BLUPLANET ECOTECH PVT LTD

Dry bulb temp Dry bulb Wet bulb temp Wet bulb Dew point
Sr. no Location RH (%) Grains/lb
( deg C) temp( deg F) ( deg C) temp( deg F) (deg F)
1 Inside of cold room 5.5 41.9 5 41 93.00 39.27 39
2 Ambient 23 73.4 22.50 72.5 94.00 128.24 72
3 Attick area 24 75.2 23.00 73.4 91.00 130.90 73
4 Panel surface Top side-68.9 deg F Bottom side-44.24 deg C

Conclusion-
It is very clear from the chart dew point of air in attick area ( area between ceiling & slab of 2 mtr ht)is (73 deg F) & outer
surface temp. of panel is (68.9 deg F), it means heavy condensation will take place unless untill (73 deg F) brought down
to (68.9 deg F).
This can only be possible by ventilation & air movement in attick area.
Dry bulb temp Dry bulb Wet bulb temp Wet bulb
Sr. no Location RH Grains/lb Dew point
( deg C) temp( deg F) ( deg C) temp( deg F)

1 Inside of cold room 5.5 41.9 5 41 93.00 39.27 39


2 Ambient 23 73.4 22.50 72.5 94.00 128.24 72
3 Attick area 24 75.2 23.00 73.4 91.00 130.90 73
4 Panel surface Top side-20.5 deg C Bottom side-6.8 deg C
5 Air lock 20.5 68.9 18.50 65.3 81.00 94.85 63.5