ENR-PRD-11

FUNCTIONAL TESTS PLC BIO-SEA version B


14/10/2014

IDENTIFICATION

Project_Hull Number A613893_C-1700 Filter Model FILTREX


BSEA CODE BSEA009959 Motors Qty 1
BIO-SEA MODEL BIO-SEA 200 Remote Control NA

POWER CABINET USED FOR TEST CONTROL CABINET TO BE TESTED

DESIGNATION A1 DESIGNATION A0
PART NUMBER ASM009365 PART NUMBER ASM009206
SERIAL NUMBER 613893004 SERIAL NUMBER 613893003
Reference Document : INS-PRD-15 Program Version 1.28

M Manual mode : Functional Tests PLC (datalog events without datas)

P001 P101 M101 M102 M103 M104 Comments and solutions if faulty
M.1 Check Pumps & Motors
OK OK OK NA NA NA

Y005 Y006 Y007 Y008 Y009


M.2 Check Valves / UV
OK OK OK OK OK

Y101 Y102 Y103 Y104 Y105 Y106 Y107


M.3 Check Valves / Filter
OK OK OK OK OK OK OK

UV Lamp / Ballast tested UV 1 / Ballast x.1 UV2 / Ballast x.2

M.4 Communication Ballast / UV Lamp OK OK


Ignition UV lamp + Full Power OK OK
(22000 W)

Release Release
Test displays and alarm Reading Comments and solutions if faulty
Warning Alarm
UV Sensor OK OK OK

M.5 Temperature Sensor OK OK OK

Flowmeter Sensor OK OK OK

Alarm thermostat cabinet OK OK OK

A Automatic Mode : Functional Tests PLC

Ballasting Mode Deballasting Mode Remote Mode


OK / OK / OK /
Comments Comments Comments
NOT OK NOT OK NOT OK

A.1 Valves Position / PID OK OK OK

A.2 Release backwash OK OK

A.3 UV Lamp Ignition OK OK OK


Display values ​of sensors on screen
A.4 OK OK OK
PROCESS
A.5 Display Curves (3) OK OK OK

A.6 UV Value stabilisated (on screen) OK OK OK

OK /
Comments and solutions if faulty
NOT OK
Start cleaning at the end of cycle (System in
A.7 OK
position OFF)
A.8 Events on PLC display OK

A.9 Alarm history on PLC display OK

A.10 Storage datas PC BIO-UV (File prod) OK

P Electric Measures on PHASES A

OK /
Comments and solutions if faulty
NOT OK
Measure current on each phase (I). Store data on file ENR-PRD-09 (data for each power
P.1 OK
cabinets)
Measure voltage on each phase (Lx-Ly). Store data on file ENR-PRD-09 (data for each
P.2 OK
power cabinets)

DATE : 14/10/2014 CONTROLLER : H RUIZ

File : ENR-PRD-11 Functional Tests PLC BIO-SEA - BSEA009959 / Functional Tests