontal seismic coefficient Ah for a soil sites 0.40 s < T < 4.00 s
structure shall be determined by: T
0.25 T > 4.00 s
Z Sa 1 + 15T T < 0.10 s
2 g
Ah =
For med- 2.5 0.10 s < T < 0.55 s
R Sa
I
= ium stiff 1.36
g soil sites 0.55 s < T < 4.00 s
where T
Z = seismic zone factor given in Table 3; 0.34 T > 4.00 s
I = importance factor given in IS 1893 (Parts 1 1 + 15T T < 0.10 s
to 5) for the corresponding structures; when 2.5 0.10 s < T < 0.67 s
not specified, the minimum values of I shall For soft
soil sites 1.67
be, T 0.67 s < T < 4.00 s
a) 1.5 for critical and lifeline structures;
0.42 T > 4.00 s
b) 1.2 for business continuity structures; and
6.4.2.1 For determining the correct spectrum to be used
c) 1.0 for the rest. in the estimate of (Sa/g), the type of soil on which the
R = response reduction factor given in IS 1893 structure is placed shall be identified by the
(Parts 1 to 5) for the corresponding classification given in Table 4, as:
structures; and a) Soil type I Rock or hard soils;
Sa
g = design acceleration coefficient for different
b) Soil type II Medium or stiff soils; and
soil types, normalized with peak ground
acceleration, corresponding to natural period c) Soil type III Soft soils.
T of structure (considering soil-structure In Table 4, the value of N to be used shall be the
interaction, if required). It shall be as given weighted average of N of soil layers from the existing
in Parts 1 to 5 of IS 1893 for the corresponding ground level to 30 m below the existing ground level;
structures; when not specified, it shall be here, the N values of individual layers shall be the
taken as that corresponding to 5 percent corrected values.
9
IS 1893 (Part 1) : 2016
∑ (λ )
2
7.7.5.2 Number of modes to be considered λ= k
k =1
The number of modes Nm to be used in the analysis for where
earthquake shaking along a considered direction,
λk = peak response quantity in mode k,
should be such that the sum total of modal masses of
and
these modes considered is at least 90 percent of the
total seismic mass. Nm = number of modes considered.
2) If building has a few closely-spaced
If modes with natural frequencies beyond 33 Hz are to
modes, then net peak response quantity
be considered, the modal combination shall be carried
λ∗ due to these closely space modes alone
out only for modes with natural frequency less than
shall be obtained as:
33 Hz; the effect of modes with natural frequencies more
than 33 Hz shall be included by the missing mass λ * = ∑ λc
correction procedure following established principles c
where
of structural dynamics. If justified by rigorous analysis,
designers may use a cut off frequency other than 33 Hz. λc = peak response quantity in closely
spaced mode c. The summation is
7.7.5.3 Combination of modes for closely spaced modes only.
The responses of different modes considered shall be Then, this peak response quantity
combined by one of the two methods given below: λ∗ due to closely spaced modes is
combined with those of remaining
a) Peak response quantities (for example, member well-separated modes by method
forces, displacements, storey forces, storey described above.
shears, and base reactions) may be combined
7.7.5.4 Simplified method of dynamic analysis of
as per Complete Quadratic Combination (CQC)
buildings
method, as given below:
Regular buildings may be analyzed as a system of
Nm Nm
masses lumped at the floor levels with each mass
λ = ∑∑
i =1 j =1
λ i ρij λ j
having one degree of freedom, that of lateral
displacement in the direction under consideration. In
where such a case, the following expressions shall hold in the
computation of the various quantities:
λ = estimate of peak response quantity;
λi = response quantity in mode i (with sign); a) Modal mass Modal mass Mk of mode k is
given by:
λj = response quantity in mode j (with sign);
ρij = cross-modal correlation co-efficient n
2
∑Wiφik
8 ζ 2 (1 + β ) β1.5 M k = in=1
= ;
g∑Wi (φik )
2
(1 − β )
2 2
+ 4 ζ 2β (1 + β )2 i =1
where
Nm = number of modes considered;
g = acceleration due to gravity,
ζ = modal damping coefficient ratio which
φik = mode shape coefficient at floor i in
shall be taken as 0.05; mode k,
ωj Wi = seismic weight of floor i of the structure,
β = natural frequency ratio = ω ; and
i
24
IS 1893 (Part 1) : 2016
0 96 DAMPING
2 vi
3.4.5 The vertical seismic coefficient where applicable ( see 3.1.5 ) may
be taken as half of the horizontal seismic coefhcient as indicated in 3.4.2.
In important structures where there is a possibility of amplification of ver-
tical seismic coefficient, dynamic analysis is preferable. In that case F,
values in Table 2 should be multiplied by 0.5.
4. BUILDINGS
4.1 Design Live Loads
4.1.1 For various loading classes as specified in IS : 875-1960*, thehori-
zontal earthquake force shall be calculated for the full dead load and the
percentage of live loads as given below:
Load Class Percentage of Design
Live Load
200, 250 and 300 25
400, 500,750 and 1 000 50
18
IS : 1893 - 1984
NOTE - The values of importance factor, Z given in this table are for guidance.
A designer may choose suitable values depending on the importance based on eco-
nomy, strategy and other considerations.
19
IS : 1893 - 1984
4.4.3 For industrial structures and frame structures of large spans and
heights, modal analysis using response spectrum method is recommended.
5. ELEVATED STRUCTURES
5.1 General
5.1.1 The elevated structures covered by these provisions include eleva-
ted tanks, refinery vessels and stacklike structures, such as chimneys of
normal pro.portions. In the case of the elevated structures of unusual
proportions, more detailed studies shall be made.
5.2 Elevated Tower-Supported Tanks
5.2.1 For the purpose of this analysis, elevated tanks shall be regarded
as systems with a single degree of freedom with their mass concentrated
at their centres of gravity.
5.2.2 The damping in the system may be assumed as 2 percent of the
critical for steel structures and 5 percent of the critical for concrete
( including masonry ) structures.
5.2.3 The free period T, in seconds, of such structures shall be
calculated from the following formula:
*Code ofpractice for earthquake resistant design and construction of buildings (Jrsl
revision ) .
28
IS: 1893.1984
where
A = the static horizontal deflection at the top of the tank
under a static horizontal force equal to a WCight W acting
at the centre of gravity of tank. In calculating the period
of steel tanks, the members may be assumed to be pin-
joined with only the tensile members of the bracing
regarded as active in carrying the loads. No pre-tension
shall be assumed in the bracing rods; and
g = acceleration due to gravity.
5.2.4 The design shall be worked out both when the tank is full and
when empty. When empty, the weight W used in the design ( see 5.2.3 )
shall consist of the dead load of the tank and one-third the weight of the
staging. When full, the weight of contents is to be added to the weight
under empty condition.
5.2.5 Using the period T as calculated in 5.2.3 and appropriate damp-
ing, the spectral acceleration shall be read off from the average accelera-
tion spectra given in Fig. 2. The design horizontal seismic coefficient, Q
shall be calculated as in 3.4.2.3 (b).
5.2.6 The lateral force shall be taken equal to:
UbW
where
alI - design horizontal seismic coefficient as given in 5.2.5, and
W = weight as defined in 5.2;4.
Thisforce shall be assumed to be applied at the centre of gravity of
the tank horizontally in the plane in which the snucture is assumed to
oscillate for purposes of carrying out the lateral load analysis.
5.2.7 E?_ydodyrzamic Pressure in Tanks
5.2.7.1 When a tank containing fluid vibrates the fluid exerts im-
pulsive and convective pressures on the tank. The convective pressures
during earthquakes are considerably less in magnitude as compared to
impulsive pressures and its effect is a sloshing of the water surface. For the
purpose of design only the impulsive pressure may be considered.
5.2.7.2 Rectangular container
The pressure at any location x ( see Fig. 6 ) is given by:
29
IS : 1893- 1984
t‘-----” ------j
(
+----
x
21 OR 2R-------4
E LE VAT ION
FIQ. 6 RECTANGULAR AND CIRCULAR WATER TANKS
30
IS :1893 -1984
where
where
5.3.1 Stacklike structures are those in which the mass and stiffness is
more or less uniformly distributed along the height. Cantilever structures
like chimneys and refinery vessels are examples of such structures
( see Note).
NOTE - Such structures will not include structures like bins, hyperbolic cool-
ing towers, refinery columns resting on frames or skirts. Modal analysis will be
necessary in such cases.
31