HVAC
1. THE HEAT LOAD CALCULATIONS ARE PERFORMED ON HAP SOFTWARE AS PER DESIGN CRITERIA
PROVIDED IN THE EMPLOYER’S REQUIREMENT
2. ALL THE AC EQUIPMENT TO PROVIDE HEAT AND COOL OPERATION
3. THE SELECTION OF THE EQUIPMENT TO BE DONE ON T3 CONDITIONS AND ARE CAPABLE OF
WORKING AT HIGH TEMPERATURE
4. THE REFRIGERANT PIPE SIZES TO BE AS PER THE MANUFACTURER'S RECOMMENDATIONS
5. THE PIPE INSULATION THICKNESS TO BE A MINIMUM 13 MM AND AS PER THE APPROVED
MATERIAL
6. THE CONDENSATE DRAIN TO BE PROVIDED WITH THE P-TRAP BEFORE CONNECTION TO THE
DRAINAE NETWORK
7. THE EXHAUST AIR IS AS PER ASHRAE 62.1 AND SBC 501 REQUIREMENTS
8. CDP PIPE MATERIAL SHALL BE PVC SCH 40
9. GI DUCTING WHERE APPLICABLE TO BE AS PER SMACNA STANDARDS
10. PACKAGE UNITS TO BE PROVIDED VIBRATION ISOLATORS