GENERAL

1.1 Scope
This calculation is in support of the design of the Retaining Wall for GISTET 500kV
PAITON type 1 Meter
1.2 Codes, Standard & References

International Code
ASCE 7-05 : Minimum Design Loads for Buildings and Other Structures
UBC - 1997 : Unit Building Code

Indonesian Code
SNI 03-1726-2012 : Seismic Resistance Design Code for Houses and Building Guide
SNI 03-2847-2013 : Requirement of Concrete Structure for Houses and Building

Book References
Braja M. Das : Principles of Foundation Engineering

1.3 Units
Metric Units are used unless noted otherwise.

1.4 Design Data and Criteria


a) Safety Factor and Reduction Factor
Safety factor of Stability
Overturning SFo = 2.00
Sliding SFs = 1.50

b) Strength Reduction Factor


Tension-controlled section (ACI 9.3.2.1) = 0.90
Shear and Torsion (ACI 9.3.2.3) = 0.75

1.5 Major Material


a) Stone Mansiry
3
- Density = 2.20 gr/cm

b) Soil
Soil Parameter
3
- Density saturation = 14.42 gr/cm
- Specific gravity (Gs) = 2.58
- Friction Angle = 40.8 °
2
- Cohesion = 0.59 kg/cm

2. ANALYSIS METHOD
a. Calculate all loads acting on the structure includes vertical loads due to self weight of concrete's
structure, horizontal loads due to active soil pressure, vertical and horizontal loads due to
uniform loads on the ground.
b. Calculate internal force at Retaining Wall including maximum horizontal load, maximum vertical
load, and maximum moment load.
c. Calculate allaowable soil bearing capacity
d. Check stability of Retaining Wall including overturning moment, sliding and bearing capacity
3. CALCULATION

3.1 Calculation of Soil Bearing Capacity


Please refer to Attachment B

3.2 Calculation of Retaining Wall


Please refer to Attachment C

4. CONCLUSION

Based on detail calculation retaining wall in Attachment C, the desain of Retaining Wall
should be design as follow: